6. Appendices
6.1 Technical specifications
Tower
5P 650i
5P 850i
5P 1150i
5P 1550i
Rack
5P 650i R
5P 850i R
5P 1150i R
5P 1550i R
Output Power
@ 230 V
650 VA
420 W
850 VA
600 W
1150 VA
770 W
1550 VA
1100 W
Output Power
@ 208 V
585 VA
378 W
765 VA
540 W
1035 VA
693 W
1395 VA
990 W
Output Power
@ 200 V
585 VA
378 W
765 VA
540 W
1035 VA
693 W
1395 VA
990 W
AC Input power
•
Rated input voltage
Single phase 200-240 V
•
Input voltage range
160 to 294 V
(1)
•
Input frequency
range
47 to 70 Hz (50 Hz system), 56,5 to 70 Hz (60 Hz system)
(2)
Output on battery power
•
Voltage
200/208/220/230/240 V (-10/+6 %)
(3)
•
Frequency
50/60 Hz ±0.1 Hz
Battery (sealed lead acid, maintenance free)
•
Standard
Tower
1 x 12 V
9 Ah
2 x 12 V
7 Ah
2 x 12 V
9 Ah
3 x 12 V
9 Ah
Rack
2 x 6 V
9 Ah
4 x 6 V
7 Ah
4 x 6 V
9 Ah
6 x 6 V
9 Ah
Environment
•
Operating
temperature range
0 to 35 °C
0 to 40 °C
•
Storage
temperature range
-15 to +50 °C
•
Relative humidity
0 to 90 % (without condensation)
•
Noise level
< 40 dBA
(1)
The high and low thresholds can be adjusted using UPS settings (up to 150-294 V).
(2)
Up to 40 Hz in low -sensitivity mode (programmable using UPS settings).
(3)
Adjustable to 200/208/220/230/240 V, must be set to the identical AC power source value.
When the appliance is used in EU area, use an external circuit breaker in front of line with rating 16 A,
250 V which is IEC/EN 60898-1 standard compliant;
When the appliance is used in America area, use an external circuit breaker in front of line with rating 20 A,
250 V.
This product is designed for IT power distribution system.
Filter
Transformer
"AVR"
Charger
Inverter
Battery