6
Output voltage range
184~265 Vac (VDE)
193.6~242Vac(Taibei)
Output voltage comeback value
194/255 Vac(VDE)
203.6/232 Vac(Taibei)
Operational frequency range
47.5 ~ 50.2 Hz (50Hz)
59.3~ 60.5Hz(60Hz)
Output frequency comeback
value
47.6/50.1 Hz(50Hz)
59.4/60.4Hz(60Hz)
Max output current
13.6A
Under the output voltage is 220VAC
O/P current distortion
<3%
Under utility voltage THD<3%
Power Factor
>0.99
Battery mode output data
Nominal output power
3000W
Wave form
Pure sine wave
Nominal output voltage
1%
Optional
:
208/220/240 Vac
Nominal output frequency
50 Hz+ 0.1Hz
O/P voltage distortion
<3% for linear load
<5% for non- linear load
O/P DC component
<50mV
Transient O/P voltage range
230+/-10%
Transient Time
120ms
Maximum Conversion Efficiency
(DC/AC)
92%
Overload capability
Line Mode
> 110%
Overload alarm for 5 min, and then will
switch to fault mode.
If user decrease the load <100%
rating, the overload alarm can release.
> 150%
Overload alarm for 1 min, and then will
switch to fault mode.
If user decrease the load <100%
rating, the overload alarm can release.
> 200%
Switch to fault mode immediately
Battery Mode
> 110%
Overload alarm for 1 min, and then will
switch to fault mode.
If user decrease the load <100%
rating, the overload alarm can release.