7.5 Trouble shooting 

Displayed on LCD 

Audible Alarm Alarm Description 

What You Should Do 

Output Overload 

Two Beeps per 
second 

The UPS is overloaded (in 
Line Mode). Your 
equipment needs more 
power than the UPS can 
provide. The UPS operates 
in bypass. 

Shut off the least important 
equipment connected to the 
UPS. If this solves the 
overload problem, the UPS 
will switch from bypass back 
to normal operation. 

Battery Test 

No Beeps 

The UPS is doing a battery 

test. 

No action needed. The UPS 

will return to normal operation 

when it successfully completes 

the battery test. 

Over-Charge 

Constant beep 

Batteries are overcharged. 

Turn off protected loads. Turn 
off UPS and call your local 
dealer 

Low Battery 

2 beeps every 
5seconds 

The unit is operating on 
Battery Power and will shut 
down soon due to very low 
battery voltage 

The unit will restart 
Automatically when 
acceptable power returns. 

On-Battery 

Once every 5 
seconds 

The unit is operating on 
Battery Power. 

Save your data and perform a 
controlled shutdown. 

Charger Failure 

Constant beep 

Charger has failed. 

Phone the local dealer 

Over-Temperature 

Constant beep 

High ambient Temperature.

Make sure the unit’s fans and 
vent holes are not blocked, and 
make sure the ambient 
surrounding temperature is not 
above 40 degree C. If these 
conditions did not solve the 
problem, call your service 
representative.  

Output Short 

Constant beep 

Output short circuit 

Call the Local dealer 

High output Voltage 

Constant beep 

High output voltage 

Call the Local dealer 

Low Output Voltage 

Constant beep 

Low output voltage 

Call the Local dealer 

 Bus Fault 

2 Beeps per 
second 

High internal DC bus 
Voltage. 

Turn off protected loads. Turn 
off UPS and call your local 
dealer 

Site wiring Fault 

1 Beep per 
second 

Voltage detected Between 
Neutral and Ground 

UPS mains connector polarity 
Wrong. Rotate the connector 
(Schuko). UPS installed to 
mains supply without ground. 
See page 15 on how to disable 
the Site wiring alarm 

Line abnormal 

1 Beep per 
second 

Wrong AC Line backed up 
during auto restart 

 

 

25

8. Maintenance 

With a minimal amount of maintenance, you can expect the UPS to application, otherwise 
consider changing the batteries. have a long life free of trouble. The most critical issues for 
the reliability of the UPS are environmental issues. Ensure that the temperature and humidity 
are always according to specifications and keep the area around the unit clean and dust free. 

At a temperature of 25°C, the typical battery lifetime is 4 years. 

Also check at regular intervals of 6 to 12 months whether the back-up time of the battery is 
adequate for its 

8.1 Replacing batteries 

The batteries may be replaced without having to turn the UPS off or disconnecting the load 
due to the hot-swappable battery feature. 

 

WARNING! 

Batteries may cause electrical shock or burn from high short circuit 

currents. Please observe the following precautions: 1. Remove jewelry and metal 
objects such as watches and rings. 2. Use tools that have insulated handles. 3. Keep 
tools and other metal objects from contacting and away from the batteries. 

ELECTRIC ENERGY HAZARD. Do not attempt to rewire, alter, or change any 
battery wiring or connectors. Attempting to make such alterations can cause 
injury. 

Replace the batteries with the same number and type as originally installed 
batteries. 

DO NOT DISCONNECT the batteries while UPS is in Battery mode. 

  Replacing batteries (700 - 3000 VA) 

 

 

 

 

 

 

 

 

 

 

 

Summary of Contents for 700VA

Page 1: ...easures z Place the receiving antenna in a separate location or orientation z Ensure a greater distance is achieved between the receiver and the equipment z Ensure that your equipment is connected to...

Page 2: ...isk of electric shock do not remove cover No user serviceable parts inside Refer servicing to qualified service personnel CAUTION Non isolated Battery supply Risk of electric shock battery circuit is...

Page 3: ...ly detailed requirements of the UPS units are described herein and installation must be carried out in accordance with this manual Electrical installations must also carefully follow local legislation...

Page 4: ...eports any problems on the LCD display An advanced battery management system always monitors the conditions of the batteries sends any forewarnings if replacement is needed Otherwise every 30 days of...

Page 5: ...operations are to be performed exactly as instructed in this manual The greatest care possible must be taken for any of these operations and any change thereof may prove very hazardous to the operato...

Page 6: ...he following illustration Vertical Installation Wall mounted installation 7 Installation with accessories of Rack mounted types Please install the types of units according to the following illustratio...

Page 7: ...8 Installation with accessories of Stack types Please install the types of units according to the following illustration Stack installation 9 5 2 Rear panel views 700 1 5KVA REAR PANEL...

Page 8: ...10 2K 3KVA REAR PANEL 11 RM 1U 700 1KVA Rear Panel...

Page 9: ...12 RM 2U 700 1K 1 5KVA Rear Panel 13 RM 2U 2K 3KVA Rear Panel...

Page 10: ...instantly shows a Site Wiring Fault rotate the connector Schuko see chapter 7 4 z After charging connect the loads to the UPS see the example in fig 3 z Do not connect any devices that have the possi...

Page 11: ...ctions 2 TxD Output TxD Output 3 RxD Input RxD Inverter Off Input 5 Common Common 6 Output Ac Fail Output 8 Output Low Battery Output 9 Output 12 VDC Power Caution Max rated values 12Vdc 17 USB port o...

Page 12: ...off the UPS 2 is a Enter button Use this button to check content of UPS and the method is listed below a Push the button at least 2 seconds to check content of UPS Each content can be displayed by pr...

Page 13: ...URE xxC Shows approximate ambient temperature BAT PACK NUM x Shows External Battery Pack Number RATING xxxxVA Shows UPS Rating CPU VERSION xx x Shows CPU Version 21 UPS configurations 1 Various settin...

Page 14: ...32 communication RS232 Control Set RS232 communication enable or disable Enable Disable Enable 23 Manual test of the UPS Manual UPS or Manual Battery tests can be conducted from the UPS configuration...

Page 15: ...er second High internal DC bus Voltage Turn off protected loads Turn off UPS and call your local dealer Site wiring Fault 1 Beep per second Voltage detected Between Neutral and Ground UPS mains connec...

Page 16: ...144 VAC Frequency 50 60 Hz Auto selection Frequency window from mains 45 65 Hz Synchronization window 3Hz Input current 700 VA 5 8A 1000 VA 8 2A 1500 VA 12 4A 2000 VA 16 5A 3000 VA 24 7A Input Power...

Page 17: ...attery mode 700 1000 VA 50 db normal and battery mode 1500 3000 VA 29 STANDARDS Safety EN50091 1 1 Emissions EN50091 2 Immunity EN50091 2 B 700 1500VA A 2K 3KVA HV Model OUTPUT POWER 700VA 490 W 1000V...

Page 18: ...o 90 3 hours to 90 3 hours to 90 Dimensions W x D x H mm 152 x 420 x 238 152 x 420 x 238 152 x 420 x 238 225 x 425 x 360 225 x 425 x 360 Weight kg 13 5 16 2 17 31 6 33 31 19 Rack mount Model 2U OUTPUT...

Page 19: ...20 x 238 152 x 420 x 238 225 x 425 x 360 225 x 425 x 360 Dimensions W x D x H mm RM2U 428 x 425 x 84 428 x 425 x 84 428 x 425 x 84 428 x 610 x 84 428 x 610 x 84 Tower 21 21 21 42 42 Weight Kg RM2U 22...

Reviews: