E2S Warning Signals
Impress House, Mansell Road, Acton, London W3 7QH
[email protected] e2s.com
Page 2 of 2
D242
-
00
-
601
-
IS_Issue_2
-
03/06/2021
INSTRUCTION & SERVICE MANUAL
SONFL1H Range
-
Alarm Horn & L.E.D Beacon
800/1000 Hz @ 0.25 sec Alternating BS5839 Alarm Tone
500/1200 Hz @ 0.3 Hz 0.5 sec Slow Whoop NEN 2575:2000
544Hz (100mS)/440 Hz (400mS) AFNOR NF S 32 001
Simulated Bell Sound
Sweeping 800/1000 Hz @ 7 Hz Sweeping
500 1200 Hz 3.75 sec / 0.25 sec Australian Evacuation
Continuous 1000 Hz PFEER toxic gas
Continuous 554 Hz
420 Hz @ 0.625 sec Australian Alert
1
2
3
4
5
6
7
8
9
Sawtooth 1200/500 Hz @ 1 Hz DIN / PFEER P.T.A.P
10
8
8
8
1
1
9
10
Tone Description
Stage 1
Stage 2
99dB(A) @1m
100dB(A) @1m
99dB(A) @1m
97dB(A) @1m
95dB(A) @1m
99dB(A) @1m
100dB(A) @1m
100dB(A) @1m
97dB(A) @1m
97dB(A) @1m
SONF1 dB@ 1m
800/1000 Hz @ 0.25 sec Alternating BS5839 Alarm Tone
500/1200 Hz @ 0.3 Hz 0.5 sec Slow Whoop NEN 2575:2000
544Hz (100mS)/440 Hz (400mS) AFNOR NF S 32 001
800/1000 Hz @ 7 Hz Sweeping
2400/2900 Hz 50 Hz Sweeping
1
2
3
4
5
6
7
8
9
Sawtooth 1200/500 Hz @ 1 Hz DIN / PFEER P.T.A.P
10
Tone Description
Stage 1
Simulated Bell Sound
Continuous 1000 Hz PFEER toxic gas
420 Hz @ 0.625 sec Australian Alert
500 1200 Hz 3.75 sec / 0.25 sec Australian Evacuation
99dB(A) @1m
100dB(A) @1m
99dB(A) @1m
97dB(A) @1m
100dB(A) @1m
95dB(A) @1m
99dB(A) @1m
100dB(A) @1m
97dB(A) @1m
100dB(A) @1m
115V AC and 230V AC Tone Table
12V DC and 24V DC Tone Table
DC
Tone
Settings
AC
Tone
Settings
Tone 1
Tone 2
Tone 3
Tone 4
Tone 5
Tone 6
Tone 7
Tone 8*
Tone 9*
Tone 10*
*To set tones 8, 9 & 10 as first
stage on DC, connect terminal
‘
S2
’
to
‘
-
’
terminal
NOTE: Please check factory settings and ensure the correct alarm tone is selected for your country or application
Tone Selection / Header Pin Setting
-
Header pin settings are shown in the tone selection table. The links covered by the jumper are
shown with a black rectangle.
Torque 5Nm
Disassembly
Reassembly
Beacon Flash Settings
See D228
-
00
-
001
-
IS
Mounting
See D242
-
05
-
501
Loosen posi
-
pan screws
in four positions to
access enclosure
Access to Enclosure
Switch
Setting
Flash Mode
0 0 0
Steady on
1 0 0
Blinking
0 1 0
Flashing 1Hz*
1 1 0
Flashing 1.5Hz*
0 0 1
Flashing
-
Double Strike
1 0 1
Flashing
-
Triple Strike
0 1 1
Flashing 2Hz*
1 1 1
Flashing
-
Temporal
Voltage
Intensity (cd) at
1Hz flash rate
Intensity (cd) at
1.5Hz flash rate
Intensity (cd) at
2Hz flash rate
12V dc
5.9
5.97
6.35
24V dc
11.65
12.32
12.38
115V ac
12.99
12.65
14.1
230V ac
13.12
13.22
13.45
On
-
axis Light Output Rating per UL1638
Flash Mode DIP Switch
-
Shown with 1
-
OFF, 2
-
ON, 3
-
OFF (0 1 0), This denotes
Flash mode 1Hz. For further
flash modes refer to table.
*Setting permitted for use as private
mode fire alarm device