Document No. D187-00-001-IS      Issue 3                 13-01-20                      

Sheet 3 of 5

 

4)  Installation 

 
 
 
 
 
 
 
 
 
 

 
 
Fig 3  Fixing hole locations

 

 

IS-D105  sounders  should  only  be  installed  by  trained 

competent personnel. 

 

4.1 Mounting 

 

The  IS-D105  sounder  may  be  secured  to  any  flat  surface 

using  the  two  M6,  147.0mm  pitch  fixing  centres.  The 

enclosure  provides  IP66  protection  and  is  suitable  for 

installation  in  exterior  locations  providing  it  is  positioned  so 

that  water  cannot  collect  in  the  horn,  and  the  cable  entry  is 

sealed. 

 

4.2  Installation procedure 

 

a.  Secure  the  IS-D105  sounder  to  a  flat  surface  via  the 

two M6, 147.0mm pitch fixing centres in the mounting 

feet. 

 

b.  Remove  the  front  of  the  sounder  by  unscrewing  the 

four  captive  screws  and  pulling  the  front  away  from 

the enclosure.  

 

c.  Remove  the  PVC  grommet  and  fit  a  20mm  cable 

gland  or  conduit  entry  into  the  hole  in  the  enclosure 

and connect the field wiring to the appropriate sounder 

terminals  as  shown  in  section  6  and  fig  2  of  this 

manual.  The  power  supply  terminals  +  and  -  are 

duplicated  so  that  sounders  may  be  connected  in 

parallel,  or  an  end  of  line  monitoring  resistor  may  be 

fitted. 

 

d.  Select  the  required  output  tone  by  positioning  the  6-

way DIP switch as shown in Table 1.0 and Fig 2.  

 

e.  Apply  power  to  the  sounder  and  adjust  the  internal 

volume control to provide the required sound level. 

 

f.  Replace  the  front  of  the  sounder  and tighten the  four 

captive cover screws. 

 

 

5)  Electrical  System  Design  For  Installation  In 

Hazardous Areas Using Zener Barriers 

 

5.1  Single stage alarm  

 

If  the  control  switch  is  in  the  positive  supply,  or  the  power 

supply is being turned on and off, only a single channel Zener 

barrier is required as shown in Fig 3. This circuit may also be 

used  if  the  sounder  is  being  controlled  by  a  mechanically 

activated switch on the hazardous area side of the barrier.  

 

 

 

 

 

 

 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

Fig 4  Single stage alarm using single channel barrier. 

 

If the control switch must be in the negative supply, the circuit 

shown in Fig 4 may be used. Any diode return barrier certified 

Ex  ia  by  a  EC  Notified  Body  may  be  used,  providing  its 

voltage drop is less than 0.9V.  

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig 5  Single stage alarm using two channel barrier. 

 

5.2  Multi-stage alarm 

 

Connecting  terminal  S2  to  0V  activates  the  second  stage 

alarm, and similarly terminal S3 for the third stage alarm. Fig 

5  shows  how  the  diode  return  barriers  may  be  used.  If  only 

two  stages  of  alarm  are  required  the  third  stage  barrier 

should be omitted, the 28V 93mA barrier and the single diode 

return channel may then be contained in one package. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig 6  Multi stage alarm using Zener barriers. 

 

 

 

 

 
 

Barrier 

Power 
Supply 

28V 93mA 
Positive 

Safe Area 

Hazardous Area 

IS-D105 Sounder 
Terminals

On/Off*

0V

To a 
maximum 
of 2 other 
sounders

Barrier 

Power 
Supply 

28V 93mA 
Positive 

Safe Area 

Hazardous Area 

IS-D105 Sounder 
Terminals 

On/Off*

0V

Barrier 

Power 
Supply 

28V 93mA 
Positive 

Safe Area 

Hazardous Area 

IS-D105 Sounder 
Terminals 

On/Off*

Diode Return 
Barrier 

Diode Return 
Barrier 

Diode Return 
Barrier 

3

rd

 Stage* 

2

nd

 Stage* 

0V

To a 
maximum 
of 2 other 
sounders 

To a 
maximum 
of 2 other 
sounders 

Detail of Fixing 
Points 