6   Operating modes 

6.1   Test mode 

In test mode, the most important functions in the control sequence are checked and shown on the text 

display. To start test mode, call up parameter no. P08 “Test mode” (see section 5.2 for more information) 

and select one of the following test modes: 

 

Test mode 1 (Valve test) 

Each valve connected is activated in sequence and shown in the text display. 

 

Test mode 2 (Input test) 

The signal statuses of the inputs are displayed on the text display. 

 

Test modes 3-5 

For manufacturer purposes only 

 

Test mode 0 (test mode off) 

Test mode is switched off. 

 

 

 

6.2   Down time cleaning 

To activate down time cleaning, perform the following steps: 

  Remove the factory-fitted wire jumper on input 10, 11. 

  Connect a free auxiliary contact (make contact) of the fan contactor to terminals 10 and 11. The input 

should be operated in isolation. 

  Set parameter P05 “Down time cleaning cycles” to the required number of cycles (see also section 5.2 

“Setting parameters”). 

 

If the fan is switched on, the contact on 10, 11 closes and switches on the cleaning. When switching off 

the fan, the contact on 10, 11 opens and activates the down time cleaning. The down time cleaning cycles 

set are carried out. The RM-208 CB then shuts down. 
 

 

 

6.3   Cleaning via start / stop input (external 

p switch) 

If the cleaning is controlled via an external 

p switch, the isolated contact on the 

p switch must be 

connected to the start / stop input 12, 13.  
 

 

 

During down-time cleaning, the start / stop input 12, 13 is inactive. 

Summary of Contents for RM-208 CB.13.01

Page 1: ...Operating and Installation Instructions Filter control system RM 208 CB 13 01 EasyLine Supply voltage 110 V AC...

Page 2: ...structions for the replacement of the device fuse 11 7 2 Cleaning the controller 12 7 3 Manufacturing 12 8 Text messages on the display 13 9 Details on the equipment function 14 10 Glossary 15 11 Tech...

Page 3: ...cable laws conditions orders and regulations governing the setting up of electrical equipment must be observed with respect to the installation site Setting of equipment with degree of protection IP00...

Page 4: ...RM 208 CB 13 01 Easy Line Documentation RDN 10000795 4 20 03 2019 3 Assembly Wall mounting of the filter controls is not permitted The device may only be mounted to machine parts...

Page 5: ...RM 208 CB 13 01 Easy Line Documentation RDN 10000795 5 20 03 2019 4 Step by step installation Supply voltage connection Solenoid valve connection Connection of expansion modules RM LV8 RM LV16...

Page 6: ...accessible for the user and to be marked as disconnecting device for the equipment The wires and cables used for the connection of the controls must be suitable for an ambient temperature of up to 13...

Page 7: ...ameters P02 P11 in sequence The parameters already displayed can be accessed by repeatedly pressing the button To change the value of a displayed parameter press the ENTER button for at least one seco...

Page 8: ...RM 208 CB 13 01 Easy Line Documentation RDN 10000795 8 20 03 2019...

Page 9: ...ve test 2 Input test 3 5 For manufacturer purposes only Off 0 0 5 P09 P09 Ser run hour Service operating hours P10 P10 Ser run h AL Service operating hours alarm 0 h 0 25000 h P11 P11 Ser r h Code Ser...

Page 10: ...e down time cleaning perform the following steps Remove the factory fitted wire jumper on input 10 11 Connect a free auxiliary contact make contact of the fan contactor to terminals 10 and 11 The inpu...

Page 11: ...the fan control Activate signal to input 10 11 Cleaning ineffective Interval time too long Set parameter P02 Interval to a lower value Pressure too low Set pressure to 6 8 bar min 5 bar Set parameter...

Page 12: ...part of the housing and tighten the six screws evenly Switch on the supply voltage again 7 2 Cleaning the controller Wipe only with a damp cloth if outside of device is soiled 7 3 Manufacturing The f...

Page 13: ...abled via input 10 11 and stopped via input 12 13 Cleaning Off Val No The control has been enabled via input 10 11 and started via input 12 13 Cleaning On Val No Down time cleaning active DTC Cleaning...

Page 14: ...Relay output 8 9 to control extractor elements If automatic components for dust removal extractor elements are fitted these need to be in operation during cleaning and during down time cleaning Connec...

Page 15: ...r element contactor Contactor which switches an extractor element drive unit on and off I O module Input output module module for the input and output of control signals Operation mode Status of the R...

Page 16: ...ell 5MT 300 mA ESKA UL 521 012 Temperature range 20 C to 50 C Protection class Housing IP 66 not evaluated by UL Type 5 Installation torque of cover screws 1 5 Nm Weight approx 0 8 kg Installation hei...

Reviews: