Installing Options and Accessories
Eaton
®
Power Xpert
®
9395C UPS Installation and Operation Manual P-164000821—Rev 01
www.eaton.com/powerquality
5-5
Figure 5-3. Remote Monitor Panel II and Relay Interface Module II Terminal Locations
Figure 5-4. Remote Monitor Panel II, Relay Interface Module II, or Supervisory Contact Module II Wiring
Terminal TB1
Signal Connections
from the UPS
Ground
Terminal
Terminal TB3
120 Vac Power
UPS Can Card J3
120 Vac from
Critical Bus
(Customer
Supplied)
Line
Neutral
Twisted Pair
Ground Terminal
RMP II, RIM II, or SCM II
Table 5-2. RMP II, RIM II, or SCM II Wiring Terminations
From
UPS CAN Card
To
RMP II, RIM II, or SCM II
Tightening Torque
Nm (lb in)
Remarks
J3–6 (TX)
TB1–5 (RDX*)
0.9 (8)
Use twisted pair
J3–7 (TX)
TB1–4 (RDX)
0.9 (8)
N/A
TB3 Line
0.9 (8)
N/A
TB3 Neutral
0.9 (8)
N/A
Ground Terminal
2.7 (24) Maximum
Summary of Contents for 9395C-1000/1000
Page 2: ......
Page 23: ...Section I Installation ...
Page 24: ......
Page 93: ...Section II Operation ...
Page 94: ......
Page 155: ......
Page 156: ... P 164000821 1 P 164000821 1 ...