Fuel Systems for Critical Power
Planning the Installation
Location
1. Location
— always locate the pump as close as possible to the supply of liquid to be
pumped. Locate it below the liquid supply if at all practical. Viking pumps are self priming
but the better the suction conditions the better the performance.
2. Accessibility
— the pump should be located where it is accessible for inspection,
maintenance, and repair.
Pressure Relief
Pressure Protection
— Viking pumps are positive displacement. This means that when the
pump is rotated, liquid will be delivered to the discharge side of the pump. If there is no place
for this liquid to go — discharge line is blocked or closed — pressure can build up until the
motor stalls, the drive equipment fails, a pump part breaks or ruptures, or the piping bursts.
Because of this, an integral pressure relief valve is mounted directly on the pump head.
EMERGENCY POWER FUEL SYSTEMS
Model M300
Filtration Polisher
INSTALLATION, OPERATION, AND MAINTENANCE