Eaton 12-110-1250y Operation And Installation Manual Download Page 20

16

Eaton 1250W / 1500W / 1800W  Inverter Operation and Installation Guide 

   IM SP180164 / Rev D     www.eaton.com

Definitions

Generator – 

The inverter is capable of handling most generators that produce nominal 115Vac, 60Hz sine wave AC power. 

The current limit for DC charging is programmable between 2A-40A, therefore use a generator which will provide sufficient 

power to satisfy charging requirements.

AC disconnect and over-current protection device – 

The inverter is required by safety and electrical codes to have 

AC and DC input/output over- current protection (i.e. circuit breakers and/or fuses), as well as disconnect devices. The follow-

ing are suggested protective measures for each configuration:

AC input:   

The branch fuse or branch circuit breaker (hard wired) used on the source of the inverter must be rated no less 

than 15A or no more than 30A and must also be approved for use on 115Vac systems. The wire used between the breaker 

and the inverter needs to be sized accordingly to pass the same amount of current rated for the fuse.

AC output:   

The fuse or circuit breaker on the output should not be rated any higher than that of the input.  The wire 

between the inverter and the AC output breaker should be rated to carry the amount of current rated for the fuse. Any sub-

sequent wiring from this output breaker to the loads must be sized accordingly for the current being passed to each indi-

vidual load. 1000 Watt models feature an integrated 15 Amp AC output breaker while 1800 Watt models feature an integrated 

20 Amp AC output breaker.

Disconnect devices – 

Each fuse or breaker system requires a method for disconnecting. If the devices used are circuit 

breakers, these will serve as the disconnects. If they are fuses, separate AC disconnect switches will be necessary ahead of 

the fuses; these switches will be a branch circuit with proper current characteristics and rated to 120Vac.

AC distribution panels –  

A usual system will incorporate distribution centers ahead of the inverter and between the 

inverter and the loads (AC load panel). AC source panels will include a main circuit breaker, serving as the over-current protec-

tion and the disconnect switch for the AC power supply. AC load panels can utilize an AC output circuit breaker, and breakers 

for each subsequent load circuit.

AC cabling – 

AC cabling includes but is not limited to all wires/cables between the AC source and the inverter, and all the 

cabling between the inverter and AC outputs (panels, circuit breakers, and loads). Wiring type and size varies with installation 

and load. Installation codes will recommend solid or stranded wires, overall size of conductors, and type/temperature ratings 

of insulation around the wire.
Ensure AC breakers and fuses are sized appropriately for current, insulation for voltage, and ambient temperature ratings.  

Table 19 gives examples of wiring sizes based on the breaker rating. Examples are based on use with a 2-conductor-plus-

ground (3-prong) cable rated at 75°C.

AC output neutral bonding – 

AC input neutral and output neutral must be isolated from each other. This being noted, 

the neutral conductor of the inverter AC output circuit (i.e. AC output neutral) is automatically connected to the safety ground 

during inverter operation. When using an AC utility power source and the inverter is in charging mode, this connection is not 

present.

DC cabling – 

DC cabling includes but is not limited to all cables and connectors between the batteries, the DC disconnect 

and breakers/fuses, and the inverter. Heavy truck or RV installations normally require multi-strand, insulated cables for flexibil-

ity and durability; they also usually require over-current protection devices.  DC cables must be copper and must be rated to 

at least 75°C. The cables should also terminate with lugs that fit the DC stud terminals on the inverter (m8 x 1.25). Choosing 

small cables may result in unsatisfactory device functionality.

DC disconnects and over-current devices – 

The DC system from the inverter to the battery must be equipped with 

an over-current device and disconnect.  Typically this consists of a separate fuse with a DC disconnect. The rating size of the 

cables must match rating of fuses. Fuse and disconnect should be situated as close as possible to the battery, on the posi-

tive cable.

Batteries – 

The inverter sources input power from a 12VDC deep cycle or dual purpose batteries. The inverter converts the 

12VDC input power to 115VAC output.

Summary of Contents for 12-110-1250y

Page 1: ...Eaton 1250W 1500W 1800W Inverter Operation and Installation Guide True Sine Wave Inverter...

Page 2: ...al loss of power additional expenses in the use of existing power facilities or claims against the purchaser or user by its customers resulting from the use of the information recom mendations and des...

Page 3: ...splay 2 Setting battery type and charge current 3 Fault codes and troubleshooting 6 Troubleshooting 8 Charger and AC transfer 9 Specifications 10 INSTALLATION Installation types and definitions 15 Cho...

Page 4: ...operly secured and protected from chaffing WARNING Failure to follow these instructions could result in death personal injury or property damage Personal precautions when working with batteries WARNIN...

Page 5: ...otect itself Some models include a three stage temperature compensated battery charger that maximizes the life of the batteries It can be configured for AGM flooded or Gel lead acid batteries Eaton in...

Page 6: ...5 Flooded 14 4 14 4 13 5 Gel 14 2 14 2 13 8 AGM 14 3 14 3 13 4 WARNING Fire hazard Programming the incorrect battery type may result in battery damage and a fire risk To change display and read curre...

Page 7: ...ent value setting is displayed Press and hold the POWER button for 5 seconds 2 Press the SELECT button to switch between the different current ratings in Amps 40 2 5 10 20 3 To choose a new setting st...

Page 8: ...Press SELECT button to toggle between the two alarm on off settings AL0 this indicates the alarm is OFF AL1 this indicates the alarm is ON 3 To choose a new setting stop at the desired value press an...

Page 9: ...tes Fixed setting FLo this indicates Flooded battery setting gEL this indicates Gel battery setting Ag this indicates AGM battery setting 3 To choose a new setting stop at the desired value press and...

Page 10: ...p 1Hz 12 110 1500 xx Warning 100W 1700 E06 Beep 0 33Hz Shutdown 100W 1800 E03 Beep 1Hz 12 110 1250 xx Warning 100W 1450 E06 Beep 0 33Hz Shutdown 100W 1550 E03 Beep 1Hz AC output short circuit protecti...

Page 11: ...harge current reduced to 0A AC transfer relay 70 C System shutdown no auto reset Max charge current resumes normal level when ChargerTransformer sensor temperature drops below 90 C Table 7 Location Wa...

Page 12: ...he unit in a location with lower ambient temperature or improve air flow around the unit E05 DC Input Under Voltage Warning Unit is detecting an input DC voltage which is too low and it is warning the...

Page 13: ...ypass mode is available To reset error code remove AC Input and turn unit off and on Dead battery charging Battery voltage must meet the following conditions or Error code E11 will display Initial bat...

Page 14: ...tput power 5 seconds 2000W Surge output power 3600W 300ms Operating temperature range 0 C to 50 C Storage temperature range 40 C to 85 C THD Resistive load 5 max 2 5 typical Output power rated at 25 C...

Page 15: ...sorption voltage Float voltage 10V 5V Charge current setting Float current Maximum charge current setting 15 min 8 hrs max 5 hrs max NOTE If an external DC load is connected to the battery and it drai...

Page 16: ...c 4 9 Table 2 Must operate per specification after the test Table 17 Electromagnetic Specifications Conducted immunity Per SAE J1113 3 Severity Level L6 0 5W Manual restart required for pulses 1 2b an...

Page 17: ...nnectors DC input M8 x 1 25 Stud Chassis ground M6 x 1 00 Stud AC output AC NEMA outlet with knockouts for AC Input and optional AC output Built in AC NEMA outlet is GFCI protected The built in AC GFC...

Page 18: ...take note of any precautions concerning the installation Prior to engaging in any service all AC and DC power sources need to be disabled Follow proper cable routing and strain relief guidelines Insta...

Page 19: ...r an AC generator In the case of multiple sources an automatic or manual AC source selector switch can be used The AC source going into the inverter must have a neutral conductor bonded to ground i e...

Page 20: ...current protec tion and the disconnect switch for the AC power supply AC load panels can utilize an AC output circuit breaker and breakers for each subsequent load circuit AC cabling AC cabling includ...

Page 21: ...of fire Installing the inverter in a compact compartment will be detrimental and may result in overheating IMPORTANT Location s must conform to these required parameters Dry Do not allow water or oth...

Page 22: ...asten the inverter to the mounting surface using pan head wood or sheet metal screws if mounting to a wall or bulk head Do not block vents on bottom of inverter Figure 6 Approved mounting orientation...

Page 23: ...Bxy 2 150 12 20 14 1 2 3 12 110 1500y 2 175 14 20 14 1 3 12 110 1500 Bxy 2 175 12 20 14 1 2 3 12 110 1800y 1 200 12 30 12 1 3 12 110 1800 Bxy 1 200 10 30 12 1 2 3 1 AC output fuse is not required as a...

Page 24: ...utput All AC wiring source to inverter inverter to AC panels AC panels to circuit breakers and GFCIs must be rated to at least the current rating of the fuses and or circuit breakers and also must be...

Page 25: ...ld be in accordance with wiring codes DO NOT connect any AC input source to the output terminals of the inverter IMPORTANT The Eaton Inverter will not operate if connected to high power consumption lo...

Page 26: ...g wires improperly i e the neutral wire into the line termination will cause the inverter to break down and possibly cause permanent damage 4 It is very important to not confuse the connections i e pu...

Page 27: ...ion or fire Proper ventilation is crucial To make connections to DC terminals 1 Ensure the inverter is OFF and no connections are being made to DC or AC circuits 2 Remove nuts and washers from the DC...

Page 28: ...gative post of the battery to the negative DC terminal of the inverter 2 Install flat washer then the lock washer and nut back on to the inverter Tighten to 12 2 13 6 Nm 9 10 ft lbs Grounding The grou...

Page 29: ...on for the panel should be dry out of direct sunlight free of corrosive fumes and suitable for mounting an electronic device 2 Draw the area to cut away with a pencil on the wall 3 Cut away the area a...

Page 30: ...verify it functions properly Hint H If the appliance functions as expected the installation is a success If it was a hardwire installation continue reading Testing in UTILITY GRID MODE 1 Using the sam...

Page 31: ...ton Boulevard Cleveland OH 44122 United States Eaton com 2019 Eaton All Rights Reserved Publication No IM SP180164 August 2017 Eaton is a registered trademark All trademarks are property of their resp...

Reviews: