OPERATION
Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide
S
164201642 Rev C
www.eaton.com/powerquality
79
Option 1:
For 24V EMO scheme, connect 2226Vdc/Vac source
across 24V EMO (TB4) terminal strip. Do not apply power to unit
yet.
Option 2:
For standard REPO/REMO scheme, replace jumper on
remote EMO switch (TB5) terminal strip with a N.C. EMO switch.
Unirom UPS/PFU startup procedures
Startup for normal operating mode.
1.
Make sure the EMO button has been released. For standard
REPO/REMO scheme, also ensure that the remote EMO switch
has been released (contact closed).
2.
Close CBEMO.
3.
Close CB1.
4.
Close CB2 if internal battery or Ultracapacitors are used OR close
battery breaker in EBC if EBC is used.
5.
On UPS display, turn UPS on.
6.
After UPS has been turned on, close CB3.
Additional steps if 24V EMO scheme is used:
1.
Turn on the 2226Vdc/Vac power supply. CBEMO shall trip while
the UPS operates normally. The EMO circuit is now active.
NOTE
In a customer application, this 2226Vdc/Vac source typically comes from the
distribution/load connected downstream of the UPS. When this 2226Vdc/Vac source is lost
for any reason, the operator should cutoff all input and output power to /from the UPS.
UPS/PFU behavior with custom input/output connection
box for Unirom
Standard behavior under normal operating mode regardless of remote
EPO/EMO scheme.
NOTE
Pushing EMO switch trips CB1, CB2 and CB3.