Figure 1. Cutaway illustration shows design detail and dimensions. Catalog PDBA625 shown.

otee:

N

Dimensions given are for reference only.

13.3 (337.8)

8.7 (220.9)

7.2 (182.9)

Table 1.  Voltage Ratings and Characteristics

Description

kV

Standard Voltage Class

25

Maximum Rating Phase-to-Phase (LRTP 200 A interface only)

26.3

Maximum Rating Phase-to-Ground

15.2

AC 60 Hz 1 Minute Withstand

40

DC 15 Minute Withstand

78

BIL and Full Wave Crest

125

Minimum Corona Voltage Level

19

Voltage ratings and characteristics are in accordance with IEEE Std 386™-2006 standard.

Table 2.  Current Ratings and Characteristics

Description

Amperes

200 A Interface*

Continuous 

Switching

200 A rms

10 operations at 200 A rms at 26.3 kV

Fault Closure 

10,000 A rms symmetrical at 26.3 kV after 10 switching 

operations for 0.17 s

Short Time 

10,000 A rms symmetrical for 0.17 s 

3,500 A rms symmetrical for 3.0 s

Current ratings and characteristics are in accordance with IEEE Std 386™-2006 standard.

600 A  

PUSH-OP 

BUSHING 

LOCATING 

PINS

HOTSTICK 

PULLING EYE

CATCH ASSEMBLY 

Prevents unit from falling off 

of PUSH-OP mating apparatus 

upon removal.

COPPER PROBE 

Field Replaceable Tin-Plated 

Copper Probe ensures 

reliable electrical connection.

GROUNDING LEAD 

48 inch #14 Stranded Plated 

Copper Ground Lead ensures 

deadfront construction and 

avoids low energy discharge 

from the molded semi-

conducting shields.

200 A 

LOADBREAK 

REDUCING TAP 

PLUG

2

Catalog Data 

CA650103EN

Effective September 2016

600 A 25 kV class PUSH-OP insulated adapter cap

 www.eaton.com/cooperpowerseries

*  If available system fault current exceeds 10 kA, current-limiting fusing must be used upstream,  

otherwise fault close and short time ratings of the 200 A interface will be exceeded.