E2S GNExB2X05-S Series Instruction Manual Download Page 12

 

European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH

 

www.e2s.com

 

Tel: +44 (0)208 743 8880

 

Document No. D156-00-621-IS

 

Issue 1

 

27-10-22

 

 

Sheet 12 of 15

 

 

 

Figure 14: Schematic of SIL 2 system wiring for fault detection in standby mode only 

 2 wire installation. 

 
To evaluate the total current drawn from the SIL 2 unit, use the equation below. 
 

 

 

 

 

 
In standby mode, where there is no fault, RLY 1-1 is open. This means the voltage only passes through the customer EOL resistor 
and the current drawn from the SIL 2 board is 25mA. Therefore, the equation for a No Fault scenario is then: 
 

 

 

 

 
In standby mode, where there is a fault, the circuit is closed. This means the voltage passes through both the customer EOL resistor 
and current sense resistor and the current drawn from the SIL 2 board is 20mA. The customer must first calculate the resistance of 
the two resistors in parallel before applying the currents to the equation. The equation for a Fault scenario is then: 
 
 

 

 
 

Table 5:  Resistor combinations and the currents drawn when no faults and faults occur. 

 
If multiple SIL 2 alarm horn sounders are to be cabled in series, the monitoring connections differ from that of a single beacon. For 
more information see manual D197-00-621-IS available from the E2S website. 
 
 
 
 
 
 
 
 
 

(Total Current 

drawn) 

 

 

(Current drawn from 

Fault Resistor) 

 

(Current drawn from 

Customer EOL resistor) 

 

(Current drawn 

from SIL board) 

 

(Standby Mode, Total Current drawn - No Fault) 

 

(0mA) 

 

(See table 5) 

 

(25mA) 

 

(Standby Mode, Total Current drawn - Fault) 

 

(Total Resistance when EOL & FR in parallel) 

 

(20mA) 

Standby 

Mode 

Power Supply Fault Resistor 

Customer EOL Resistor 

(Fault Mode Only) 

Current 

drawn 

from SIL 

Board 

Total 

current 

drawn 

Resistor 

Value 

Current 

drawn (

Resistor 

Value 

Current 

drawn (

Total 

resistance 

Current 

drawn (

No Fault 

2.2 kΩ

 

0 mA 

2.2 kΩ

 

10.9 mA 

25 mA 

35.9 mA 

Fault 

1.1 kΩ

 

21.8 mA 

20 mA 

41.8 mA 

No Fault 

1.

0 kΩ

 

0 mA 

1.0 kΩ

 

24.0 mA 

25 mA 

49.0 mA 

Fault 

500 Ω

 

48.0 mA 

20 mA 

68.0 mA 

No Fault 

2.2 kΩ

 

0 mA 

3.3 kΩ

 

7.3 mA 

25 mA 

32.3 mA 

Fault 

1.3 kΩ

 

18.2 mA 

20 mA 

38.2 mA 

No Fault 

1.8 kΩ

 

0 mA 

3.9 kΩ

 

6.2 mA 

 

 

25 mA 

31.2 mA 

Fault 

1.2 kΩ

 

19.5 mA 

20 mA 

39.5 mA 

No Fault 

1.8 

kΩ

 

0 mA 

4.7 kΩ

 

5.1 mA 

25 mA 

30.1 mA 

Fault 

1.3 kΩ

 

18.4 mA 

20 mA 

38.4 mA 

No Fault 

2.2 kΩ

 

0 mA 

4.7 kΩ

 

5.1 mA 

25 mA 

30.1 mA 

Fault 

1.5 kΩ

 

16.0 mA 

20 mA 

36.0 mA 

Summary of Contents for GNExB2X05-S Series

Page 1: ...AND CABLE GLANDS IF TEMPERATURE EXCEEDS AS PER STANDARDS INDICATIONS BELOW FOR ATEX IECEx UKEX STANDARDS 70 C AT ENTRY OR 80 C AT BRANCHING POINT FOR NEC CEC STANDARDS 60 C AT ENTRY OR 60 C AT BRANCHI...

Page 2: ...in compliance with the National Electric Code CEC Class Zone Ratings Canada Standards CAN CSA C22 2 No 60079 0 Ed 4 02 2019 Explosive Atmospheres Part 0 Equipment General Requirements CAN CSA C22 2 N...

Page 3: ...mented joints is not permitted Figure 1 Flame Path The enclosure is non conducting and may generate an ignition capable level of electrostatic charges under certain extreme conditions The user should...

Page 4: ...Explosive dust atmospheres The installation of the units must also be in accordance with any local codes that may apply and should only be carried out by a competent electrical engineer who has the ne...

Page 5: ...C or the cable branching point temperature may exceed 60 C and therefore suitable heat resisting cables and cable glands must be used with a rated service temperature at least as stated below Table 3...

Page 6: ...P Switch Location Switch Setting S1 Mode SIL Approved 00 1Hz 60FPM Yes 01 1 33Hz 80FPM No 10 1 5Hz 90FPM No 11 Double Flash No Table 4 Switch Positions for Flash Patterns 9 End of Line Monitoring DC U...

Page 7: ...l and Repair Maintenance repair and overhaul of the equipment should only be carried out by suitably qualified personnel in accordance with the current relevant standards EN60079 19 IEC60079 19 Explos...

Page 8: ...and Function The SIL 2 Beacon Unit Monitors Standby mode and Active mode Health status of power supply Beacons correct function and flash pattern The SIL 2 beacon operates as part of a SIL 2 system Th...

Page 9: ...correct the latched fault the alarm horn sounder may require further investigation please contact your local E2S representative Commissioning System Functional start up of System Normally in reverse...

Page 10: ...hough it is highly recommended that the unit is wired as stated in section 15 1 as a 4 Wire System J1 Header Current Sense Resistor CSR Shown in factory default position A see section 15 3 places TB1...

Page 11: ...om the circuit Note a cable short circuit will not be detectable in this configuration For one unit only Beacon power supply terminal block Current drawn mA Active Mode 190mA Standby Mode 25mA SIL2 TB...

Page 12: ...hen no faults and faults occur If multiple SIL 2 alarm horn sounders are to be cabled in series the monitoring connections differ from that of a single beacon For more information see manual D197 00 6...

Page 13: ...Position B pins 2 3 linked Places power supply terminal Fault Resistor RLY 1 2 in circuit As used in 2 Wire Configuration Figure 16 J2 Header pin positions Fault Resistor FR 15 4 SIL 2 Hard Reset Func...

Page 14: ...Random Hardware Failures and Architectural constraints route 1H 2 As an unvoted item i e hardware fault tolerance of 0 at SIL 2 The product was assessed against failure modes Failure respond to an in...

Page 15: ...be specified when ordering The values of resistors available are shown in table 6 below Code Resistor Value Default resistor coding is as follows GNExB2X05DC024AS1S1R A AFZ Example of a custom require...

Page 16: ...ATERIAL SHEET SCALE TITLE A3 IF IN DOUBT ASK DO NOT SCALE ALL DIMENSIONS IN MM DRAWING NUMBER A B C D E F G 10 9 G F E 7 8 6 5 D C 1 3 4 2 A B D191 06 621 M ABALOS B ISARD R N POTTS OF NTS 1 1 23 09 2...

Page 17: ...B V Utrechtseweg 310 6812 AR Arnhem Netherlands Quality Assurance Notification Module D SIRA 05 ATEX M342 Provisions fulfilled by the equipment II 2G Ex db IIC T4 T6 Gb II 2D Ex tb IIIC T80 C T138 C D...

Page 18: ...Date and Place of Issue London 03 12 2021 EU Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on t...

Page 19: ...e Lane Eccleston Chester CH4 9JN UK Quality Assurance Notification Module D CSAE 22UKQAN0046 Provisions fulfilled by the equipment II 2G Ex db IIC T4 T6 Gb II 2D Ex tb IIIC T80 C T138 C Db IP6X Dust P...

Page 20: ...r Date and Place of Issue London 24 02 2022 UKCA Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed o...

Reviews: