Page 36
I.B. 70A2580H02
Effective November 2012 Style
70A2580H02
Printed in USA
6-12 TROUBLESHOOTING CHART
SYMPTOM
INSPECTION AREA
PROBABLE DEFECTS
Undesirably Closes
•
Control Circuit
• Close Circuit
(CS/C Getting Shorted)
•
Mechanism
• Close Release Latch
(Fails to reset)
• Close Floor Tripper
(Fails to reset)
Fails To Trip
• Control Circuit
• Control Power
(Fuse blown or switch off)
• Secondary Disconnect
• Auxiliary Switch
(a contact not making, poor or burned)
• Trip Coil
(Burned or open)
• Terminals and Connections
(Poor or burned or open)
• No Trip Sound
• Trip Mechanism
• Trip Clapper
(Jammed)
• Trip Mechanism
• Trip Bar, Trip Latch
(Jammed)
• Pole Shaft
(Jammed)
• Operating Rod Assembly
(Broken or pins out)
• Trip Sound
But No Trip
• Vacuum Interrupter
(One or more welded)
Undesirably Trips
• Control Circuit
• Control Power
(CS/T Switch, remains made)
• Mechanism
• Trip Coil Clapper
(Not resetting)
• Trip Bar or Trip Latch
(Poor engagement of mating
or worn surfaces)
• Trip Bar Reset Spring
(Loss of torque)
• Tip of Main Cam Chipped or Worn
(Trip after Closed Breaker is Charged)