OPERATION AND TROUBLESHOOTING GUIDE 

 

OPERATION AND MAINTENANCE 

ELECTRICAL WIRING 

Every DC power unit from Eagle Hydraulic is assembled with a solenoid starter assembly that is mounted on the motor.  
Independent battery leads must be connected to the terminals of the DC motor and solenoid starter.  See the drawing  
below: 

 

Connect the positive side of the battery to the positive side of the solenoid starter (B), mounted on the electrical motor. 
Then, connect the negative side of the battery to the ground terminal (F) on the motor. 
 
Select the proper cable size to connect the battery to your Eagle Hydraulic power unit from the chart below. Improper 
cable sizing may create problems if it is too small for the load of the power unit or if the cables are too long.  Selecting the 
proper cable size is especially important if the unit is further than 25 feet from the battery.  Eagle Hydraulic recommends 
that the ground cable size be equivalent or larger than the battery "hotside" cable. 
 

60-70 ft 

#1 

#00 

 

 

 

50-60 ft 

#2 

#0 

#0 

 

 

40-50 ft 

#2 

#1 

#0 

#00 

 

30-40 ft 

#4 

#1 

#0 

#00 

#00 

20-30 ft 

#4 

#2 

#1 

#0 

#00 

10-20 ft 

#4 

#2 

#1 

#0 

#00 

0-10 ft 

#4 

#2 

#1 

#0 

#00 

 

0-100 amp 

100-150 amp 

150-200 amp 

200-250 amp 

250-300 amp 

 

 

N.B. If in doubt, always consult with a qualified automotive electrician for correct connection of DC electrical devices. Low voltage could cause 

damage to the DC motor.  DC motors should not be run for extended periods (Consult technical data for duty cycles).

 

 
 
 
 
 

Summary of Contents for Hydraulic

Page 1: ...OPERATION AND TROUBLESHOOTING GUIDE 12 24 volt DC Power Units Revision 2 0 2018...

Page 2: ...r warranty Any disassembly or modification made on a power unit that is still under warranty will automatically VOID that warranty Eagle Hydraulic stands behind their products All our power units are...

Page 3: ...unit from the chart below Improper cable sizing may create problems if it is too small for the load of the power unit or if the cables are too long Selecting the proper cable size is especially import...

Page 4: ...vice life with just a few maintenance checks at regular intervals Oil Level the level of oil inside the tank should be verified every day and topped up if necessary If you see a change in the need of...

Page 5: ...ou can encounter and what you should verify in each case SYMPTOM OR PROBLEM VERIFICATION TO DO The motor is not running Check the connection from your power supply to the DC motor Check the power to t...

Page 6: ...down too quickly Orifice might have some debris If unit is an Option 12 or 24 Verify that the solenoid starter operates the directional valve Operate actuator back and forth and make sure it works in...

Page 7: ...advice and support All unit returns must be authorized by Eagle Hydraulic and must be accompanied by a RGA number In the invent that you need to send you power unit back please make sure that there i...

Page 8: ...12055 Arthur Sicard Mirabel Qu bec J7J 0E9 450 433 2800 T 450 433 3004 F info eagle hydraulic com PROUDLY ASSEMBLED AND TESTED IN CANADA...

Reviews: