background image

 

Instruction Book

 

 

                                                                                                                                                              

Effective: November 2017        Page 56 

 

 

For more information visit: 

www.Eaton.com

 IB131016EN 

Table 6.4 Troubleshooting Guide (continued on next page) 

Symptom 

Probable Cause 

Corrective Actions 

Circuit breaker undesirably opens 

Undervoltage release operates; 
voltage too low or zero. 

Check and correct the UVR supply 
voltage (85-110% rated voltage) 

Shunt Trip operates 

Check control signal(s) to shunt trip; 
correct if necessary 

Trip latch is defective 

Inspect latch condition and 
engagement before closing; consult 
Eaton service center 

Circuit breaker cannot be opened 
remotely, but can be opened locally 

Shunt trip control signal absent or 
too low 

Check supply voltage exceeds 
minimum of voltage range when 
signal is applied to shunt trip 

Shunt trip is faulty or improperly 
installed. 

Remove front cover; check voltage 
supplied to shunt trip; make sure 
shunt trip is seated and retainer 
snapped into place. Check for 
shunt trip motion; replace shunt trip 
if faulty 

Secondary contact wiring problem 

Make sure electrical pin and socket 
connectors are properly seated in 
molded plug. Verify proper wiring 

Circuit breaker cannot be opened locally 

OPEN pushbutton locked

 

Remove lock 

Faulty mechanism or one or more 
vacuum interrupter contacts welded 

Contact Eaton service center 

Circuit breaker makes no attempt to close 
with either local (manual) or remote 
controls; springs do not discharge 

Closing spring not fully charged 
(check SPRING CHARGED 
indicator) 

Charge spring manually; check 
voltage to electrical operator; 
replace electrical operator if faulty 

If equipped with undervoltage 
release, undervoltage release is not 
energized or is faulty 

Unplug undervoltage release from 
mounting deck and retry closing 
operation; if OK, check voltage 
supply to undervoltage release 
(>85%); replace undervoltage 
release if faulty 

Circuit breaker locked in OPEN 
position 

Check reason for lock 

Circuit breaker interlocked with 
another circuit breaker or device 

Check for presence of an 
interlocking scheme (cable interlock 
or key interlock); check to see if 
interlocked circuit breaker is 
CLOSED 

 
 
 

Summary of Contents for 150 VCP-T16

Page 1: ...Eaton com Instructions for the Use Operation and Maintenance of Types VCP T and VCP TR Vacuum Circuit Breakers IB131016EN Effective November 2017 VCP TR Fixed up to 25kA VCP T Drawout up to 25kA VCP TR Fixed up to 40kA VCP T Drawout up to 40kA ...

Page 2: ......

Page 3: ...HEIR NAMEPLATE RATINGS OPERATION OUTSIDE OF THESE RATINGS MAY CAUSE THE EQUIPMENT TO FAIL RESULTING IN DEATH BODILY INJURY AND PROPERTY DAMAGE ALL SAFETY CODES SAFETY STANDARDS AND OR REGULATIONS AS THEY MAY BE APPLIED TO THIS TYPE OF EQUIPMENT MUST BE STRICTLY ADHERED TO SERIOUS INJURY INCLUDING DEATH CAN RESULT FROM FAILURE TO FOLLOW THE PROCEDURES OUTLINED IN THIS MANUAL THESE CIRCUIT BREAKER E...

Page 4: ...erfaces 23 4 6 2 Circuit Breaker Positioning 24 4 6 3 Drawout Electrical Interfaces 26 4 6 4 Levering Circuit Breaker 28 SECTION 5 DESCRIPTION AND OPERATION 5 1 Introduction 31 5 2 Vacuum Interrupter Assembly 31 5 2 1 Contact Erosion Indicator up to 25kA 34 5 2 2 Contact Wipe and Stroke up to 25kA 34 5 2 3 Contact Wipe and Erosion up to 40kA 34 5 3 Stored Energy Mechanism 35 5 3 1 Manual Operation...

Page 5: ...Preferred Lifting Method Using Lifting Yoke To Lift 40kA Breaker 14 3 5 Front and Rear Views All VCP TR Fixed except 25kA 2000 2500A and all 31 5 40kA 16 3 6 Front and Rear Views All VCP T Drawout except 25kA 2000A and all 31 5 40kA 17 3 7 Front and Rear Views Drawout Cassette except 25kA 2000A and all 31 5 40kA 18 3 8 Front and Rear Views VCP T Drawout Breaker 25kA 2000A and all 31 5 40kA 19 3 9 ...

Page 6: ...ary Protective Hood in Place 37 5 15 Top View Secondary Connectors 43 5 16 Secondary Male Connector with Female Pins 43 5 17 Optional Terminal Block 43 5 18 AMP Secondary Wiring Removal Tool AMP 305183 43 5 19 Digitrip RMS 1 150Vi Programmable Trip Unit Installed in VCP T Circuit Breaker 44 5 20 Hand Held Tester 44 5 21 Through The Window Electrical Accessories 46 5 22 Shunt Trip Device 46 5 23 Sp...

Page 7: ...lable in voltage classes of 4 76 8 25 and 15 0 kV They are tested in accordance with ANSI C37 04 and C37 09 Table 1 1 1 1 VCP T and VCP TR Vacuum Breaker Ratings Refer to Tables 1 1 and 1 2 on pages 2 and 3 The circuit breaker s nameplate provides complete rating information Reliable control and protection for medium voltage equipment and circuits are achieved through the use of VCP T and VCP TR V...

Page 8: ...9 60 600 1200 1600 2000 2500 25 65 10000 10000 10000 10000 10000 50 VCP T32 and 50 VCP TR32 4 76 19 60 600 1200 2000 2500 31 5 82 10000 10000 10000 10000 50 VCP T40 and 50 VCP TR40 4 76 19 60 600 1200 2000 2500 40 104 10000 10000 10000 10000 75 VCP T16 and 75 VCP TR16 8 25 20 60 600 1200 1600 16 42 10000 10000 10000 75 VCP T20 and 75 VCP TR20 8 25 20 60 600 1200 1600 20 52 10000 10000 10000 75 VCP...

Page 9: ... 36 95 600 1200 1600 20 52 10000 10000 10000 150 VCP T25 and 150 VCP TR25 15 36 95 600 1200 1600 2000 2500 25 65 10000 10000 10000 10000 150 VCP T32 and 150 VCP TR32 15 36 95 600 1200 2000 2500 31 5 82 10000 10000 10000 10000 150 VCP T40 and 150 VCP TR40 15 36 95 600 1200 2000 2500 40 104 10000 10000 10000 10000 Use 15kV Breaker and Cassette when 95kV Impulse Withstand required Also 2 Second Short...

Page 10: ...Page 4 For more information visit www Eaton com IB131016EN 1 2 Types VCP T and VCP TR Outlines and Dimensions Circuit Breakers and Drawout Cassettes Figure 1 1 VCP TR Fixed Breaker Outlines in inches mm except 25kA 2000 2500A and all 31 5 40kA ...

Page 11: ...Instruction Book Effective November 2017 Page 5 IB131016EN For more information visit www Eaton com Figure 1 2 VCP T Drawout Breaker Outlines in inches mm except 25kA 2000A and all 31 5 40kA ...

Page 12: ...Instruction Book Effective November 2017 Page 6 For more information visit www Eaton com IB131016EN Figure 1 3 VCP T Breaker Cassette Outlines in inches mm except 25kA 2000A and all 31 5 40kA ...

Page 13: ...Instruction Book Effective November 2017 Page 7 IB131016EN For more information visit www Eaton com Figure 1 4 VCP TR Fixed Breaker Outlines in inches mm Refer to above Applicable Ratings Table ...

Page 14: ...Instruction Book Effective November 2017 Page 8 For more information visit www Eaton com IB131016EN Figure 1 5 VCP T Drawout Breaker Outlines in inches mm Refer to above Applicable Ratings Table ...

Page 15: ...Instruction Book Effective November 2017 Page 9 IB131016EN For more information visit www Eaton com Figure 1 6 VCP T Breaker Cassette Outlines in inches mm Refer to above Applicable Ratings Table ...

Page 16: ...Instruction Book Effective November 2017 Page 10 For more information visit www Eaton com IB131016EN REFER TO IL131031EN FOR VCP T T VAC 31 5kA 40kA 2000A Cassette Bus Bar Assembly Instructions ...

Page 17: ... use an isolation means and follow all lock out and tagging rules of the Local Electrical Codes and any and all applicable codes regulations and work rules Always ensure that drawout circuit breakers are in one of their designed cell positions such as Connect Test Disconnect or Remove A circuit breaker permitted to remain in an intermediate position could result in control circuits being improperl...

Page 18: ...circuit breaker is described in the next paragraph in detail Unpacking a drawout circuit breaker is also simple to accomplish and is not described here in detail Just proceed by carefully removing all packing material used for protection during shipment and the fasteners used to secure the drawout circuit breaker to its shipping pallet When ready to inspect and install the circuit breaker carefull...

Page 19: ...Instruction Book Effective November 2017 Page 13 IB131016EN For more information visit www Eaton com ...

Page 20: ...approximately 400 watts for each 100 cubic feet of volume is recommended with the heaters distributed uniformly throughout the structure near the floor Indoor storage should be in a building with sufficient heat and circulation to prevent condensation If the building is not heated the same general rule for heat as for outdoor storage should be applied THE CUSTOMER SHOULD READ AND UNDERSTAND THE MA...

Page 21: ...nd 150 VCP T25 600 1200 1600 2000 2500 168 170 172 342 346 245 247 249 432 NA 161 161 161 161 NA 50 VCP TR32 and 50 VCP T32 600 1200 1600 2000 2500 329 329 333 338 342 419 419 424 428 NA 301 301 301 301 NA 150 VCP TR32 and 150 VCP T32 600 1200 1600 2000 2500 333 333 338 342 346 424 424 428 432 NA 301 301 301 301 NA 50 VCP TR40 and 50 VCP T40 600 1200 1600 2000 2500 333 333 338 342 346 424 424 428 ...

Page 22: ...erface or Bottom Conductor 69C3008H03 11 Drive Insulator with Internal Contact Loading Spring Wipe Spring 16kA 69C3053G01 25kA 69C3053G03 12 Vacuum Interrupter Movable Stem 13 Rear Customer Mounting Holes 69C3010G01 Base Plate 14 Customer Earth Connection 69C3010G01 Base Plate 1 Horizontal Phase Barrier 95kV BIL Only 68B3016H02 2 Vertical Phase Barrier 95kV BIL Only 69C3027G01 3 Integral Lifting H...

Page 23: ...le Unit Assembly 67A3158 67A3159 or 67A3160 Depending on the kA and AMP Rating Contact your Eaton Sales or Local Eaton Rep for more information 10 Primary Disconnect Finger Cluster 1200 1250A Shown 1200 1250A 68B3031G01 600 630A 68B3031G02 11 Drive Insulator with Internal Contact Loading Spring Wipe Spring 16kA 69C3053G01 25kA 69C3053G03 12 Vacuum Interrupter Movable Stem 13 Cradle with Levering M...

Page 24: ... Primary Connection Pad 68B3219H01 11 Primary Insulating Tube Spout 70D3211H01 12 Safety Shutter Operating Arm 68B3332H01 13 Secondary Umbilical Cord Connector Cell Wiring Harness 69C3259G01 Male Connector Secondary Block 73477JAA01 14 Customer Earth Connection 69C3266H01 1 Automatic Primary Safety Shutters Closed Position 69C3219H04 2 Cradle Stop Hook Stop 68B3315G01 3 Mounting Holes Base Tray As...

Page 25: ... Pole Unit Molding Removable Cover 70D3251H02 8 Vacuum Interrupter Located Behind Removable Back Covers Part of Pole Unit 9 Cradle with Levering Mechanism 69C3305G11 10 Shoot Bolt Handle Part of 69C3305G11 11 Shoot Bolt Part of 69C3305G11 12 Push Pull Handle Part of 69C3305G11 13 Racking Screw Lock Plate Part of 69C3305G11 14 Levering Drive Nut Part of 69C3305G11 15 Integral Wheel 67A3201H01 Pin 6...

Page 26: ...anism 69C3287H02 10 Primary Insulating Tube Spout 69C3347G02 11 Safety Shutter Operating Arm 68B3298H03 12 Secondary Umbilical Cord Connector Male Connector 73477JAA01 13 Customer Ground Connection 69C3266H11 1 Automatic Primary Safety Shutters Closed Position 69C3288H04 2 Cradle Stop Hook Stop 68B3315G01 3 Mounting Holes Base Tray Assembly 70D3328G02 4 Rejection Interlock Pins Rej Pin Kit 68B3049...

Page 27: ...A10895G01 Supplied Lead Security Seals 4 Manual OFF Button 2A10895G01 WTU 2C12190G01 2C12190G02 5 Manual ON Button 2A10895G01 W O 2C12812H06 6 Manual Charging Handle 2C12297G01 13 Front Cover Mounting Hardware 7 Operations Counter 592C040H01 SPG Washer 70550AC10R 8 Nameplate Flat Washer 70540AK10R 9 Trip Unit Optional 67A3153XXX 67A3154XXX Bolt 70045BB0BG 10 Rating Plug 5720B93XXX O Ring 71070CA00...

Page 28: ... Both secondary connection devices are mounted at the top front of the circuit breaker Secondary contacts are dedicated and identified Refer to Figures 5 10 to 5 13 for secondary connection details NOTICE Refer to the circuit breaker weights in Table 3 1 to ensure that any table used for inspections is capable of supporting the circuit breaker 4 1 INITIAL INSPECTION Before attempting to use or put...

Page 29: ...LECTRICAL FAULT WHICH COULD RESULT IN DEATH BODILY INJURY AND OR EQUIPMENT DAMAGE Figure 4 2 Bottom View of VCP TR Circuit Breaker showing Mounting Holes As the circuit breaker is pushed into the structure the mating pins on the bottom of the circuit breaker move past a set of corresponding pins in the cassette if the circuit breaker and cassette are compatible If there is a mismatch between the c...

Page 30: ...ng the fixed primary disconnects The locking system is not automatically disabled when the breaker is being connected Consequently the lock must be removed prior to racking or damage to the shutter drive will result Handle Interlock Prevents racking in or removing a circuit breaker which is closed Hook Interlock Prevents a circuit breaker which is racked in from being inserted into a cassette Refe...

Page 31: ... the floor of the cassette in a guided manner Position the circuit breaker so that the two rear wheels begin to roll on the cassette s floor and then firmly push the circuit breaker into the cassette until the horizontal shoot bolts on either side of the breaker cradle contact the front of the cassette Figure 4 5 Care should be taken not to bind the secondary umbilical cord between the circuit bre...

Page 32: ...e made between the breaker and the cassette Refer to paragraph 4 6 3 for details on making secondary connections to the cassette Once the secondary connection is made and the shoot bolt handle is in Position C fully engaged the circuit breaker can be levered from the TEST position to the CONNECTED position For the circuit breaker to reach its CONNECTED position it must be manually levered to that ...

Page 33: ...cation 2 to Location 3 right and forward in keyed slot Figure 4 12 This will lock the secondary connector of the umbilical cord and the cassette s secondary connector together The shoot bolt handle can now be rotated to its full up position Position C Figure 4 7 In this position the shoot bolts engage the cassette s interlock plates completely and the interlock lever cannot be moved back to Locati...

Page 34: ...the next paragraph 4 6 4 levering details and additional safety shutter information 4 6 4 LEVERING CIRCUIT BREAKER CAUTION MAKE SURE THE CIRCUIT BREAKER ELEMENT IS IN THE FULLY RACKED OUT POSITION IN THE CRADLE BEFORE ANY ATTEMPT IS MADE TO PUT THE CIRCUIT BREAKER INTO THE CASSETTE FAILURE TO DO SO COULD RESULT IN EQUIPMENT DAMAGE OR BODILY INJURY DURING LIFTING AND HANDLING REFER TO PARAGRAPH 4 6...

Page 35: ...ocess If the breaker is closed and in the TEST position it will trip when the screw lock plate is pushed In addition the circuit breaker will not close with the locking plate recessed To connect the circuit breaker lever it in a clockwise direction Figure 4 17 The upper circuit breaker portion moves into the cassette while the lower cradle portion remains stationary in the front portion of the cas...

Page 36: ...ever the circuit breaker out of the CONNECT position reverse the process just described for levering the circuit breaker to the CONNECT position Remember that the circuit breaker must be open before the racking screw lock plate can be recessed to gain access to the large drive nut Figure 4 16 Once the drive nut is accessible engage it with the socket and levering crank Begin levering the Figure 4 ...

Page 37: ...e made through a standard secondary disconnect block or an optional screw type terminal block supplied in kit form The drawout VCP T circuit breakers utilize spring loaded finger disconnects to make its primary connection The number of individual silver plated fingers that make up a finger cluster depends upon the current rating of the circuit breaker The circuit breaker finger disconnects mate wi...

Page 38: ...ront Cover Removed 1 Secondary Wiring 2 Through The Window Accessories 3 Electric Charging Motor 4 Manual Charging Handle 5 Contact Status Open Close 6 Spring Status Charged Discharged 7 Manual OFF Pushbutton 8 Manual ON Pushbutton 9 Operations Counter 10 5A 5B Auxiliary Switch 11 Opening Spring 12 OFF Key Lock Location 13 Motor Cutoff Switch 14 Trip Unit Location ...

Page 39: ...10895G01 6 Spring Status Charged Discharged 2A10895G01 7 Manual OFF Pushbutton 2A10895G01 8 Manual ON Pushbutton 2A10895G01 9 Operations Counter 592C040H01 10 5A 5B Auxiliary Switch 698B822H01 11 Opening Spring 67A3139H02 12 OFF Key Lock Location 13 Motor Cutoff Switch 73430E1A02 14 Integral Protective Relay Optional 15 Cradle with Levering Mechanism 25kA 69C3305G01 40kA 69C3305G11 16 Shoot Bolt H...

Page 40: ...ire vacuum interrupter assembly must be replaced 5 2 2 CONTACT WIPE AND STROKE Up to 25kA Contact wipe is the indication of 1 the force holding the vacuum interrupter contacts closed and 2 the energy available to hammer the contacts open with sufficient speed for interruption Stroke is the gap between fixed and moving contacts of a vacuum interrupter with the breaker open The circuit breaker mecha...

Page 41: ...ith one shunt trip The closing springs can only be charged manually To manually charge the springs insert one finger in the recess behind the charging handle and pull out This permits a hand to grasp the handle and begin charging Figure 5 6 It takes a number of down ward strokes on the charging handle to complete the manual charging process Keep in mind that it is possible to manually recharge the...

Page 42: ...ll circuit breakers have a standard mechanical anti pump feature If the circuit breaker is open it only accepts one attempt to reclose when the close command continues uninterrupted 5 3 5 LATCH CHECK SWITCH Any circuit breaker capable of being electrically closed is provided with a latch check switch The latch check switch insures that all closing conditions are met before the circuit breaker can ...

Page 43: ...nts Figure 5 15 There are two secondary connection options for fixed type VCP TR circuit breakers 1 Standard Secondary Disconnect Block The secondary disconnect block is a female connector with male pins compatible with a male connector with female pins mounted under the protective hood Figure 5 16 The customer plugs secondary wiring with crimp on connectors into the back of the female plug in con...

Page 44: ...Instruction Book Effective November 2017 Page 38 For more information visit www Eaton com IB131016EN Figure 5 10 VCP T and VCP TR Non Trip Unit Connection Diagram ...

Page 45: ...Instruction Book Effective November 2017 Page 39 IB131016EN For more information visit www Eaton com Figure 5 11 VCP T and VCP TR with 520V Trip Unit Connection Diagram ...

Page 46: ...Instruction Book Effective November 2017 Page 40 For more information visit www Eaton com IB131016EN Figure 5 12 VCP T and VCP TR with 1150V Trip Unit Connection Diagram ...

Page 47: ...Instruction Book Effective November 2017 Page 41 IB131016EN For more information visit www Eaton com Figure 5 12A VCP T and VCP TR with 520MCV Trip Unit Connection Diagram ...

Page 48: ...Instruction Book Effective November 2017 Page 42 For more information visit www Eaton com IB131016EN Figure 5 13 VCP T Drawout Umbilical Cord and Connector Wiring Diagram ...

Page 49: ...Instruction Book Effective November 2017 Page 43 IB131016EN For more information visit www Eaton com Figure 5 15 Top View Secondary Connectors Figure 5 18 AMP Secondary Wiring Removal Tool AMP 305 183 ...

Page 50: ...e self powered When the circuit breaker is closed no external power is required to operate their protective systems Current signal levels and the control power are derived from the current sensors mounted behind the cassette Table 5 1 Digitrip Trip Units Functions 520V 1150V LSIG Protection Yes Yes Disable Yes Yes GF Protection Yes Yes GF Alarm No Yes Display No Yes Programmable No Yes Metering No...

Page 51: ...tional to the load current Under pre selected conditions of current magnitude and time the sensors furnish the trip unit with a signal and the energy required to trip the circuit breaker Table 5 2 Current Sensors and Matching Rating Plugs Current Rating in Amperes 100 200 250 300 400 600 630 800 1000 1200 1250 1600 2000 2500 Neutral current sensors are available for customer installation The addit...

Page 52: ...rip devices and one close device can be used The three plug in accessories are Shunt Trip ST Spring Release SR Undervoltage Release UVR Shunt Trip The shunt trip opens the circuit breaker instantaneously when its coil is energized by a voltage input Figure 5 22 and Table 5 3 One shunt trip is supplied as standard with all manually operated and electrically operated circuit breakers An optional sec...

Page 53: ...220 Vac 187 242 450 VA 60 ms 240 Vac 204 264 450 VA 60 ms 5 6 2 INTERNAL ELECTRICAL ACCESSORIES Other electrical accessories are mounted inside the circuit breaker behind the front cover Access to these devices is gained by simply removing the front cover There are three internally mounted electrical accessories Motor Operator Auxiliary Switch Trip Indicator Overcurrent Trip Switch Motor Operator ...

Page 54: ...106 138 3 Amperes 400 of Running 250 VA 5 sec 220 Vdc 187 242 2 Amperes 400 of Running 250 VA 5 sec 250 Vdc 213 275 2 Amperes 400 of Running 250 VA 5 sec 110 Vac 94 121 3 Amperes 400 of Running 250 VA 5 sec 120 Vac 102 132 3 Amperes 400 of Running 250 VA 5 sec 220 Vac 187 242 2 Amperes 400 of Running 250 VA 5 sec 240 Vac 204 264 2 Amperes 400 of Running 250 VA 5 sec Table 5 7 Auxiliary Switch Cont...

Page 55: ...al interlock holds one or more circuit breakers tripped prevents closure Figure 5 27 Pushbutton Cover Mounted is interconnected with either cables or rods depending upon the relative orientation of the breakers Rods can be used only when the circuit breakers to be interlocked are vertically stacked Cables can be used for any orientation of the breakers Mechanical interlocks are available for both ...

Page 56: ... insure the best possible ongoing service It is imperative that an established schedule be followed To establish an exact schedule for a specific installation use the following guidelines 1 In a clean non corrosive environment inspect and maintain each breaker every 2000 operations or 3 years whichever comes first 2 For special conditions such as frequent breaker operation contaminated environment...

Page 57: ...e indicator is visible Contact wipe erosion 40Ka Refer to 6 5 1 details Replace pole unit 87mm Replace pole unit assembly Adequate Vacuum See Section 6 5 Dirt on ceramic body Visual Check Clean with dry lint free cloth 3 Control Circuit Closing and Tripping Device Smooth and correct operation by control power Test closing and tripping of the breaker twice Replace any defective device identify per ...

Page 58: ... a dc test unit is available In this case the equipment must be capable of delivering 5 milliamperes for one minute to avoid ambiguity due to field emission or leakage currents and the test voltage shall be as shown in Table 6 2 Table 6 2 Test Voltage Breaker Rated Maximum Voltage Vacuum Interrupter Integrity Test Voltage at 60 Hz dc 4 76 kV 20 kV 28 kV 8 25 kV 20 kV 28 kV 15 0 kV 27 kV 40 kV The ...

Page 59: ...or more information visit www Eaton com Figure 6 1 Contact Erosion Mark Visible on Stem Figure 6 2 Contact Wipe Inspection Area Figure 6 3 Satisfactory Contact Wipe Condition with Breaker Closed Figure 6 4 Unsatisfactory Contact Wipe Condition with Breaker Closed ...

Page 60: ...icates that the contacts have eroded to an unacceptable performance level The entire vacuum interrupter assembly must be replaced Vacuum interrupters on 31 5 40kA breakers are not visible from the rear of the circuit breaker without removing the individual rear covers Figure 3 9 It is not necessary to remove the rear covers to make the wipe measurement The rear covers are held in place by the uppe...

Page 61: ...st machine Ground the breaker frame Starting with zero increase the voltage to 1500 volts rms Maintain the voltage for one minute Successful withstand indicates satisfactory insulation strength of the secondary control circuit Remove the shooting wire and reconnect the motor leads 6 8 PRIMARY CIRCUIT RESISTANCE CHECK Since the main contacts are inside the vacuum chamber they remain clean and requi...

Page 62: ... replace shunt trip if faulty Secondary contact wiring problem Make sure electrical pin and socket connectors are properly seated in molded plug Verify proper wiring Circuit breaker cannot be opened locally OPEN pushbutton locked Remove lock Faulty mechanism or one or more vacuum interrupter contacts welded Contact Eaton service center Circuit breaker makes no attempt to close with either local ma...

Page 63: ...ase if faulty Secondary contact wiring problem Make sure electrical pin and socket connectors are properly seated in molded plug Verify proper wiring Latch check switch open Bad switch or not reset Circuit breaker cannot be closed locally but can be closed remotely Opening and or closing pushbuttons locked Check reason for lock Circuit breaker does not recharge electrically but will recharge manua...

Page 64: ...Instruction Book Effective November 2017 Page 58 For more information visit www Eaton com IB131016EN Figure 6 7 Circuit Breaker Lubrication ...

Page 65: ...Instruction Book Effective November 2017 Page 59 IB131016EN For more information visit www Eaton com Figure 6 8 Drawout Cassette Lubrication ...

Page 66: ...ommended the IEEE Std C37 10 Section A 1 and the reporting form IEEE Std 1325 be considered for reporting the breaker failure event to EATON SECTION 7 RENEWAL PARTS 7 1 GENERAL In order to minimize production downtime it is recommended that an adequate quantity of spare parts be carried in stock The quantity will vary from customer to customer depending upon the service severity and continuity req...

Page 67: ...Page 61 IB131016EN For more information visit www Eaton com Ronis 67A3140G01 Fixed Bkr Only Castell 67A3140G02 Fixed Bkr Only Kirk 67A3140G03 Fixed Bkr Only Kirk 69C3333G01 Draw Out Bkr Only Eaton does not supply Lock or Key only the provision ...

Page 68: ... 31 5kA 67A3158G51 67A3158G52 67A3158G54 67A3158G55 67A3158G56 67A3158G57 5kV 40kA 67A3158G61 67A3158G62 67A3158G64 67A3158G65 67A3158G66 67A3158G67 7 5kV 16kA 67A3159G21 67A3159G22 67A3159G24 67A3159G25 67A3159G26 67A3159G27 7 5kV 20kA 67A3159G31 67A3159G32 67A3159G34 67A3159G35 67A3159G36 67A3159G37 7 5kV 25kA 67A3159G41 67A3164G42 67A3159G44 67A3159G45 67A3159G46 67A3159G47 7 5kV 31 5kA 67A3159...

Page 69: ...Instruction Book Effective November 2017 Page 63 IB131016EN For more information visit www Eaton com ...

Page 70: ...ator Customer Field Installable 9 Breaker Terminal Block Bracket Additional items available from manufacturer Pin for 14 18 AWG wire AMP 66597 2 Pin for 18 26 AWG wire AMP 640545 2 Pin Crimper Tool AMP 90067 4 Removal Tool AMP 305183 10 Screw Type Terminal Block Customer Field Installable Control Voltage Stylet 24 Vdc 48 Vdc 125 Vdc 250 Vdc 120 Vac 240 Vac 69C3193G11 69C3193G01 69C3193G12 69C3193G...

Page 71: ...Instruction Book Effective November 2017 Page 65 IB131016EN For more information visit www Eaton com ...

Page 72: ...Instruction Book Effective November 2017 Page 66 For more information visit www Eaton com IB131016EN 69C7573G11 69C7573G12 ...

Page 73: ...re information visit www Eaton com 7 IP54 Cover Kit Transparent Customer Field Installable 9 25kA Racking Cradle 69C3305G01 Customer Field Installable 8 Spout Boot up to 25kA only Customer Field Installable 10 40kA Racking Cradle 69C3305G11 Customer Field Installable ...

Page 74: ...3G04 400 69C3011H04 400 5720B93G05 600 69C3011H06 600 5720B93G06 630 69C3011H63 630 5720B93G07 800 69C3011H08 800 5720B93G08 1000 69C3011H10 1000 5720B93G09 1200 69C3011H12 1200 5720B93G10 1250 69C3011H13 1250 5720B93G11 1600 69C3011H16 1600 5720B93G12 2000 69C3011H20 2000 5720B93G13 2500 69C3011H30 2500 5720B93G14 Description Style Zero Sequence Current Transformer 100 1 and 200 1 tap ratio 50 1 ...

Page 75: ...ber 2017 5 15Kv VCP T VCP TR Front Cover Castell and Kirk Lock Kit 69C3150G01 Eaton Corporation 1000 Cherrington Parkway Moon Township PA 15108 4312 USA tel 1 800 525 2000 www EatonElectrical com VCP T CASSETTE MECHANICAL INTK CABLE KIT 2 WAY 25kA VERSION 67A3350G01 40kA VERSION 67A3348G01 VCP TR BREAKER MECHANICAL INTK CABLE KIT 2 WAY 25kA VERSION 67A3349G01 VCP TR BREAKER MECHANICAL INTK CABLE K...

Page 76: ...Instruction Book Page 70 Effective November 2017 For more information visit www Eaton com IB131016EN ...

Reviews: