INSTRUCTION & SERVICE MANUAL

 

SONFL1H Range 

-

 Alarm Horn & L.E.D Beacon

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

800/1000 Hz @ 0.25 sec Alternating BS5839 Alarm Tone

500/1200 Hz @ 0.3 Hz 0.5 sec Slow Whoop NEN 2575:2000

544Hz (100mS)/440 Hz (400mS) AFNOR NF S 32 001

Simulated Bell Sound

Sweeping 800/1000 Hz @ 7 Hz Sweeping

500 1200 Hz 3.75 sec / 0.25 sec Australian Evacuation

Continuous 1000 Hz   PFEER toxic gas

Continuous 554 Hz

420 Hz @ 0.625 sec Australian Alert

1

2

3

4

5

6

7

8

9

Sawtooth 1200/500 Hz @ 1 Hz   DIN / PFEER P.T.A.P

10

8

8

8

1

1

9

10

Tone Description

Stage 1

Stage 2

 

 

 

99dB(A) @1m

100dB(A) @1m

99dB(A) @1m

97dB(A) @1m

95dB(A) @1m

99dB(A) @1m

100dB(A) @1m

100dB(A) @1m

97dB(A) @1m

97dB(A) @1m

SONF1 dB@ 1m

800/1000 Hz @ 0.25 sec Alternating BS5839 Alarm Tone

500/1200 Hz @ 0.3 Hz 0.5 sec Slow Whoop NEN 2575:2000

544Hz (100mS)/440 Hz (400mS) AFNOR NF S 32 001

800/1000 Hz @ 7 Hz Sweeping

2400/2900 Hz 50 Hz Sweeping

1

2

3

4

5

6

7

8

9

Sawtooth 1200/500 Hz @ 1 Hz   DIN / PFEER P.T.A.P

10

Tone Description

Stage 1

Simulated Bell Sound

Continuous 1000 Hz   PFEER toxic gas

420 Hz @ 0.625 sec Australian Alert

500 1200 Hz 3.75 sec / 0.25 sec Australian Evacuation

99dB(A) @1m

100dB(A) @1m

99dB(A) @1m

97dB(A) @1m

100dB(A) @1m

95dB(A) @1m

99dB(A) @1m

100dB(A) @1m

97dB(A) @1m

100dB(A) @1m

115V AC and 230V AC Tone Table

 

12V DC and 24V DC Tone Table

 

DC

Tone
Settings

AC
Tone
Settings

Tone 1

Tone 2

Tone 3

Tone 4

Tone 5

Tone 6

Tone 7

Tone 8*

Tone 9*

Tone 10*

*To set tones 8, 9 & 10 as first 
stage on DC, connect terminal 

S2

’ 

to 

-

’ 

terminal

 

NOTE: Please check factory settings and ensure the correct alarm tone is selected for your country or application

 

 

Tone Selection / Header Pin Setting 

-

 Header pin settings are shown in the tone selection table. The links covered by the jumper are 

shown with a black rectangle.

 

 

Torque 5Nm

 

Disassembly

 

Reassembly

 

Beacon Flash Settings

   

See D228

-

00

-

001

-

IS

 

Mounting

   

See D242

-

05

-

501

 

Loosen posi

-

pan screws

 

in four positions to 
access enclosure

 

Access to Enclosure

 

           

           

           

               

                   

                   
           

                        
                      
                 

                
           

             
                  

Switch 

Setting

 

Flash Mode

 

0 0 0

 

Steady on

 

1 0 0

 

Blinking

 

0 1 0

 

Flashing 1Hz*

 

1 1 0

 

Flashing 1.5Hz*

 

0 0 1

 

Flashing 

-

 Double Strike

 

1 0 1

 

Flashing 

-

 Triple Strike

 

0 1 1

 

Flashing 2Hz*

 

1 1 1

 

Flashing 

-

 Temporal

 

Voltage

 

Intensity (cd) at 

1Hz flash rate

 

Intensity (cd) at 

1.5Hz flash rate

 

Intensity (cd) at 

2Hz flash rate

 

12V dc

 

5.9

 

5.97

 

6.35

 

24V dc

 

11.65

 

12.32

 

12.38

 

115V ac

 

12.99

 

12.65

 

14.1

 

230V ac

 

13.12

 

13.22

 

13.45

 

On

-

axis Light Output Rating per UL1638

 

         

  

Flash Mode DIP Switch 

-

 

Shown with 1

-

OFF, 2

-

ON, 3

-

OFF (0 1 0), This denotes 
Flash mode 1Hz. For further 
flash modes refer to table.

 

*Setting permitted for use as private 
mode fire alarm device

 