background image

4 Position

Combi-

nation 

No.

Desired Circuit 

Operation

X Circuit Closed

O Circuit Open

Contact Blocks Required to 

Accomplish Circuit Function

Combi-

nation 

No.

Desired Circuit 

Operation

X Circuit Closed

O Circuit Open

Contact Blocks Required to 

Accomplish Circuit Function

Mounting Location

Mounting Location

Top Plunger A

Bottom 

Plunger B

Top Plunger A

Bottom 

Plunger B

1

X O O O

10

X O X O

2

O X O O

3

O O X O

11

X X X O

4

O O O X

5

X O O X

12

O X X X

6

O X X O

7

O O X X

13

X O X X

8

X X O O

9

O X O X

14

X X O X

3 Position

Combi-

nation 

No.

Desired Circuit 

Operation

X Circuit Closed

O Circuit Open

Contact Blocks Required to Accomplish Circuit Function

(Jumpers must be installed where indicated)

Operator with Cam Code #2

Operator with Cam Code #3

Mounting Location

Mounting Location

Top Plunger A

Bottom Plunger B

Top Plunger A

Bottom Plunger B

1

X O O

2

X X O

3

X O X

4

O O X

5

O X X

6

O X O

2 Position

Combi-

nation 

No.

Desired Circuit 

Operation

X Contacts 

Closed

O Contacts 

Open

Contact Blocks Required 

to Accomplish Circuit 

Function

Top Plunger

A

Bottom 

Plunger 

B

1

X O

2

O X

2

Instructions and Operation 

P20442

Effective February 2018

Heavy Duty Oiltight Selector Switch

SWITCH UNITS-10250T/91000T OR E34

 

EATON CORPORATION

 www.eaton.com

GENERAL

With any electrical component there is the possibility an external factor (loose wire, moisture, etc.) can cause a short circuit between the component and 

ground. If the device is adequately grounded, the condition causes the protective fuse or circuit breaker to open and remove the potential. If not, an electrical 

hazard may remain unnoticed.

GROUNDING NIBS – 10250T

This 10250T device is designed to make direct metallic contact to the rear of the panel (with no interfere with component-to-panel ground continuity). As 

a further aid in establishing an electrical ground, the device has 4 metal points, “grounding nibs” designed to penetrate most paint or other protective coatings. 

Penetration of these nibs is dependent upon the torque applied to the mounting nut. Recommended torque is 5 ft.lbs (6.8Nm). More or less may be necessary 

to penetrate the specific type of thickness of your panel coating. Test for continuity to ground after installation. If a short circuit to ground does occur, the 

fault should be corrected and the device replaced.

GROUNDING KITS

For grounding 10250T devices to non-metallic panels or metal panels having excessive surface coating or for grounding E34 with any panel we offer the 

following grounding kits which provide for a separate grounding circuit, daisy chained between components and then to ground. Use 10250TKG1.

EARTH TERMINALS-  91000T/E34

These devices are supplied with an earth/ground terminal incorporated. These devices have a 6-32 terminal screw and will accommodate ring type terminations 

for bonding to international specifications.

Select cam code giving 

simplest contact block 

arrangement for circuit(s) 

required.

-Ordinarily, these operators should not be used with overlap and early closing contact 

blocks (10250T/91000T55, T56, T57 and T58). Contact local EATON sales office on 

specific application.

CONTACT BLOCK SELECTION CHART

INSTRUCTIONS FOR THE ASSEMBLY OF THE PADLOCK ATTACHMENT E34TA11, 10250T/91000TA11 

TO KNOB OPERATED HEAVY DUTY OIL TIGHT SELECTOR SWITCH OPERATORS

1. With the knob of the selector positioned per dimension “A”, place the 

padlock attachment over the knob with the mounting screws located as 

shown in the illustration.

2. Tighten the mounting screws alternately and uniformly to prevent the 

attachment from being assembled skewed.

3. The outer lock ring can now be turned to any desired selector position. 

there are provisions for 5 padlocks.

Dimension “A”- For 2 or 3 position selector switch operators. Locate the 

knob half way between clockwise and center positions.

GROUNDING OF 10250T/91000T AND E34 

COMPONENTS

Nib

Earth

Terminal

FOR  HORIZONTAL MOUNTED UNITS THIS BASE IS TURNED 90 DEG. 

HOWEVER, KNOB POSITION AND ASSEMBLY INSTRUCTIONS SHOWN 

HERE APPLY

PADLOCK 

ATTACHMENT

FOR ASSEM-

BLING SEE ITEM 

2 INSTRUCTIONS

SELECTOR 

KNOB 

POSITION 

DIM “A”

MOUNT-

ING 

SCREWS

OUTER 

LOCK RING

INTER LOCK 

RING

OR

OR

OR

Reviews: