background image

5

GLOSSARY:

AGM – Absorbed Glass Mat –

A class of VRLA (Valve

Regulated Lead-Acid) battery in which the electrolyte is
absorbed into a glass mat. 

Ambient Temperature –

The average temperature of the 

battery room. Temperatures below 77°F (25°C) will reduce
battery capacity. Temperatures above 77°F (25°C) will
reduce battery service life.

Amp Hour (Ah) –

Amps times Hours

Battery Efficiency –

The amount of Ah return required 

to achieve full SOC vs. the amount of Ah removed during 
discharge. Require 110% to 115% Ah return.

Capacity –

The capacity of a battery is specified as the 

number of Amp-Hrs that the battery will deliver at a specific
discharge rate and temperature. The capacity of a battery is
not a constant value and is seen to decrease with increasing
discharge rate.

C20 –

Battery capacity measured in Ah (amp hour) at the

20hr rate.

End Voltage –

The minimum voltage at which a DC system

will operate. 

Flooded –

A battery in which the products of electrolysis 

and evaporation are allowed to escape to the  atmosphere 
as they are generated. Electrolyte is free flowing throughout
the battery.

Gel –

A class of VRLA (Valve Regulated Leda-Acid) battery

in which the electrolyte is immobilized in a gel form (sulfuric
acid mixed with silica).

Parallel –

A circuit that provides more than one path for the

flow of current. A parallel arrangement of batteries (usually
of like voltages and capacities) has all positive terminals
connected to a conductor and all negative terminals con-
nected to another conductor. If two 12-volt batteries of 50
ampere-hour capacity each are connected in parallel, the 
circuit voltage is 12 volts, and the ampere-hour capacity of
the combination is 100 ampere-hours.

Series –

A circuit that has only one path for the flow of 

current. Batteries arranged in series are connected with 
negative of the first to positive of the second, negative of the
second to positive of the third, etc. If two 12-volt batteries
of 50 ampere hours capacity each are connected in series,
the circuit voltage is equal to the sum of the two battery
voltages, or 24 volts, and the ampere-hour capacity of the
combination is 50 ampere-hours.

SOC (State of Charge) –

The amount of deliverable 

low-rate electrical energy stored in a battery at a given time
expressed as a percentage of the energy when fully charged
and measured under the same discharge conditions. If the
battery is fully charged the “SOC” is said to be 100%.

Temperature Correction –

A factor used to compensate for

battery capacity and/or adjust battery voltage at ambient
temperatures greater than or less than 77°F (25°C).

Undercharge (Deficit charge) –

Charging a battery with less

ampere-hours (Ah) than is required to return the battery to
its initial state-of-charge. This results in a reduction in the
battery state-of-charge.

VPC –

Volts per Cell

VRLA –

Valve Regulated Lead Acid – a lead-acid cell/battery

that is sealed with exception of a valve that opens to the
atmosphere when the internal gas pressure exceeds atmos-
pheric pressure by a pre-selected amount. VRLA batteries
provide a means for recombination of internally generated
oxygen and the suppression of hydrogen gas evolution to
limit water consumption.

Summary of Contents for Deka SOLAR

Page 1: ...Renewable Energy Technical Manual ...

Page 2: ... 3 Series Parallel Wiring 3 Glossary 5 APPENDIX A Renewable Energy Worksheet 6 APPENDIX B Example of Typical 3 Stage Charger 7 APPENDIX C Example of Depth of Discharge vs Freezing Point 8 TABLE OF CONTENTS PROPOSITION 65 WARNING Battery posts terminals and related accessories contain lead and lead compounds chemicals known to the State of California to cause cancer and reproductive harm Batteries ...

Page 3: ...sus ceptible to freezing in a particular application If the electrolyte would freeze the internal damage would be irreversible requir ing the battery to be replaced Depth of Discharge DoD Depth of discharge is a function of design The deeper the discharge per cycle the shorter the life of the battery A cycle is a discharge and its subsequent recharge regardless of depth of discharge Systems should...

Page 4: ...cturer should be used to ensure the most energy is returned to the batteries The below calculation will assist in identifying the necessary maximum charge current for the system If the calculation shows the absorption time is greater than the minimum average peak sun hours for the installation location the amount of available current to the batteries should be increased which could be accomplished...

Page 5: ...trength and adequately anchored to the floor Battery rack design and anchoring should be reviewed by a structural engineer Ventilation It is the responsibility of the installer to provide detailed methods or engineering design required by Federal State and local regulations to maintain safe levels of hydrogen in battery rooms enclosures The rate of hydrogen evolution is highest when the battery is...

Page 6: ...gy source Wiring connection assessment difficult to follow with multiple wirings connected to same battery terminal increasing chance of re connection wiring errors Common bus wiring A wiring scheme in which same polarity terminals are con nected to a single termination point All interconnecting wiring should be of same length to minimize voltage drop Advantages Cables can be of same gauge Mainten...

Page 7: ... conductor If two 12 volt batteries of 50 ampere hour capacity each are connected in parallel the circuit voltage is 12 volts and the ampere hour capacity of the combination is 100 ampere hours Series A circuit that has only one path for the flow of current Batteries arranged in series are connected with negative of the first to positive of the second negative of the second to positive of the thir...

Page 8: ...6 APPENDIX A Completing all parameters ensures accurate battery sizing Worksheet to be submitted to sales representative for battery recommendation ...

Page 9: ...7 APPENDIX B Example of typical 3 stage charger ...

Page 10: ...om the company Domestic Inquiries Call 1 800 372 9253 www mkbattery com e mail sales mkbattery com East Penn Manufacturing Co Lyon Station PA 19536 0147 Domestic International Inquiries Call 610 682 3263 Phone 610 682 6361 Fax 610 682 0891 www dekabatteries com e mail reservepowersales dekabatteries com APPENDIX C Below graph is for general reference only Consult specific battery Installation Oper...

Reviews: