16
Stated values are maximum values (see electrical data for exact values).
8.4 Remove the switch box cover
Voltage
(V)
Hz
Min.
(V)
Max.
(V)
MCA
(A)
TOCA
(A)
MFA
(A)
MSC
(A)
RLA
(A)
KW
FLA
(A)
Outdoor Unit
Power Current
Compressor
OFM
1
1
1
1
14
18
-
13.50
0.10
0.50
264
25
220-240 50
198
-
14.50
0.17
1.50
16
19
264
25
220-240 50
198
-
17
19
15.50
0.17
1.50
264
198
25
220-240 50
12
25
-
0.10
0.50
220-240 50
198
264
18
11.50
System
6kW
4kW
8kW
10kW
-
25
30
23.50
0.17
1.50
264
198
35
220-240 50
12kW
-
26
30
24.50
0.17
1.50
264
198
35
220-240 50
14kW
1
-
27
30
25.50
0.17
1.50
264
198
35
220-240 50
16kW
-
10
14
9.15
0.17
1.50
456
342
16
380-415 50
12kW 3-PH
1
-
11
14
10.15
0.17
1.50
456
342
16
380-415 50
14kW 3-PH
-
12
14
11.15
0.17
1.50
456
342
16
380-415 50
16kW 3-PH
1. Select the wire diameters( minimum value) individually for each unit based on the table 8-1 and table 8-2
where the rated current in table 9-1 means MCA in table 9-2. In case the MCA exceeds 63A, the wire diameters
should be selected according to the national wiring regulation.
2. Select circuit breaker that having a contact separation in all poles not less than 3 mm providing full
disconnection
where MFA is used to select the current circuit breakers and residual current operation
breakers:
8.3 Safety device requirment
Table 8-2
Rated current
of appliance:
Nominal cross-sectional area (mm )
2
Flexible cords
Cable for fixed wiring
Table 8-1
≤
3
0.5 and 0.75
1 and 2.5
>
3 and
≤
6
0.75 and 1
1 and 2.5
>
6 and
≤
10
1 and 1.5
1 and 2.5
>
10 and
≤
16
1.5 and 2.5
1.5 and 4
>
16 and
≤
25
2.5 and 4
2.5 and 6
>
25 and
≤
32
4 and 6
4 and 10
>
32 and
≤
50
6 and 10
6 and 16
>
50 and
≤
63
10 and 16
10 and 25
NOTE
MCA :
Max. Circuit Amps. (A)
TOCA :
Total Over-current Amps. (A)
MFA :
Max. Fuse Amps. (A)
MSC :
Max. Starting Amps. (A)
RLA :
In nominal cooling or heating test condition
the input Amps of compressor where MAX. Hz
can operate Rated Load Amps. (A);
KW :
Rated Motor Output
FLA :
Full Load Amps. (A)
Unit
4kW
6kW
8kW
10kW
12kW
14kW
16kW
12kW 3-PH 14kW 3-PH
16kW 3-PH
Maximum
overcurrent
protector(MOP)(A)
18
18
19
19
30
30
30
14
14
14
Wiring size(mm
2
)
4.0
4.0
4.0
4.0
6.0
6.0
6.0
2.5
2.5
2.5
V.2