8-10 kVA, 50/60 Hz (1-phase input) &
8-15 kVA, 50/60 Hz (3-phase input)
P-164000341
User's Guide
Revision 1
3.
Turn the battery breaker
F1
and the rectifier input breaker
F2
to the ON position.
4.
Use the UPS LCD commands to turn the UPS ON and wait until it is fully started. Make sure
the UPS is not displaying any alarms. You may verify the output voltage from the meters of the
LCD display.
5.
Use the UPS LCD commands to transfer the UPS to static bypass mode. Remember to verify
the transfer before proceeding to the next step.
6.
Turn the
S1
bypass switch to OFF position to connect the UPS output to the load and to
disconnect the mechanical bypass output:
7.
Use the UPS LCD commands to transfer the UPS to Normal mode.
8.
The UPS is now in the Normal mode, see below:
9.3.2 Maintenance bypass switch operation
NOTE
The MBS consists of three switches and failure to understand the correct sequence may drop
the critical load.