EARTHSTONE OVENS PRE-ASSEMBLED GAS OVEN INSTALLATION INSTRUCTIONS – ETL LISTED
17
GAS PRESSURE
Please follow the gas requirements listed below:
Inlet Gas Pressure 7” W.C. for Natural Gas - 12”W.C. for LP gas
Manifold Pressure: The amounts listed below are set at the factory.
Natural Gas Manifold pressure
60-PAGW
4” W.C.
45,000 btu
90-PAGW
4” W.C.
85,000 btu
110-PAGW
5” W.C.
110,000 btu
120-PAGW
3.5" W.C. 130,000 btu
130-PAGW
5” W.C.
140,000 btu
160-PAGW
4.5” W.C. 170,000 btu
Add 0.5” W.C. for ovens with rear burner.
LP Gas Manifold pressure
60-PAGW
7”W.C.
45,000 btu
90-PAGW
10” W.C.
85,000 btu
110-PAGW
10” W.C.
110,000 btu
120-PAGW
10" W.C.
130,000 btu
130-PAGW
10” W.C.
140,000 btu
160-PAGW
10” W.C. 170,000 btu
The inlet and manifold (outlet) pressure taps are located at the Gas Control Valve. This
part is in the burner controls box and attached to the oven support stand.