3
Installation
2
4
1
KO-II
MANUAL
KOP 160-250-400A Tap Off Boxes Installation
1- Open Plug-in cover by using screw driver.
2- Release the plastic headed bolt to loosen
mechanical fixing clamps. Push left side of tap-off box
towards busbar and lock fixing clamps to the busbar.
Tight back the plastic headed bolt to hold busbar rigidly.
3- Carefully align the tap-off box contacts and push
right side of tap-off box towards to busbar and be sure
fixing tap-off box firmly.
4- Tight the plastic headed bolt on the right side
to fix the tap-off box mechanicaly to the busbar.
ENGLISH
16