background image

Eaton Corporation

Electrical Sector
1111 Superior Ave.
Cleveland, OH 44114
United States
877-ETN-CARE (877-386-2273)
Eaton.com

© 2011 Eaton Corporation
All Rights Reserved
Printed in USA
Publication No. IL04707001E / Z11206
June 2011

Eaton is a registered trademark 
of Eaton Corporation. 

All other trademarks are property 
of their respective owners.

Instructional Leafl et 

IL04707001E

Effective June 2011

10250T contact block assembly 

  
  

Push–pull operators

Application guide

To assist in the selection of contact blocks, the diagram on page 1 
shows pictorially by symbols “A” and “B” locations of contact 
circuits after assembly of contact blocks to the operator. 

Table 1

 and 

Table 2

 show the effect of the push and pull operations on either 

NO or NC contacts.

A maximum of two contact blocks may be used with each operator. 
Maximum torque of stacking screws is 9 in-lbs. Adding more 
than two blocks may cause this switch to malfunction. Single 
circuit contact must be mounted under circuit “A”. Special function 
contact blocks are not available for use with the three-position 
push–pull operator.

ote: 

N

Buttons and lenses in various colors are ordered and packaged sepa-

rately. This pushbutton unit is oiltight when the adapter gasket and button or 
lens gasket are securely tightened.

Table 1.   Push–Pull Operator Types

Operator
Type

Contact
Block
Circuit

Operator Mode and Contact Circuit

Pulled

Intermediate

Pushed

Circuits
A B

Circuits
A B

Circuits
A B

Momentary
push and pull
and
momentary pull,
maintained push

2NC

1NO

X X

O

O X

O

O O

X

Maintained 
push and pull
(Two-positions)

1NC
2NC
1NO
2NO

X or X
X   X
O or  O
O   O

No
intermediate
position

O or  O
O   O
O   O
X   X

Momentary
push and pull
(Three-positions)

1NO–1NC

O X

O O

X O

ote: 

N

X = contacts closed; O = contacts open

Table 2.   Push–Pull Wire Position Operation

Control

Line Diagram

Operator

Circuits

Operator Mode

Three-wire,
three-position,
momentary

Circuit

Circuit

L2

L1

M

M

OL

A

B

Momentary
push and pull

2NC
contact
blocks

START

(Momentary)

Normal position

(Maintained)

STOP

(Momentary)

Two-wire,
two-position,
maintained

Circuit

L2

L1

M

or

OL

A

B

Maintained
push and pull

1NC
contact
blocks

START

(Maintained)

No
intermediate
position

STOP

(Maintained)

Three-wire
momentary pull,
maintained push

Circuit

Circuit

L2

L1

M

M

OL

A

B

Maintained
push and
maintained
ready,
momentary
pull to start

2NC
contact
blocks

START

(Momentary)

Normal position

(Maintained)

STOP

(Momentary)

Reviews: