FC-20 Series – Firmware Upgrade v1.3
18
Step 6
The window below will show the total number of Modbus devices.
If there is a duplicate Modbus address in the bus, it will prompt an error and the scan will be stop.
Step 7
Hit Set button and the program will set the selected serial settings to all the device listed in the window.
The device do not need a power cycle or reboot for the serial settings to take effect. Try rescanning again
to confirm the serial settings.