European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH           www.e2s.com              Tel: +44 (0)208 743 8880 

Document No. D204-00-001-IS           Issue 7        16-12-2022                         Sheet 5 of 6                                                                                            

 

 

 
Once the cover is removed the broken glass will be free to be 
removed, clean out any other fragments of glass carefully. 
 

 

 
To fit the new glass element rotate the top cam clockwise by 
an angle of 50º (use a 6mm Allen key) this will than allow the 
glass to fit back into the pocket it sits in, resting on the pivot 
point and test cam, release the top cam to rest on the top of 
the glass element. 
 

    

 

    

 

 
 
Pivot point     Test Cam 

 

Rotate test cam back 

 

 

 

 

Upright set point 

 
Replace  the  cover  plate  and  tighten  the  4  off  M4  cap  head 
screws. 
 
Ensure  the  glass  element  is  free  to  move  under  the  cover 
plate.  This  can  be  done  by  running  through  the  units  test 
operation. See section 13 of this instruction manual. 
 
 
 
 
 
 

15)  End-of-Line and Series Devices 

 

All  models  can  be  fitted  with  series  resistors,  end-of-line 
monitoring  resistors,  monitoring  diodes  and  zener  diodes  if 
supplied with direct current up to 48Vdc. 
 
Min. resistor values and current limitations must be observed 
depending on supply voltage and type of components fitted. If 
a  combination  of  resistors  /  diodes  /  zener  diodes  is  used, 
values  for  all  components  must  be  observed  and  lowest 
current limit for either component becomes overall limit. 
 
Current  limitation  for  units  fitted  with  end-of-line  resistors, 
diodes  or  zener  diodes  must  be  ensured  by  using  a  current 
limited power supply or fitting a current limiting resistor at the 
control panel (not provided). 
 
The  following  table  1  shows  limitations  for  all  possible 
variations: 

 

* note :- EOL and series resistor values  are listed 
as the minimum resistor value allowable at the 
specified minimum wattage.

 

 
EOL (End of line) device; 

 

resistor – ExxxR 

 

diode – ED1 

 

zener – ExxxZ  
 

Series (In line) device; 

 

resistor – SxxxR 

 

diode – SD1 

 

zener – SxxxZ 

 

LED  
 

Microswitch 1 = M/S 1 
Microswitch 2 = M/S 2 

 

Supply voltage 

24Vdc 

Supply voltage 

48Vdc 

Type of 
component fitted 

value 

Max. 
current 

value 

Max. 
current 

End-of-Line 
Resistor 
*See note 

min. 
470R 

/  

2W 
or 
min.  2k2 
/ 0.5W 

3.0 A 

min. 
2k2  / 
2W 
or 
min. 
8k2  / 
0.5W 

1.0 A 

End-of-Line Diode 
Type 1N5401 

2W 

59.13 
mA 

2W 

25.26 mA 

Series Resistor 
*See note 

min. 
470R 

/  

2W 
or 
min.  2k2 
/ 0.5W 

3.0 A 

min. 
2k2  / 
2W 
or 
min. 
8k2  / 
0.5W 

1.0 A 

Series Diode 
Type 1N5401 

2W 

59.13 
mA 

2W 

25.26 mA 

Series Zener 
Diode Type 
1N5333B 

3.3V 

230 mA 

3.3V 

230 mA 

4.7V 

162 mA 

4.7V 

162 mA 

5.1V 

149 mA 

5.1V 

149 mA 

5.6V 

136 mA 

5.6V 

136 mA 

6.2V 

122 mA 

6.2V 

122 mA 

6.8V 

112 mA 

6.8V 

112 mA 

10V 

76 mA 

10V 

76 mA 

12V 

63 mA 

12V 

63 mA 

Summary of Contents for STExCP8-BG-D

Page 1: ...tified Body No The units can be installed in locations with the following conditions Area Classification Gas Zone 1 Explosive gas air mixture likely to occur in normal operation Zone 2 Explosive gas a...

Page 2: ...the base Insert the M6 x 40 cover bolts and fully tighten down tightening torque 8 8Nm ensuring no gap is visible between the cover and base of the enclosure The metallic enclosure has a non conductiv...

Page 3: ...max 5 0A max 48Vdc max 1 0A max 24Vdc max 3 0A max A supply voltage variation of 10 outside the voltage range is permissible Electrical connections are to be made into the terminal blocks DIN rail pro...

Page 4: ...s see Section 15 For wiring schematic see document D204 06 001 Wiring Diagram For 8 Way DIN Rail Fig 4 DIN Rail in Base Wiring Diagram For 6 Way PCB Terminal Board Fig 5 PCB Terminal Block in Base See...

Page 5: ...e observed depending on supply voltage and type of components fitted If a combination of resistors diodes zener diodes is used values for all components must be observed and lowest current limit for e...

Page 6: ...nit must only be cleaned with a damp cloth Units must not be opened while an explosive atmosphere is present 17 SIL 2 Reliability Data Reliability and Functional safety IEC EN61508 which has been asse...

Page 7: ...DOS PARAFUSOS DA TAMPA A4 70 N O ABRA QUANDO HOUVER GASES OU P S EXPLOSIVOS NO AMBIENTE POTENCIAL PERIGO DE DESCARGA ELETROST TICA TODAS AS ENTRADAS M20 X 1 5 SE A TEMPERATURA EXCEDER 70 C NA ENTRADA...

Page 8: ...ente se tornar o limite geral A limita o de corrente para unidades equipadas com resistores de fim de linha diodos ou diodos zener deve ser garantida usando uma fonte de alimenta o limitada de corrent...

Page 9: ...to M5 usando um terminal de crimpagem para fixar o condutor de aterramento ao terminal de aterramento O condutor de terra externo deve ter pelo menos 4 mm de tamanho Ao concluir a instala o das jun es...

Page 10: ...e can be fitted either by customer or pre installed by E2S at point of order When fitting diodes or zener diodes polarity across devices must be observed Resistor polarity is unimportant SERIES EOL Wi...

Page 11: ...07 2019 D204 06 001 FOR PERMITTED MIN MAX VALUES OF EOL SERIES DEVICES PLEASE REFER TO INSTRUCTIONS Standard Unit showing positions of optional Series and EOL Devices 1 2 3 4 5 6 M S 1 M S 2 7 8 N O...

Page 12: ...open 1 2 3 4 5 6 M S 1 M S 2 7 8 N O COM 4A Circuit as shown in Unoperated condition Terminals 1 4 M S 1 and 5 8 M S 2 open Terminals 1 3 M S 1 and 5 7 M S 2 closed N C N O COM N C 1 2 3 4 5 6 M S 1 M...

Page 13: ...shown in Operated condition Terminals 1 2 M S 1 and 4 5 M S 2 open Terminals 1 3 M S 1 and 4 6 M S 2 closed STExCP8 R N POTTS R S RAIT 03 07 2019 B ISARD Optional Single or Double Microswitch Circuit...

Page 14: ...ion Service Notified BodyNo 2813 CSAGroup Netherlands B V Utrechtseweg 310 6812AR Arnhem Netherlands Quality Assurance Notification ModuleD SIRA 05 ATEX M342 Provisions fulfilledby theequipment II 2G...

Page 15: ...er Date andPlace of Issue London 23 12 2020 EU Declaration of Conformity On behalf of European SafetySystems Ltd I declarethat on the date the equipment accompanied by this declaration is placed onthe...

Page 16: ...n Module D CSAE 22UKQAN0046 Provisions fulfilled by the equipment II 2G Ex db IIC T5 Gb II 2G Ex db IIC T6 Gb Standards applied EN IEC 60079 0 2018 EN 60079 1 2014 Directive 2014 30 EU Electromagnetic...