Step 8 - While holding the marker tip on the tape, close
the breaker (Figure 6-12).
Step 9 - Move the marker back and forth horizontally
approximately 15
o
in both directions to create a line on
I.B. 32-255-1G
Page 40
Effective 12/02
Step 5 - Mount the transparent CloSure
TM
Test Tool with
two bolts and washers. Refer to Figures 6-19, 6-20 and
Table 6.4 for appropriate mounting holes
. Hand tighten
the bolts (Figures 6-9, 6-10, 6-19 and 6-20).
Step 6 - A Sanford
®
Sharpie
®
black fine point perma-
nent marker, item no. 30001, is recommended for this
next step. Place the marker tip in the proper hole (“C”).
Refer to Figure 6-19 and make a heavy mark on the
tape as shown in Figure 6-10.
Step 7 - Charge the closing springs with the mainte-
nance tool. Continue charging the closing springs
until a “click” is heard and the status indicator shows
“Charged” (Figure 6-11).
Figure 6-11 Manually Charging Closing Springs
Figure 6-13 Top View of Cam and Marker Interface
Figure 6-14 Move Marker 15
o
to Right
Figure 6-12 Manually Closing Circuit Breaker with
Marker in Hole “C”.
C
the tape that identifies the closed rest position (Figures
6-13, 6-19 and 6-15).
Cam
15
o
15
o
Marker
Closure
TM
Tool
Figure 6-10 Attaching CloSure