CREATED ON: April 28, 2016

 

 

  Wiring

 

    System Type : Star/Wye 

 
 
 
 
 
 

 

 
 
 
     

 

        

    

Keys and Operation 

RUN Mode 

 

Once there is power failure, energy, Load/hour, Display Status will be 
saved. 

 

RS485 communication status can be viewed in Page 1 “DEV ID” 
parameter.”T” for transmit, ”R” for receive & “U” for device ID 
mismatch. 

PROGRAM  Mode 

 

SELECT Key 

RUN Mode             

: used to select the required page.

 

PROGRAM MODE 

: used to enter into program mode. 

                               : used to select digits. 

 

ADVANCE Key 

RUN Mode

             : used to view the pages. 

PROGRAM Mode

  : used to increase the value by one

 

 

PREVIOUS Key 

RUN MODE

 : used to view previous pages and parameters 

PROGRAM MODE

: used to program previous parameters. 

 

NEXT Key 

RUN MODE

: used to view next pages and parameters 

PROGRAM MODE

: used to program next parameters. 

SCROLL/HOLD Key 

RUN MODE

:used to scroll/hold the parameters 

 

Program 

page 

Function 

Range 

Factory 

setting 

PASSWd 

0001 to 9999 

1000 

CT-PRI 

1A to 5000A 

CT-SEC 

1A to 5A 

PT-PRI 

110V to 999KV 

415 

PT-SEC 

110V to 500V 

415 

CLR-EN 

Y/N 

dEV-Id 

1 to 247 

001 

bAUd 

2400,4800,9600 

and 19200(bps) 

9600 

POLES 

1 to 28 

04 

10 

PLSOUT 

Active energy/ 

Reactive energy 

11 

ChPASS 

0001-9999 

0001 

    Technical Specification    

   

   

 

 

Disposition

 

             

                                                                                   

 

Once the product life is over, you may send back the unit to EAPL for       

 

      disposition              

Contact

 

Electronic Automation Pvt. Ltd 
#20, KHB Industrial Area                                                                                                     
Yelahanka, Bangalore -560064 
Ph: +91-80-28567561/2, /42802345  
Email:  

[email protected]

      

www.eaplindia.com

 

Product Function 

 

Multi Function Meter 

Rated voltage(Aux.Supply) 

24V DC ±10% 

Power consumption                                

< 1W  

Input voltage 

3 Phase 4 wire (R,Y,B,N ) 

 

Range - 415 VAC (-40% to +20%) 

 

               110 VAC (-40% to +20%) 

Input current                                           

Current inputs (AR, AY, AB) 
1A to 5A (to 200%)                                                                                          

Input Frequency 

50 Hz, 

±

 2% 

 

Burden 

< 0.2 VA per Volts/Amps input 

Accuracy 

Class 0.5 

Recovery Time 

2 sec minimum. 

Communication 

RS-485 MODBUS RTU Protocol 

Meter Constant 

3200 Pulses / KWh 

3200 pulses / KVArh

 

Ambient Temperature                                                                                                     

Operation : -10°C to + 55°C(14°F to131°F) 

Storage :  -25°C to + 80°C(-13°F to 176°F) 

Humidity 

Up to 95% RH @ 40°C 

OD RE KN 540011 REV 02/28-04-16

 

 

Page 2 of 2 

1, 2, 3, 4

  :  R, Y, B, N

 

5 ,6

          :  No connection 

7,8

           :  A,B (RS 485Communication port) 

9, 10

        :  S1, S2 (R Phase) 

11,12

       :  S1, S2 (Y Phase) 

13,14

       :  S1, S2 (B Phase) 

15,16

       :  Auxilary Supply(24V DC±10%) 