Eaton
®
Power Xpert
®
9395C UPS Installation and Operation Manual P-164000821—Rev 01
www.eaton.com/powerquality
6-1
Chapter 6
Understanding UPS Operation
6.1
UPS System Overview
The Eaton Power Xpert 9395C-1100 UPS is a continuous-duty, solid-state, transformerless (at 480 Vac),
three-phase, true online system that provides conditioned and uninterruptible AC power to the UPS system's
output and critical load.
The basic system consists of a rectifier, battery converter, inverter, monitoring/operation control panel,
integrated communication server, and digital signal processor (DSP) logic. Figure 6-1 shows the main elements
of the UPS system.
If utility power is interrupted or falls outside the parameters specified in Chapter 10, “Product Specifications”
the UPS uses a backup battery supply to maintain power to the critical load for a specified period of time or
until the utility power returns. For extended power outages, the UPS system allows you to either transfer to an
alternative power system (such as a generator) or shut down your critical load in an orderly manner.
Figure 6-1. Main Elements of the UPS System
Battery
Battery
Breaker
Battery
Converter
Input
Contactor
K1
AC Input to
Rectifier/
Charger
AC Input to
Bypass
Power Module
Inverter
Rectifier
Digital
Metering
Static
Switch
AC Output
to Critical
Load
UPS Cabinet
Battery System
Summary of Contents for 9395C-1000/1000
Page 2: ......
Page 23: ...Section I Installation ...
Page 24: ......
Page 93: ...Section II Operation ...
Page 94: ......
Page 155: ......
Page 156: ... P 164000821 1 P 164000821 1 ...