operating environment must meet the height, clearance, and environmental
requirements specified.
4.3.1
Environmental and installation considerations
The UPS system installation requires a TN, TT or IT power distribution system
(the IT distribution system shall include a neutral wire).
The UPS system installation must meet the following guidelines:
• The system must be installed on a level floor suitable for computer or
electronic equipment. The floor must be suitable for heavy weight and
wheeling.
• The system must be installed in a temperature and humidity controlled
indoor area that is free of conductive contaminants.
• The cabinet can be installed in line-up-and-match or standalone
configurations.
If you do not obey these guidelines your warranty may become void.
CAUTION
Do not stack anything on top of the UPS cabinet.
Do not stack the UPS 91PS/93PS C-model cabinet on top of any other similar
cabinet(s).
If installed on a shelf, use suitable supports to prevent the UPS from tipping
or dropping.
The UPS equipment operating environment must meet the weight requirements
shown in Table
, and the size requirements shown in Table
Table 7: Dimensions
C-model 8-20 kW
[mm]
15/20 kW frame
[mm]
30/40 kW frame
[mm]
Shipping dimen-
sions (WxDxH)
540 x 857 x 705
540 x 857 x 1460
750 x 820 x 1975
Cabinet dimensions
(WxDxH)
335 x 750 x 645
335 x 750 x 1300
480 x 750 x 1750
Table 8: UPS cabinet weights with cardboard packaging
C-model 8-20 kW
frame
15/20 kW
frame
30/40 kW
frame
Shipping weight
98 kg
293 kg
558 kg
Installed weight
86 kg
280 kg
532 kg
Floor loading
310 kg/m
2
1,007 kg/m
2
1,478 kg/m
2
Eaton 91PS/93PS UPS 8–40 kW
User's and installation guide
©
Eaton Corporation plc 2018. All rights reserved.
Revision: 005
Document ID: P-164000493
35 (117)