CLINK II SCU MANAGER
functional description scu
version 5.0
47
5.8.3
Acknowledge command
Configuring the acknowledge command
To define which trip and warning signals can be acknowledged via manual control or process control, the
setpoints listed in table 34 are configured via LCU-5 by selecting:
SCU Manager - Module Protection - Settings,
tab Enable
.
After a trip or warning, an acknowledge command has to be given to confirm the protection and/or status
message. This can be done from two levels:
•
Process control, via DeviceNet, see table 35.
•
By an acknowledge push-button on the motor starter tray.
Note
The Acknowledge commands can only be set when the Interlock Status (see table 24 on page 32) of manual,
local and process control are FALSE.
Trip Current L2
0-1200.000
A
Actual
Trip Current L3
0-1200.000
A
Actual
Table 34: Process Control Acknowledge setpoints
Name
Description
Parameter
type
Process Control Acknowledge Trip
Enable
Motor Stall
Motor Overload
Phase Unbalance
Earth Leakage
Process Overload
Process Underload
External Protection
Setpoint
Process Control Acknowledge
Warning enable
See above.
Setpoint
Manual Control Acknowledge Trip
Enable
See above.
Setpoint
Manual Control Acknowledge
Warning Enable
See above.
Setpoint
Table 35: Acknowledge commands via DeviceNet command object
Name
Description
Parameter
type
Acknowledge
Protection
0->1 = Acknowledge Protection
Setpoint
Table 33: Read-out of Trip Current by DeviceNet
Name
Range
Unit
Parameter
type