CLINK II SCU MANAGER
functional description scu
version 5.0
40
5.6.9
Command after communication failure
Command After Communication Failure generates a command when the last master is not available anymore.
At that moment also the LED Network A or Network B on the front of the Starter Control Unit will start flashing.
The command is set via LCU-5, see table 29.
Select:
SCU Manager - Module Control - Settings - tab Com
.
The output status of the General Purpose Outputs 0-4 will be set to zero after loss of communication. This
status is fixed set and thus not adjustable by the user.
5.7
Automatic restart
The automatic restart function detects failures in the mains voltage and ensures, depending on the duration of
the failure, a direct or delayed restart so that the continuity of the process is guaranteed.
5.7.1
Mains failure detection
The Starter Control Unit continuously monitors the condition of the mains. As soon as the mains voltage drops
below 65% of the nominal voltage there is a mains failure (see figure 16). As soon as the mains voltage returns
to a value > 90% of the nominal voltage, the mains voltage is considered healthy.
Table 28: Stop/start commands (command object)
Command
Trigger event if Drive Type is
Direct-on-
Line 1
Phase
Direct-on-Line
3 Phase
Star-Delta
Forward-
Reverse
Dual
Speed
Stop
Stop
Stop
Stop
Stop
Stop
Start 1
Start
Start
Not Available
Start For-
ward
Start Low
Start 2
Not Available
Not Available
Start
Start
Reverse
Start High
Table 29: Setpoint Command after Communication Failure (parameter object)
Name
Default
Description
Parameter
type
Command After Communication Failure
No Action
No Action
Stop
Start1
Start 2
Setpoint