European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH

 

www.e2s.com

 

Tel: +44 (0)208 743 8880

 

Document No. D157-00-001-IS

 

Issue 7

 

02-11-21

 

 

Sheet 2 of 7

 

 

2)  Warnings

   

 

 

 

  DO NOT OPEN WHEN ENERGISED. 

  DO NOT OPEN WHEN AN EXPLOSIVE

 

ATMOSPHERE IS 

PRESENT. 

  POTENTIAL ELECTROSTATIC CHARGING HAZARD. 

  ALL ENTRIES M20 X 1.5MM. 

  IF TEMPERATURE EXCEEDS 70°C AT ENTRY OR 80°C 

AT BRANCHING POINT USE SUITABLE RATED CABLE 
AND CABLE GLANDS. 

  IF  OPENING  THE  UNIT  DURING  MAINTENANCE 

OPERATIONS  A  CLEAN  ENVIRONMENT  MUST  BE 
MAINTAINED AND ANY DUST LAYER REMOVED PRIOR 
TO OPENING THE UNIT. 

 

3)  Marking & Rating Information 

 
All  units  have  a  rating  label,  which  carries  the  following 
important information. 
 
Products  may  have  further  approvals,  see  E2S  website  for 
further details. 
 

ATEX / IECEx Ratings 

 

Standards 

EN60079-0:2018   EN IEC60079-0:2018 

General Requirements 

EN60079-1:2014 A/C:2018   EN 60079-1:2014 ed. 7 

Flameproof Enclosure ‘d’

 

Model No: 

Rating 

GNExS1DC024 
GNExS1DC048 
GNExS1AC230 

 

Ex db IIC T4 Gb for Ta 

60°C to +50°C 

Ex db IIC T3 Gb for Ta 

60°C to +70°C 

Ex db IIB T6 Gb for Ta 

60°C to +50°C 

Ex db IIB T5 Gb for Ta 

60°C to +65°C 

Ex db IIB T4 Gb for Ta 

60°C to +70°C 

 

Certificate No.    

SIRA  13ATEX1139X

  

IECEx SIR 13.0029X 

        

Epsilon x 
Equipment Group 
and Category: 

 

II 2G 

CE Marking and 
Notified Body No. 

 

2813 

 

4)  Zones, Gas Group, Category and 

Temperature Classification 

 
The  units  can  be  installed  in  locations  with  the  following 
conditions: 
 

Area Classification 

Zone 1 

Explosive gas air mixture likely to occur in 
normal operation. 

Zone 2 

Explosive gas air mixture not likely to occur in 
normal operation, and if it does, it will only exist 
for a short time. 

Gas Groupings 

Group IIA 

Propane 

Group IIB 

Ethylene 

Group IIC 

Hydrogen and Acetylene 

Temperature Classification for Gas Applications 

T1 

450

o

 C  

T2 

300

o

 C 

T3 

200

o

 C 

T4 

135

o

 C 

T5 

100ºC 

T6 

85ºC 

Equipment Category 

2G 

Ambient Temperature Range 

GNExS1 

-60°C to +70°C 

IP Rating 

IP6X to EN/IEC60079-0 
IP66 to EN60529 

 

5)  Special Conditions for Safe Use 

 
Repair of the Flame Path is not permitted. 
 

 

Figure 1: Flame Path.

 

 
The  enclosure  is  non-conducting  and  under  certain  extreme 
conditions  may  generate  an  ignition  capable  level  of 
electrostatic charge. The user shall ensure that the equipment 
is  not  installed  in  a  location  where  it  may  be  subjected  to 
extreme conditions (such as high-pressure steam) which might 
cause  a  build-up  of  electrostatic  charge  on  non-conducting 
surfaces. 
 

6)  Product Mounting and Access 

 

6.1. Location and Mounting

 

 

The sounder should be secured to any flat surface using the 
three 7mm fixing holes (see figure 2). The angle can then be 
adjusted  as  required  but  the  mounting  restrictions  must  be 
observed  (see  outline  drawings  for  details,  D157-05-001  for 
GNExS1F  and  D157-05-051  for  GNExS1R).  This  can  be 
achieved by loosening the two large bracket screws in the side 
of the unit, which allow adjustments in steps of 18°. 
 

Summary of Contents for GNExS1F Series

Page 1: ...50 60Hz 73mA 80mA 110 105 230Vac 48mA GNExS1FDC024 12Vdc 10 30Vdc 221mA 221mA 115 110 24Vdc 185mA GNExS1FDC048 48Vdc 38 60Vdc 115mA 221mA 115 110 GNExS1FAC230 115Vac 100 260Vac 50 60Hz 73mA 80mA 115...

Page 2: ...lassification The units can be installed in locations with the following conditions Area Classification Zone 1 Explosive gas air mixture likely to occur in normal operation Zone 2 Explosive gas air mi...

Page 3: ...ble between the cover and base of the sounder enclosure Tighten the M3 grub screw 7 Installation Requirements 7 1 Installation Standards Compliance Warning High voltage may be present risk of electric...

Page 4: ...ed in the table below Max Ambient Temperature C Model 40 45 50 55 60 65 70 GNExS1 70 75 80 85 90 95 Table 2 Min Ratings of Cables Cable Glands Cable Glands Appropriate cable glands to be customer supp...

Page 5: ...t tones that can be selected independently for the first and second stage alarms The tones are selected by operation of the tone setting DIP switch 1 DIP 2witch 2 see figures 6 and 7 on the PCB for st...

Page 6: ...06 005 for AC schematic diagrams 7a AC Single Stage Configuration Default 7b AC Three Four Stage Configuration Default 8 AC Two Stage Voltage Free Activation Configuration Custom K Table 3 Summary of...

Page 7: ...ant standards EN60079 19 IEC60079 19 Explosive atmospheres Equipment repair overhaul and reclamation EN 60079 17 IEC60079 17 Explosive atmospheres Electrical installations inspection and maintenance F...

Page 8: ...NE MONITORING RESISTOR CUSTOMER SUPPLIED 14V MAX SYSTEM 120 MIN 2W MIN OR 1K MIN 0 5W MIN 28V MAX SYSTEM 470 MIN 2W MIN OR 2 4K MIN 0 5W MIN RECOMMENDED MINIMUM VALUES R1 Stage 1 ve IN Stage 1 ve OUT...

Page 9: ...ve OUT Stage 1 ve OUT Stage 3 ve Stage 1 ve IN H2 H1 Stage 1 ve Stage 1 ve Stage 2 ve Stage 2 ve OF 2 3 R1 S2 S3 R1 S2 R2 OPTIONAL LINE MONITORING RESISTOR CUSTOMER SUPPLIED 14V MAX SYSTEM 120 MIN 2W...

Page 10: ...ge 2 ve Stage 2 ve Two Three Stage Voltage Free Activation Configuration Config 5 Customer Set H1 H2 to Negative Switching See Below Power ve ve Stage 1 Connect Stage 1 ve to Common ve Stage 2 Cconnec...

Page 11: ...RAIT B ISARD R N POTTS OF NTS 1 SWITCHES FOR STAGE OPERATION CUSTOMER SUPPLIED 1 Earth Earth Stage 2 Stage 3 Common Live IN Live OUT Neutral IN Neutral OUT Earth Stage 1 Stage 2 Common N N L L E N N...

Page 12: ...0 0 0 1 0 1 0 0 0 0 1 1 0 0 0 1 1 1 0 0 0 0 0 0 1 0 0 1 0 0 1 0 0 0 1 0 1 0 0 1 1 0 1 0 0 0 0 1 1 0 0 1 0 1 1 0 0 0 1 1 1 0 0 1 1 1 1 0 0 0 0 0 0 1 0 1 0 0 0 1 0 0 1 0 0 1 0 1 1 0 0 1 0 0 0 1 0 1 0 1...

Page 13: ...y No 2813 CSA Group Netherlands B V Utrechtseweg 310 6812 AR Arnhem Netherlands Quality Assurance Notification Module D SIRA 05 ATEX M342 Provisions fulfilled by the equipment II 2G Ex db IIB or IIC T...

Page 14: ...te and Place of Issue London 23 12 2020 EU Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the...

Reviews: