8
Instruction Booklet
IB0191004EN
Effective June 2020
EAFR-110PLV current and arc light
sensor relay user manual
EATON
www.eaton.com
3.6 Dipswitch settings
The EAFR-110PLV functionality, such as tripping logic, is configured
using the dipswitch settings. The relay contains two switch groups
SW1 and SW2 (see Figure 4). The dipswitches are located at the
back of the relay for easy access.
Figure 4. EAFR-110PLV dipswitches SW2 and SW1.
Different trip configurations can be easily programmed by selecting
the appropriate dipswitch settings. The most convenient way to
set the EAFR-110PLV single relay or more complex arc protection
system is to use the Standard Arc Schemes for Arc Quenching
Switchgear. For different arc schemes applications, see the Standard
Arc Flash Relay Schematics for Arc Quenching Switchgear manual
(IB0191003EN).
Tripping may be selected based on arc light only or current thresh-
olds. Other tripping criteria, such as under-voltage or similar, may
be applied instead of over-current as well using binary inputs. The
circuit breaker failure protection (CBFP) configuration may also be
enabled using the dipswitches. See Table 2: EAFR-110PLV Dipswitch
SW1 Setting and Table 3: EAFR-110PLV Dipswitch SW2 Setting for
details of settings.
Table 2. EAFR-110PLV dipswitch SW1 setting.
Dipswitch
Function selection
ON (Left Position)
OFF (Right Position)
8
S1: Light / Light + Current
Sensor channel 1 trip criteria.
Trip on light only.
Trip on light and over-current. Both signals are required
simultaneously to trip.
7
S2: Light / Light + Current
Sensor channel 2 trip criteria.
Trip on light only.
Trip on light and over-current. Both signals are required
simultaneously to trip.
6
SX: Light / Light + Current.
Sensor channels 3 - 5 trip criteria (channel 3 in
EAFR-110F)
Trip on light only.
Trip on light and over-current. Both signals are required
simultaneously to trip.
5
a/b
Selection of standard arc configuration type.
Standard arc configurations type a. Standard arc configurations type b.
4
Configuration select
Selection of standard arc configuration.
Refer to IB0191003EN.
Refer to IB0191003EN.
3
Configuration select
Selection of standard arc configuration.
Refer to IB0191003EN.
Refer to IB0191003EN.
2
Configuration select
Selection of standard arc configuration.
Refer to IB0191003EN
Refer to IB0191003EN
1
Configuration select
Selection of standard arc configuration.
Refer to IB0191003EN
Refer to IB0191003EN.
Table 3. EAFR-110PLV dipswitch SW2 setting.
Dipswitch
Function selection
ON (left position)
OFF (right position)
8
T1/T2: latch/non-latch
Latch or non-latch for trip relays T1 and T2.
T1 and T2 operate as latched.
T1 and T2 operate as non-latched.
7
HSO: latch/non-latch
Latch or non-latch for HSO1 and HSO2.
HSO1 and HSO2 operates as latched. HSO1 and HSO2 operates as non-latched.
6
S1: TBD
Reserved for future use.
N/A
N/A
5
S5: N/A
Arc quenching device output
N/A
Enables arc quenching device output. Switch should
always be set to this position.
4
Fast / CBFP
Selection of trip relay T2 function.
Trip relay T2 will have 7 ms trip time. Trip relay T2 will work as CBFP relay. If any sensor
or light input (BI2) is activated for more than the
set CBFP time (100 or 150 ms), the CBFP function
activates the trip relay T2 and binary output BO1.
Note:
Master trip command (BI2, see dipswitch 4)
will not activate T2 when in CBFP mode
3
100 / 150 ms
CBFP time setting.
CBFP time is set to 100 ms.
CBFP time is set to 150 ms.
2
Phase sensor: 1A / 5A
Phase currents IL1, IL2, and IL3 nominal current
selection.
1A nominal current.
5A nominal current.
1
Earth Ground sensor: 1A / 5A
Earth current ground sensor nominal current
selection.
1A nominal current.
5A nominal current.