E2S E2xBL2 Instruction Manual Download Page 5

 

European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH

 

www.e2s.com

 

Tel: +44 (0)208 743 8880

 

Document No. D209-00-401-IS

 

Issue 1

 

20-08-22

 

 

Sheet 5 of 5

 

 

 

 

Fig. 8b End of Line Resistor Placement 

 

11) Settings 

 

11.1  Flash Rate Setting 

 

 

The E2xBL2 beacons can produce different flash patterns as 
shown  in  Table  1.  The  flash  patterns  are  selected  by 
operation of the flash setting DIP switch on the PCB, Fig 6.   
  

 

 

Fig. 9: DIP Switch Location 

 
Table 1: Switch Positions for Flash Patterns 
 

 

 
 
 

 
 

Fig. 10 Dip Switch 

 

1=ON; 0=OFF 
Example shown: 100000 = Flashing 1Hz (Default setting)

 

 

12) Interchangeable & Spare Parts 

 

 

 

The  Beacon  lens  cover  is  interchangeable,  contact  E2S  Ltd 
for a replacement lens cover available in various colours. 
 
To change the lens cover, unscrew the 4-off M5 Cap screws, 
spring and flat washers using a 4mm Allen Key. Remove the 
wire guard and replace the old cover with the new cover. 
 

 

 

Fig. 11 Replacement of beacon lens cover 

 

Fit  the  wire  guard back onto  the  housing,  over  the  new  lens 
cover  aligning  the  fixing  holes  of  the  guard,  lens  cover  and 
housing. Refit the fixings to hold into place, the fixings MUST 
be fitted in the order shown above. 

 

13) Maintenance, Overhaul & Repair 

 

Maintenance,  repair  and  overhaul  of  the  equipment  should 
only  be  carried  out  by  suitably  qualified  personnel  in 
accordance with the current relevant standards: 

 

EN60079-19 
IEC60079-19 

Explosive atmospheres - Equipment repair, 
overhaul and reclamation 

 

EN 60079-17 
IEC60079-17 

Explosive atmospheres - Electrical 
installations inspection and maintenance 

 

To  avoid  a  possible  ELECTROSTACTIC  CHARGE  the  unit 
must only be cleaned with a damp cloth. 

 

Units must  not  be  opened  while an  explosive  atmosphere  is 
present. 
If  opening  the  unit  during  maintenance  operations  a  clean 
environment must be maintained and any dust layer removed 
prior to opening the unit. 

Switch 

Setting 

S1 Mode 

S2 Mode 

S3 Mode 

(123456) 

(DC & AC) 

(DC Only) 

(DC Only) 

000000

 

Steady High 

Power

 

Flashing 1Hz

 

Flashing Triple 

Strike

 

000001

 

Steady Low 

Power

 

Flashing 1Hz

 

Flashing Triple 

Strike

 

100000

 

Flashing 1Hz

 

Flashing 

Double Strike

 

Flashing Triple 

Strike

 

101000

 

Flashing 

1.5Hz 

Flashing 2Hz

 

Flashing 

Double Strike

 

010000

 

Flashing 2Hz

 

Flashing Triple 

Strike

 

Flashing Triple 

Strike

 

110000

 

Flashing 

Double Strike

 

Steady High 

Power

 

Flashing Triple 

Strike

 

001000

 

Flashing 

Triple Strike

 

Flashing 2Hz

 

Flashing 

Double Strike

 

Warning – high-intensity light source. Avoid 
looking directly at the light source for 
extended periods of time. 

Warning –

 

Hot surfaces. External surfaces 

and internal components may be hot after 
operation, take care when handling the 
equipment. 

End of Line Resistor 

M5 screw 
M5 spring washer 
M5 flat washer 

Summary of Contents for E2xBL2

Page 1: ...5 MINUTES APRES AVOIR DEBRANCHE L ALIMENTATION AVANT D OUVRIR LA BOITIER 3 Rating Marking Information 3 1 ATEX IECEx UKEx certification The E2xBL2 LED beacon complies with the following standards Stan...

Page 2: ...to 55 C Installation must be carried out in compliance with the Canadian Electric Code 4 Zones Gas Groups Category and Temperature Classification When connected to an approved system the E2XBL2 LED be...

Page 3: ...wo large bracket screws in the side of the unit which allow adjustment of the beacon in steps of 18 On completion of the installation the two large bracket adjustment screws on the side of the unit mu...

Page 4: ...when the cover is inserted into the chamber the wires do not exert excess pressure on the terminal blocks This is particularly important when using cables with large cross sectional areas such as 2 5...

Page 5: ...nt should only be carried out by suitably qualified personnel in accordance with the current relevant standards EN60079 19 IEC60079 19 Explosive atmospheres Equipment repair overhaul and reclamation E...

Page 6: ...IGHT Kg SURFACE FINISH MATERIAL ALTERNATIVE MATERIAL SHEET SCALE TITLE A3 IF IN DOUBT ASK DO NOT SCALE ALL DIMENSIONS IN MM DRAWING NUMBER A B C D E F G 10 9 G F E 7 8 6 5 D C 1 3 4 2 A B D209 06 401...

Page 7: ...Assurance Notification Module D SIRA 05 ATEX M342 Provisions fulfilled by the equipment II 3G Ex ec IIC T4 T3 T2 Gc II 3D Ex tc IIIC 85 C 120 C Dc IP6X Dust Protection to EN60079 0 EN60079 31 Standar...

Page 8: ...e and Place of Issue London 22 08 2022 EU Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the m...

Page 9: ...on Module D CSAE 22UKQAN0046 Provisions fulfilled by the equipment II 3G Ex ec IIC T4 T3 T2 Gc II 3D Ex tc IIIC 85 C 120 C Dc IP6X Dust Protection to EN60079 0 EN60079 31 Standards applied EN IEC 6007...

Page 10: ...Place of Issue London 22 08 2022 UKCA Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the marke...