Installation, Operation & Maintenance Manual

 

Control Panels for Automatic Self-Cleaning Strainers

 

Model 596 and Model 2596

 

 

 

CONTROL PANEL DESCRIPTION

 

The ACS Series Control Panel is a rugged electro-mechanical 
unit made with industrial grade components and suitable of 
outdoor (NEMA 4) installation. The enclosure houses all 
components, is compact in size and is offered in two 
configurations:

 

 

ACS-2S

: All standard features and includes motor and starter 

for backwash arm for 120 volt-single phase power supply

 

ASC-3S

: All standard features plus motor starter for backwash 

motor and transformer for 460 volt-3 phase power supply

 

 

The ACS line of control panels allows operation either in the 
Manual or Auto modes. In the Manual mode, the strainer will 
continuously backwash. In the Auto mode, the strainer is 
allowed to backwash according to the preset timing cycle or 
when the differential pressure switch is activated.

 

 

NOTE: The customer determines the timing cycle 
length and changes it as required.

 

 

 

The control logic protects the strainer from sudden high 
quantities of solids or an improperly adjusted timer cycle. 
Whenever the differential pressure switch is activated, it 
overrides the timer circuit and opens the backwash valve.

 

 

 

NOTE: An On-Off cycling of the backwash 
valve will occur.

 

 

 

If frequent activation of the differential pressure switch is 
evident, the timer cycle must be re-set to backwash more 
often.

 

 

The panel door locates the selector switch and the indicating 
lights. The weatherproof rating is maintained as long as the 
lamp lenses are not broken and are not removed.

 

 

 

 

 

 

Summary of Contents for 2596

Page 1: ... Timed Cycle 2 Valves 2 Valve Selection 2 Backwash Blow Down Drain Valve 3 Electric Actuators 3 Pneumatic Actuators 3 Differential Pressure Switches 4 Switch Description 4 Mounting Piping and Wiring 4 Adjustment 4 Control Panel 5 Description 5 Cycle Time Sequence 5 Standard Features 5 Operating Modes 6 Changing Backwash Timer Settings 6 SmartWire DT Error Messages 7 System Error Messages 7 Electri...

Page 2: ...d protection and fused disconnect STRAINER MODE OF OPERATION AUTOMATIC BACKWASH TIMED CYCLE The preferred mode of operation for a self cleaning strainer is one where the control system will permit both intermittent and continuous backwash as required by operating conditions The drain line requires a blow down drain valve which may be manually operated Normal valve position is CLOSED The backwash l...

Page 3: ...PNEUMATIC ACTUATORS A double acting piston design that uses a clean air supply of 40 125 psi pressure powers the actuator properly Using an electric signal a solenoid pilot valve controls the air supply to the actuator Most actuators have pipe thread connections NPT located so that the solenoid valves may be mounted with minimal tubing runs Customer must run wiring and conduit from the control pan...

Page 4: ...ure connections furnished on the inlet discharge nozzles of the strainer as shown in Fig 1 Customer must supply and run wiring and conduit between the differential pressure switch and the control panel See Fig 2 for wiring connections DIFFERENTIAL SWITCH ADJUSTMENT While it is possible to use other equipment than what is described below any installation should have the items described here Equipme...

Page 5: ... supply The ACS line of control panels allows operation either in the Manual or Auto modes In the Manual mode the strainer will continuously backwash In the Auto mode the strainer is allowed to backwash according to the preset timing cycle or when the differential pressure switch is activated NOTE The customer determines the timing cycle length and changes it as required The control logic protects...

Page 6: ... closes then HIGH DIFFERENTIAL indicator illuminated HI DP alarm contact closes AUTO MODE Timer range limits for BACKWASH ON valve open is 1 to 1440 minutes Timer range limits for BACKWASH OFF valve closed is 1 to 1440 minutes CHANGING THE BACKWASH TIMER SETTINGS To change timer settings press ALT button Use the UP or DOWN arrow buttons to move the cursor to select lines BW Open SP or BW Close SP ...

Page 7: ...errors If a hardware error occurs the screen will display what device and node is damaged or disconnected If more than one node is damaged or disconnected the screen will cycle though all errors present SYSTEM ERROR MESSAGES Motor Overload If there is a motor overload the following message will flash on the screen Hi DP Backwash Hi DP backwash is indicated by the red LED and with a change of state...

Page 8: ...ge 8 of 9 Eaton Filtration LLC 44Apple Street Tinton Falls NJ 07724 www eaton com filtration Phone 732 212 4700 Installation Operation Maintenance Manual Control Panels for Automatic Self Cleaning Strainers Model 596 and Model 2596 ...

Page 9: ...ranca São Paulo SP 05038 001 Brazil Tel 55 11 3616 8461 For more information please email us at filtration eaton com or visit www eaton com filtration 2020 Eaton All rights reserved All trademarks and registered trademarks are the property of their respective owners All information and recommendations appearing in this brochure concerning the use of products described herein are based on tests bel...

Reviews: