background image

Safe Area

Hazardous Area

-

IS-L101L
Beacon

+

0V

+

Power
Supply

Diode Return

    Barrier

Barrier

On/Off

28V  1.2W
Positive

Ac.Sw

 

 

Fig 4  Single stage alarm using two channel barrier. 

 

The  circuit  will  continue  to  work  at  lower  voltages,  but  the 

beacon brilliance will be reduced. 

 

6.2  Use with a IS-A105N intrinsically safe sounder 

 

When using the IS-L101L beacon with an IS-A105N 

sounder, the Special Conditions for Safe Use in the 

sounder certificate, Sira 04ATEX2301X must also be met. 

 

The  very  low  current  consumption  of  the  IS-L101L  beacon 

allows  it  and  a  IS-A105N  intrinsically  safe  sounder  to  be 

powered  from  a  common  Zener  barrier  as  shown  in  Fig  5. 

This reduces the sounder output by about 2dB. 

  

The  IS-L101L  beacon  contains  a  circuit  that  will  silence  the 

sounder  for  a  pre-set  time,  but  leave  the  beacon  flashing  at 

twice its normal frequency. The sounder silence time is set by 

internal DIP switches. An operator may therefore silence the 

audible  alarm  but  be  continuously  reminded  of  the  alarm 

condition by the beacon. If the alarm is not cleared within the 

silence  time,  the  sounder  will  be  reactivated.  If  the  alarm  is 

cleared during the silence time the beacon will stop flashing, 

but  the  beacon  and  the  sounder  will  both  be  re-activated  if 

the  alarm  reoccurs.  See  table  1  on  page  5  of  these 

instructions for full DIP switch settings. 

 

Note when the beacon is operated on its own, without a 

sounder connected, all of the DIP switches should be set 

to OFF the position. 

 

Safe Area

Hazardous Area

IS-A105N
Sounder

Accept
Switch

+

S+

S-

-

IS-L101L
Beacon

28V 93mA  (see sounder certificate)
Positive

0V

+

Power
Supply

Barrier

On/Off

 

 

 

Fig 5  Combined beacon and sounder with alarm accept 

switch 

 

The  silence  accept  push-button  may  be  any  mechanically 

operated switch, providing it has an IP protection suitable for 

the environmental conditions to which it is subjected, located 

within the  same  hazardous  area  as  the beacon, see section 

4.5. 

 

In  order  that  the  beacon  continues  to  produce  a  reasonable 

light output level when used in conjunction with an IS-A105N 

sounder,  the  power  supply  voltage  to  the  barrier  should  be 

maintained at a minimum of 18V. 

 

 

7. ELECTRICAL SYSTEM DESIGN FOR INSTALLATION IN 

    HAZARDOUS AREAS USING GALVANIC ISOLATORS.

 

Although  more  expensive  than  Zener  barriers,  galvanic 

isolators  are  easier  to  install  as  they  do  not  require  a  high 

integrity  earth  connection.      Any  certified  device  with  output 

safety  parameters  below  the  maximum  input  safety 

parameters  of  the  IS-L101L  beacon  may  be  used  –  See 

section 4.3. 

 

7.1  Stand alone operation  

Fig 6 shows the basic circuit that is used for all stand alone 

applications.   

  

Safe Area

Hazardous Area

+

Ac.Sw

-

IS-L101L
Beacon

+

-

On / Off

Galvanic   28V  1.2W
Isolator

+

0V

Power
Supply

 

 

Fig 6  Basic circuit for use with a galvanic isolator. 

 

The  control  arrangement  will  vary  depending  upon  the 

isolator chosen.  The galvanic isolator must be able to supply 

an  output  of  30mA  at  about  16V.    This  circuit  may  also  be 

used  if  the  beacon  is  controlled  by  a  mechanically  activated 

switch on the hazardous area side of the isolator.  

 

7.2  Use with a IS-A105N intrinsically safe sounder 

 

When using the IS-L101L beacon with a IS-A105N 

sounder, the Special Conditions for Safe Use in the 

sounder certificate, Sira 04ATEX2301X must also be met. 

 

The  very  low  current  consumption  of  the  IS-L101L  beacon 

allows  it  and  a  IS-A105N  intrinsically  safe  sounder  to  be 

powered from a common galvanic isolator as shown in Fig 7. 

This reduces the sounder output by about 2dBA.  

Safe Area

Hazardous Area

IS-A105N
Sounder

Accept
Switch

+

S+

S-

-

IS-L101L
Beacon

Galvanic   28V 93mA (see sounder certificate)
Isolator

0V

+

Power
Supply

+

-

On / Off

 

 

Fig 7  Combined beacon and sounder with alarm accept  

            switch 

 

The  IS-L101L  beacon  contains  a  circuit  that  will  silence  the 

sounder  for  a  pre-set  time,  but  leave  the  beacon  flashing  at 

twice its normal frequency. The sounder silence time is set by 

internal DIP switches. An operator may therefore silence the 

NOTE:

 If sounder silence is not required, cut the 

link across the Ac.Sw connector. 

NOTE

 If sounder silence is not required, cut the 

link across the Ac.Sw connector. 

www.acornfiresecurity.com

www.acornfiresecurity.com

Summary of Contents for IS-L101L-R/Y

Page 1: ...5 When the beacon is operated alone without a sounder connected all of the DIP switches should be set to the OFF position When used alone i e without a sounder connected two flash frequencies may be s...

Page 2: ...ertain extreme conditions The user should ensure that the equipment is not installed in a location where it may be subjected to external conditions that might cause a build up of electrostatic charges...

Page 3: ...fixing holes The lens should be aimed towards the area where maximum visibility is required 5 2 Installation procedure a Remove the beacon lens by unscrewing the two captive screws and pull the lens a...

Page 4: ...nable light output level when used in conjunction with an IS A105N sounder the power supply voltage to the barrier should be maintained at a minimum of 18V 7 ELECTRICAL SYSTEM DESIGN FOR INSTALLATION...

Page 5: ...L101L beacon Suspect beacons must be returned to European Safety Systems Ltd or to your local agent for repair 11 GUARANTEE Beacons which fail within the guarantee period should be returned to Europea...

Page 6: ...ondon W3 7QH UK www e2s com WARNING TO AVOID A POSSIBLE ELECTROSTATIC CHARGE ONLY CLEAN WITH A DAMP CLOTH IS L101L Beacon II 1G 2813 SIRA 04ATEX2302X Year Serial No 09 1000001 IECEx SIR 04 0039X Ui 28...

Page 7: ...e quoted and for which the output is non ignition capable for the Class Division or Zone and Group of use 7 The IS L101L Beacon enclosure has an ingress protection rating of IP 66 If supplied without...

Page 8: ...n capable for the Class Division or Zone and Group of use 6 The IS L101L Beacon enclosure has an ingress protection rating of IP 66 If supplied without cable entry devices then metallic or plastic cab...

Page 9: ...ng the shunt zener diode barrier to the beacon capacitance of the cable connecting the sounder to the beacon 11 The total capacitance connected to terminals of the beacon plus the total capacitance co...

Page 10: ...rminals of the beacon plus the total capacitance connected to terminals of the sounder i e C cable plus any other capacitance shall not exceed 83nF 11 L cable loop inductance of cable connecting the g...

Reviews: