Register
Serial
Number
Parameter
Register start
address
(
Hex
)
The value description
Patter
n
High
Byte
Low
Byte
40013
Pulse 1 output
pulse width
00
OC
Set range
:
60, 100, 200
,
Unit:ms
,
Default:35. Note
:
If the pulse constant of pulse 1 =1000imp/kWh
,
Then
the automatic fixation is 35ms
,
can’t be set.
Data length : 4 byte
Data type : Float
Read/
Write
40019
Parity bit and
stop bit
00
12
Set range
:
0~3
,
Default 0
0 Stands for 1 stop bit, no parity
;
1 Stands for 1 stop bit, even parity
;
2 Stands for 1 stop bit
,
odd parity
;
3 Stands for 2 stop bit
,
no parity.
Data length : 4 byte
Data type : Float
Read/
Write
40021
Modbus
address
00
14
Set range
:
1~247
,
Default 1
Data length : 4 byte
Data type : Float
Read/
Write
40023
Pulse 1
pulse constant
00
16
Set range 0~3
,
Default 0
0
Stands for 1000 imp/kWh
1
Stands for 100 imp/kWh
2
Stands for 10 imp/kWh
3
Stands for 1 imp/kWh
Note: if the pulse constant of pulse 1=1000imp/kWh
,
it is automatically fixed to 35ms , cannot be set.
Data length : 4 byte
Data type : Float
Read/
Write
40025
Password
00
18
Set range 0000 ~ 9999
,
Default1000
Data length : 4 byte
Data type : Float
Read/
Write
40029
Baud rate
00
1C
Settable value
:
0, 1, 2, 5
,
Default2.
0
Stands for 2400 bps
1
Stands for 4800 bps
2
Stands for 9600 bps
5 Stands for 1200 bps
Data length : 4 byte
Data type : Float
Read/
Write
40059
Automatic
scrolling display
00
3A
Set range 0~30
,
unit
:
second
,
Default0.
0 Stands for no scrolling display
。
Data length : 4 byte
Data type : Float
Read/
Write