5) 

The equipment has not been assessed as a safety-

related  device  (as  referred  to  by  Directive 

2014/34/EU Annex II, clause 1.5). 

6) 

Installation of this equipment shall be carried out by 

suitably-trained personnel in accordance with the 

applicable code of practice. 

7) 

Repair of this equipment shall only be carried out by 

the manufacturer or in accordance with the 

applicable code of practice. 

8) 

The certification of this equipment relies on the 

following materials used in its construction: 

 

 

 

Enclosure:

 

ABS Plastic 

 

 

Lens:   

Polycarbonate

 

 

If the equipment is likely to come into contact with 

aggressive substances, then it is the responsibility of 

the user to take suitable precautions that prevent it 

from being adversely affected, thus ensuring that the 

type of protection is not compromised. 

 

“Aggressive substances” - e.g. acidic liquids or 

gases that may attack metals, or solvents that may 

affect polymeric materials. 

 

“Suitable precautions” - e.g. regular checks as part 

of routine inspections or establishing from the 

material’s data sheet that it is resistant to specific 

chemicals. 

 

SPECIAL CONDITIONS FOR SAFE USE (as stated in the 

EC Type Examination Certificate SIRA 05ATEX2084X)

 

Conditions for IS-mCl Combined Sounder / Beacon 

 

The  equipment  has  an  ingress  protection  rating  of  IP65. 

However, if it has been supplied without cable entry devices, 

then the user shall ensure that the devices that are fitted will 

provide  an  ingress  protection  that  is  appropriate  to  the 

environment in which it is installed i.e. IP20 or better. If only 

one of the two cable entries are used, then the unused entry 

'knockout' shall be left intact or fitted with a blanking device 

that  ensures  ingress  protection  appropriate  to  the 

environment in which it is installed i.e. IP20 or better. 

 

The total capacitance connected to sounder ter wrt - 

(i.e. the capacitance of the cable plus any other capacitance) 

shall not exceed 83nF. 

 

The  enclosure  is  non-conducting  and  may  generate  an 

ignition-capable  level  of  electrosatic  charges  under  certain 

extreme  conditions.  The  user  should  ensure  that  the 

equipment  is  not  installed  in  a  location  where  it  may  be 

subjected to external conditions that might cause a build-up 

of  electrostatic  charges  on  non-conducting  surfaces, 

additionally, cleaning of the  equipment  should  be  done only 

with a damp cloth. 

  

The equipment shall only be supplied via Sounder Terminals 

+  w.r.t.  Sounder  Terminals  -  from  a  barrier  having  a 

maximum  open  circuit  voltage  Uo  that  is  <  28V  and  a 

maximum short circuit current Io that is < 93mA, where Io is 

resistively  limited.  The  barrier  shall  be  ATEX  certified  by  a 

notified body. 

If  not  already  fitted  optional  internal  wiring  connections 

between Sounder Ter / - and Beacon Ter / - 

may  be  fitted  by  the  user.  The  wiring  used  for  such 

connections  shall  have  a  minimum  radial  thickness  of 

insulation of 0.5mm. 

 

4.2  Zones, Gas Groups and Temperature Classification 

The IS-mC1 minialert unit has been certified Ex ia IIC T4 Ga. 

When connected to an approved system it may be installed 

in: 

 

Zone 0  explosive gas air mixture 

 

continuously present. 

 

Zone 1  explosive  gas  air  mixture  likely  to  occur  in 

normal operation. 

 

Zone 2  explosive gas air mixture not likely  to occur, 

and if it does, it will only exist for a short time. 

 

Be used with gases in groups: 

 

 

 

Group A 

propane 

 

Group B 

ethylene 

 

Group C 

hydrogen 

 

Having a temperature classification of: 

 

T1 

450ºC 

T2 

300ºC 

T3 

200ºC 

T4 

135ºC 

 

4.3  S and - Terminals 

Power  is  supplied  to  the  sounder  section  via  the  sounder 

input ter and – on the sounder PCB (see Fig 2) and 

the terminals have the following input safety parameters: 

 

 

Ui 

28V 

 

Ii 

93mA 

 

Pi 

  660mW 

 

 

Ci = 0  Li = 0 

 

The IS-mC1 combined sounder section may be powered from 

an  ATEX  certified  Zener  barrier  or  galvanic  isolator  which 

have output parameters equal to or less than 28V, 93mA and 

660mW,

 

where Io is resistively limited. The cable parameters 

stated  on  the  selected  Zener  barrier  or  galvanic  isolator 

certificate must be observed. 

 

4.4  Sounder S2 and S3 Terminals 

When terminals S2 or S3 are connected to 0V (- terminal) the 

sounder  output  tone  changes  to  the  second  or  third  stage 

alarm  respectively.    The  input  safety  parameters  for  these 

terminals are: 

 

Ui 

28V 

 

 

Ii 

0mA  

 

Because the permitted input current is zero, these terminals 

may  only  be  connected  to  a  diode  return  barrier,  an 

intrinsically safe relay or a galvanic isolator, all of which must 

have  been  certified  by  an  EC  Notified  Body.      Only  diode 

return barriers with a voltage drop of less than 0.9V may be 

used.  Alternatively,  these  terminals  may  be  connected 

directly  to  a  mechanically  activated  switch  within  the 

hazardous area. 

 

 

 

 

 

 

 

 

 

 

 

 

Summary of Contents for Minialert IS-mC1

Page 1: ...but at supply voltages above 16V the internal current limit will function and therefore it is recommended that they are not operated continuously with a direct supply greater than 16V IS mC1 Sounder S...

Page 2: ...e that the equipment is not installed in a location where it may be subjected to external conditions that might cause a build up of electrostatic charges on non conducting surfaces additionally cleani...

Page 3: ...nd remove the sounder beacon section from the base by turning it anti clockwise Ensure that the O ring seal remains in place b Remove the required 20mm knockout section s depending on system wiring an...

Page 4: ...meet the requirements for the sounder section see section 4 3 Hazardous Area IS mC1 Beacon IS mC1 Sounder 0V Power Supply Safe Area Barrier On Off 28V 93mA Positive Fig 7 Combined Unit wired for simu...

Page 5: ...Intermittent 800Hz 0 25s ON 1s OFF Alternating 544Hz 100ms 440Hz 400ms NFS 32 001 Motor Siren Slow rise to 1200Hz Motor Siren Slow rise to 800Hz Continuous 1200Hz Motor Siren Slow rise to 2400Hz Inte...

Page 6: ...rictive but care should be taken not to exceed a capacitive limit of 83nF for installations when very long cables are used 9 Volume Control The output level of the IS mC1 Combined Sounder Beacon can b...

Page 7: ...ounder Terminal w r t Sounder Terminal from a barrier having a maximum open circuit voltage Uo that is 28V and a maximum short circuit current Io that is 93mA where Io is resistively limited If not al...

Page 8: ...uoted and for which the output is non ignition capable for the Class Division or Zone and Group of use 7 The IS mC1 Combined Unit enclosure has an ingress protection rating of IP 65 If supplied withou...

Page 9: ...ospheres disconnect power before servicing 8 Substitution of components may impair safety 9 The total capacitance connected to terminals of the sounder i e Ccable plus any other capacitance shall not...

Page 10: ...2018 EN 60079 11 2012 IEC 60079 26 2014 Regulation EU No 305 2011 Construction Products Regulation CPR IS mA1 tones 2 3 9 15 16 17 only Notified Product Certification Body for Certificate of Constanc...

Page 11: ...and Place of Issue London 23 12 2020 EU Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the ma...

Page 12: ...EU No 305 2011 Construction Products Regulation CPR IS mA1 tones 2 3 9 15 16 17 only Notified Product Certification Body for Certificate of Constancy of Performance or EC Type Examination Certificate...

Page 13: ...and Place of Issue London 04 02 2022 UKCA Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the m...

Reviews: