background image

 

European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH

 

www.e2s.com

 

Tel: +44 (0)208 743 8880

 

Document No. D209-00-011-IS

 

Issue 1

 

20-08-22

 

 

Sheet 2 of 5

 

  

Certificate No. 

DEMKO 06ATEX 0421554X 
IECEx ULD 14.0012X 
UL21UKEX2135X 
 

ATEX Mark, Equipment 
Group and Category: 

 

II 3G 
II 3D

 

CE Marking 
 

 

 

UKCA Marking 

 

 

 

3.2. NEC & CEC Ratings 

 

NEC & CEC Class / Division Ratings for US / 
Canada 

 

Standards 

UL 121201-2021 (Ed. 9) 
CAN/CSA C22.2 No. 213-17 (Ed. 3) 

Ratings 

E2Xs2: 

Class I, Div 2,  

ABCD   T3C Ta -20°C to +55°C 

Class I, Div 2,  

ABCD   T4 Ta -20°C to +40°C 

Class II, Div 2,   FG  

T6 Ta -20°C to +55°C 

Class III, Div 1 & 2              Ta -20°C to +55°C 

Installation must be carried out in compliance with the National 
Electric Code / Canadian Electric Code 

 

NEC Class / Zone ratings US 
 

Standards 

UL 60079-0 (Ed. 7): 

Explosive Atmospheres - part 0: Equipment - General 
Requirements  

UL 60079-7 (Ed. 5): 

Explosive Atmospheres - Equipment Protection by Increased 

Safety "e" 

UL 60079-31 (Ed. 2) 

Explosive Atmospheres - Equipment Dust Ignition Protection 

by Enclosure "t" 

Ratings 

E2xS2: 

Class I Zone 2 AEx ec IIC T4 Gc Ta -20°C to +55°C 
Zone 22 AEx tc IIIC T85°C Dc Ta -20°C to +55°C 

Installation must be carried out in compliance with the National 
Electric Code. 

 

 
 
 
 
 
 
 
 
 
 

CEC Class / Zone ratings Canada 

 

Standards 

CAN/CSA C22.2 No. 60079-0 (Ed. 4) 02/2019 

Explosive Atmospheres - Part 0: Equipment - General 
Requirements  

CAN/CSA C22.2 No. 60079-7 (Ed. 2) 

Explosive Atmospheres - Equipment Protection by Increased 

Safety "e" 

CAN/CSA C22.2 No. 60079-31 (Ed. 2) 

Explosive Atmospheres - Equipment Dust Ignition Protection 

by Enclosure "t" 

Rating 

E2xS2:

 

Ex ec IIC T4 Gc Ta -20°C to +55°C 
Ex tc IIIC T85°C Dc Ta -20°C to +55°C 

Installation must be carried out in compliance with the Canadian 
Electric Code 

 

4)  Zones, Gas Group, Category and 

Temperature Classification 

 

When connected to an approved system the E2XS2 alarm 
horn may be installed in: 
 

Area Classification 

Zone 2 

Explosive gas air mixture not likely to occur in 
normal operation, and if it does, it will only 
exist for a short time. 

Zone 22 

Explosive dust air mixture not likely to occur in 
normal operation, and if it does, it will only 
exist for a short time. 

Gas Groupings 

Group IIA 

Propane 

Group IIB 

Ethylene 

Group IIC 

Hydrogen and Acetylene 

Temperature Classification for Gas Applications 

T1 

450ºC  

T2 

300ºC 

T3 

200ºC 

T4 

135°C 

Dust Groupings 

(ATEX / IECEx / UKEX only) 

Group IIIA 

Combustible Flyings 

Group IIIB 

Non-conductive Dust 

Group IIIC 

Conductive Dust 

Maximum Surface Temperature for Dust Applications 

(ATEX / IECEx / UKEX only) 

E2xS2: 

85°C 

Equipment Category 

3G / 3D  

Equipment Level Protection 

Gc, Dc 
 

Summary of Contents for E2xS2FDC024

Page 1: ...ON HUMIDE HAUT TENSION RISK DE CHOC ATTENDEZ 5 MINUTES APRES AVOIR DEBRANCHE L ALIMENTATION AVANT D OUVRIR LA BOITIER 3 Rating Marking Information 3 1 ATEX IECEx UKEx certification The E2xS2 alarm hor...

Page 2: ...l Electric Code CEC Class Zone ratings Canada Standards CAN CSA C22 2 No 60079 0 Ed 4 02 2019 Explosive Atmospheres Part 0 Equipment General Requirements CAN CSA C22 2 No 60079 7 Ed 2 Explosive Atmosp...

Page 3: ...ction the cable entries must be fitted with suitably rated certified cable entry and or blanking devices during installation Equipment with the flare horn shall not be installed with the flare higher...

Page 4: ...ons are to be made into the terminal blocks on the PCBA located in the enclosure See section 6 of this manual for access to the enclosure Wires having a cross sectional area between 0 5 mm to 2 5mm ca...

Page 5: ...1 0 0 1 544Hz 100mS 440Hz 400mS NF S 32 001 40 Tone 17 Tone 23 0 1 1 0 0 1 800Hz 0 25 sec on 1 sec off Intermittent 39 Tone 45 Tone 34 1 0 1 0 0 1 2000Hz Continuous 38 Tone 45 Tone 9 0 0 1 0 0 1 1000...

Page 6: ...IN MM DRAWING NUMBER A B C D E F G 10 9 G F E 7 8 6 5 D C 1 3 4 2 A B D209 06 001 R S RAIT R N POTTS R N POTTS 05 08 2020 OF E2xS1R E2xS1F E2xS2F SOUNDER WIRING DIAGRAMS INTRODUCTION RSR 05 08 2020 NT...

Page 7: ...Assurance Notification Module D SIRA 05 ATEX M342 Provisions fulfilled by the equipment II 3G Ex ec IIC T4 T3 T2 Gc II 3D Ex tc IIIC 85 C 120 C Dc IP6X Dust Protection to EN60079 0 EN60079 31 Standar...

Page 8: ...e and Place of Issue London 22 08 2022 EU Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the m...

Page 9: ...on Module D CSAE 22UKQAN0046 Provisions fulfilled by the equipment II 3G Ex ec IIC T4 T3 T2 Gc II 3D Ex tc IIIC 85 C 120 C Dc IP6X Dust Protection to EN60079 0 EN60079 31 Standards applied EN IEC 6007...

Page 10: ...Place of Issue London 22 08 2022 UKCA Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the marke...

Reviews: