I.B. 70A2580H02
Page 33
Effective November 2012
Figure 6-16 Illustrative Testing Tape Sample
Figure 6-17 Front View of CloSure
TM
Tool Showing
Mounting/Testing Hole Locations (6352C49H01)
Step 13 -
Evaluate the CloSure
TM”
performance by
comparing the test tape with the illustrations in Figure
6-
16.
If the marking is similar to
6-16A
,
measure the over
travel “x”: If “x” is greater than or equal to 0.6 inches, the
circuit breaker performance is satisfactory. If “x” is less
than 0.6 inches or if the marking is similar to
6-16B
or
6-
16C
,
contact your local Eaton sales representative or
distributor for service or go to www.EatonElectrical.com
for more Information about our products and support.
Figure 6-18 Typical Circuit Breaker Front View with
CloSure
TM
Tool Attached (approximate mechanism
chassis width)
Breaker
Line
Approximate
Mechanism
Cabinet
Width (inch)
Upper
Mounting
Hole
Lower
Mounting
Hole
Marker
Placement
Hole
VCP-Wind
33 A2 B2 C6
Table 6.3 Closure
TM
Tool Mounting/Testing Locations
by Circuit Breaker Type
Step 14 -
Remove the CloSure
TM
Tool. Reassemble
the front cover onto the circuit breaker. Return the
circuit breaker to its original configuration and setup.