(MNU) SETUP MENU
This screen allows one access to the calibration, configuration, and alarm set point screens. All selections require
one to enter a password before access is allowed.
CAL: Access the sensor inputs and analog output calibration menu
CFG: Access the configuration parameters (full-scale, relay assignments, etc.)
ALM: Access the danger and critical alarm set points for each channel.
ESC: Return to the main screen.
Screen time-out is ten-seconds (returns to main screen).
(CAL) CALIBRATE ANALOG MENU SCREEN (password protected)
If CAL is selected under the SETUP MENU, the CAL ANALOG MENU is displayed.
SNS: Access the CAL GAS SENSOR INPUT selection screen.
OUT: Access the CAL OUT SELECT screen.
NOTE: When this menu and sub screens are accessed, the sensor alarms are deactivated and the analog outputs are forced to 4mA.
Screen time-out is two-minutes (returns to the setup menu and then the main screen).
(SNS) CALIBRATE GAS SENSOR 4-20mA INPUT SCREEN
CH1/CH2: Select channel one (CH1/PV1) or channel two (CH1/PV2).
mA: Calibrate the inputs using a 4-20mA calibrator (accesses sub menu).
ESC: Return to the last menu.
Screen time-out is two-minutes (returns to the CAL ANALOG MENU).
Gas sensor calibration is documented later in this manual.
(OUT) CALIBRATE ANALOG OUTPUTS SCREEN
Select channel one (CH1/PO1) or channel two (CH2/PO2).
Press ESC to return to the last menu.
Screen time-out is two-minutes (returns to the CAL ANALOG MENU).
Analog output (4-20mA) calibration is documented later in this manual.
(CFG) CONFIGURATION (password protected)
Configuration is documented later in this manual.
(ALM) DANGER/CRITICAL ALARM SET POINTS
(password protected)
Pressing ALM will access the danger (DGR) and critical (CRT) alarm set points for each channel.
NXT: Select next set point
LST: Select last set point
ADJ: Adjust set point – see below
ESC: Return to the SETUP MENU screen.
INC/DEC adjusts the set point value.
When adjusting the set point, one must press ENT to accept the new value entered.
If ESC is pressed, any change to the set point will be ignored and the original set
point value will be restored.