Eaton 12-110-1250y Operation And Installation Manual Download Page 24

20

Connect the AC input wires (optional for AC input)

Eaton 1250W / 1500W / 1800W  Inverter Operation and Installation Guide 

   IM SP180164 / Rev D     www.eaton.com

General AC wiring considerations

AC wiring connectors

AC wires are fixed to their respective barrier strip terminals by clamp screws. The amount of insulation to be stripped off the 

individual wires should not be so much that it is visible outside the connector.

AC and DC Wiring Separation

Do not mix DC and AC wiring configurations. Do not use the same conduit or panel. If wires must cross, only do so at 90° to 

one another. If necessary, examine applicable codes for specific AC and DC wiring proximity. Figure 7 is an illustration of the 

AC wiring compartment.

AC wiring and GFCIs 

AC input must be hardwired to the inverter. AC loads can either be plugged into the GFCI mounted to the front panel of the 

inverter, or hardwired directly to the panel. An external GFCI should be used if output is hardwired since the integrated GFCI 

does not control the AC Output hardwired connections. This section will explain how to hardwire the inverter with AC input 

and output. All AC wiring (source to inverter, inverter to AC panels, AC panels to circuit breakers, and GFCIs) must be rated 

to at least the current rating of the fuses and/or circuit breakers, and also must be insulated to at least 120Vac. Multi-strand 

wire is required. Typically, 30A circuit breaker requires a 10AWG wire.
The knockouts for AC input and output hardwiring are located on the front sidewalls. Make sure to read the labels on the 

inverter for proper input and output wiring.

AC input connections

1.  Ensure AC and DC power are OFF.
2.  Install required circuit breaker to the AC input wiring system.
3.  Remove mounting screws holding the GFCI AC receptacle and take off the front panel.
4.  Leave the GFCI inside the inverter, but remove the knockout from the sidewall.
5.  Install the supplied NM clamp (Romex clamp) into the knockout hole.
6.  Locate the terminal blocks. The whole area will be labeled “AC INPUT” and there will be three terminations:

• 

(GND), 

• 

(L)

• 

(N)

7.  Strip enough of the input cable jacket as to expose the three wires, about 2 inches (50mm).
8.  Strip approximately 3/8 inches (10mm) of insulation from each wire. The terminal blocks will accept wire sizes up to 

10AWG.

Figure 7.  AC wiring compartment

Status

Input Voltage (V)

Input Current (A)

Output power (KW)

Utility

Battery

Fuse

000

I N V E R T E R

12-110-1800-B4

SELECT

Summary of Contents for 12-110-1250y

Page 1: ...Eaton 1250W 1500W 1800W Inverter Operation and Installation Guide True Sine Wave Inverter...

Page 2: ...al loss of power additional expenses in the use of existing power facilities or claims against the purchaser or user by its customers resulting from the use of the information recom mendations and des...

Page 3: ...splay 2 Setting battery type and charge current 3 Fault codes and troubleshooting 6 Troubleshooting 8 Charger and AC transfer 9 Specifications 10 INSTALLATION Installation types and definitions 15 Cho...

Page 4: ...operly secured and protected from chaffing WARNING Failure to follow these instructions could result in death personal injury or property damage Personal precautions when working with batteries WARNIN...

Page 5: ...otect itself Some models include a three stage temperature compensated battery charger that maximizes the life of the batteries It can be configured for AGM flooded or Gel lead acid batteries Eaton in...

Page 6: ...5 Flooded 14 4 14 4 13 5 Gel 14 2 14 2 13 8 AGM 14 3 14 3 13 4 WARNING Fire hazard Programming the incorrect battery type may result in battery damage and a fire risk To change display and read curre...

Page 7: ...ent value setting is displayed Press and hold the POWER button for 5 seconds 2 Press the SELECT button to switch between the different current ratings in Amps 40 2 5 10 20 3 To choose a new setting st...

Page 8: ...Press SELECT button to toggle between the two alarm on off settings AL0 this indicates the alarm is OFF AL1 this indicates the alarm is ON 3 To choose a new setting stop at the desired value press an...

Page 9: ...tes Fixed setting FLo this indicates Flooded battery setting gEL this indicates Gel battery setting Ag this indicates AGM battery setting 3 To choose a new setting stop at the desired value press and...

Page 10: ...p 1Hz 12 110 1500 xx Warning 100W 1700 E06 Beep 0 33Hz Shutdown 100W 1800 E03 Beep 1Hz 12 110 1250 xx Warning 100W 1450 E06 Beep 0 33Hz Shutdown 100W 1550 E03 Beep 1Hz AC output short circuit protecti...

Page 11: ...harge current reduced to 0A AC transfer relay 70 C System shutdown no auto reset Max charge current resumes normal level when ChargerTransformer sensor temperature drops below 90 C Table 7 Location Wa...

Page 12: ...he unit in a location with lower ambient temperature or improve air flow around the unit E05 DC Input Under Voltage Warning Unit is detecting an input DC voltage which is too low and it is warning the...

Page 13: ...ypass mode is available To reset error code remove AC Input and turn unit off and on Dead battery charging Battery voltage must meet the following conditions or Error code E11 will display Initial bat...

Page 14: ...tput power 5 seconds 2000W Surge output power 3600W 300ms Operating temperature range 0 C to 50 C Storage temperature range 40 C to 85 C THD Resistive load 5 max 2 5 typical Output power rated at 25 C...

Page 15: ...sorption voltage Float voltage 10V 5V Charge current setting Float current Maximum charge current setting 15 min 8 hrs max 5 hrs max NOTE If an external DC load is connected to the battery and it drai...

Page 16: ...c 4 9 Table 2 Must operate per specification after the test Table 17 Electromagnetic Specifications Conducted immunity Per SAE J1113 3 Severity Level L6 0 5W Manual restart required for pulses 1 2b an...

Page 17: ...nnectors DC input M8 x 1 25 Stud Chassis ground M6 x 1 00 Stud AC output AC NEMA outlet with knockouts for AC Input and optional AC output Built in AC NEMA outlet is GFCI protected The built in AC GFC...

Page 18: ...take note of any precautions concerning the installation Prior to engaging in any service all AC and DC power sources need to be disabled Follow proper cable routing and strain relief guidelines Insta...

Page 19: ...r an AC generator In the case of multiple sources an automatic or manual AC source selector switch can be used The AC source going into the inverter must have a neutral conductor bonded to ground i e...

Page 20: ...current protec tion and the disconnect switch for the AC power supply AC load panels can utilize an AC output circuit breaker and breakers for each subsequent load circuit AC cabling AC cabling includ...

Page 21: ...of fire Installing the inverter in a compact compartment will be detrimental and may result in overheating IMPORTANT Location s must conform to these required parameters Dry Do not allow water or oth...

Page 22: ...asten the inverter to the mounting surface using pan head wood or sheet metal screws if mounting to a wall or bulk head Do not block vents on bottom of inverter Figure 6 Approved mounting orientation...

Page 23: ...Bxy 2 150 12 20 14 1 2 3 12 110 1500y 2 175 14 20 14 1 3 12 110 1500 Bxy 2 175 12 20 14 1 2 3 12 110 1800y 1 200 12 30 12 1 3 12 110 1800 Bxy 1 200 10 30 12 1 2 3 1 AC output fuse is not required as a...

Page 24: ...utput All AC wiring source to inverter inverter to AC panels AC panels to circuit breakers and GFCIs must be rated to at least the current rating of the fuses and or circuit breakers and also must be...

Page 25: ...ld be in accordance with wiring codes DO NOT connect any AC input source to the output terminals of the inverter IMPORTANT The Eaton Inverter will not operate if connected to high power consumption lo...

Page 26: ...g wires improperly i e the neutral wire into the line termination will cause the inverter to break down and possibly cause permanent damage 4 It is very important to not confuse the connections i e pu...

Page 27: ...ion or fire Proper ventilation is crucial To make connections to DC terminals 1 Ensure the inverter is OFF and no connections are being made to DC or AC circuits 2 Remove nuts and washers from the DC...

Page 28: ...gative post of the battery to the negative DC terminal of the inverter 2 Install flat washer then the lock washer and nut back on to the inverter Tighten to 12 2 13 6 Nm 9 10 ft lbs Grounding The grou...

Page 29: ...on for the panel should be dry out of direct sunlight free of corrosive fumes and suitable for mounting an electronic device 2 Draw the area to cut away with a pencil on the wall 3 Cut away the area a...

Page 30: ...verify it functions properly Hint H If the appliance functions as expected the installation is a success If it was a hardwire installation continue reading Testing in UTILITY GRID MODE 1 Using the sam...

Page 31: ...ton Boulevard Cleveland OH 44122 United States Eaton com 2019 Eaton All Rights Reserved Publication No IM SP180164 August 2017 Eaton is a registered trademark All trademarks are property of their resp...

Reviews: