E2S E2xBL2 Instruction Manual Download Page 2

 

European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH

 

www.e2s.com

 

Tel: +44 (0)208 743 8880

 

Document No. D209-00-401-IS

 

Issue 1

 

20-08-22

 

 

Sheet 2 of 5

 

 

3.2. NEC & CEC Ratings 
 

NEC & CEC Class / Division Ratings for US / Canada 
 

Standards 

UL 121201-2021 (Ed. 9) 
CAN/CSA C22.2 No. 213-17 (Ed. 3) 

Ratings 

E2XBL2: 
 

Class I, Div 2, ABCD T4A Ta -20°C to +55°C 
Class II, Div 2, FG T6 Ta -20°C to +55°C 
Class III, Div 1&2 Ta -20°C to +55°C 

Installation must be carried out in compliance with the National 
Electric Code / Canadian Electric Code 

 
NEC Class / Zone ratings US 
 

Standards 

UL 60079-0 (Ed. 7): 

Explosive Atmospheres - part 0: Equipment - General 
Requirements  

UL 60079-7 (Ed. 5): 

Explosive Atmospheres - Equipment Protection by Increased 

Safety "e" 

UL 60079-31 (Ed. 2) 

Explosive Atmospheres - Equipment Dust Ignition Protection by 

Enclosure "t"

 

Ratings 

E2XBL2: 
 

Class I Zone 2 AEx ec IIC Gc T4 Ta -20°C to +55°C 
AEx tb IIIC Dc T85°C Ta -20°C to +55°C 

Installation must be carried out in compliance with the National 
Electric Code. 

 
CEC Class / Zone ratings Canada 
 

Standards 

CAN/CSA C22.2 No. 60079-0 (Ed. 4) 02/2019 

Explosive Atmospheres - Part 0: Equipment - General 
Requirements  

CAN/CSA C22.2 No. 60079-7 (Ed. 2) 

Explosive Atmospheres - Equipment Protection by Increased 

Safety "e" 

CAN/CSA C22.2 No. 60079-31 (Ed. 2) 

Explosive Atmospheres - Equipment Dust Ignition Protection by 

Enclosure "t"

 

Rating 

E2XBL2: 

 

Ex ec IIC Gc T4 Ta -20°C to +55°C 
Ex ec IIC Gc T4A Ta -20°C to +40°C 
Ex tb IIIC Dc T85°C Ta -20°C to +55°C 

Installation must be carried out in compliance with the Canadian 
Electric Code 

 

4)  Zones, Gas Groups, Category and 

Temperature Classification 

 

When connected to an approved system the E2XBL2 LED 
beacon may be installed in: 
 
 
 
 

Area Classification 

Zone 2 

Explosive gas air mixture not likely to occur in 
normal operation, and if it does, it will only 
exist for a short time. 

Zone 22 

Explosive dust air mixture not likely to occur in 
normal operation, and if it does, it will only 
exist for a short time. 

Gas Groupings 

Group IIA 

Propane 

Group IIB 

Ethylene 

Group IIC 

Hydrogen and Acetylene 

Temperature Classification for Gas Applications 

T1 

450ºC  

T2 

300ºC 

T3 

200ºC 

T4 

135°C 

Dust Groupings 

(ATEX / IECEx / UKEX only) 

Group IIIA 

Combustible Flyings 

Group IIIB 

Non-conductive Dust 

Group IIIC 

Conductive Dust 

Maximum Surface Temperature for Dust Applications 

(ATEX / IECEx / UKEX only) 

E2XBL2: 

85°C 

Equipment Category 

3G / 3D  

Equipment Level Protection 

Gc, Dc 

Ambient Temperature Range 

-20°C to +55°C 

IP Rating 

IP6X to EN/IEC60079-0 

IP66 to EN60529 
To maintain the ingress protection rating, the two off cable entries 
must be fitted with suitably rated, certified cable entry and/or 
blanking devices during installation. 

Type Rating 

Per UL50E / NEMA250: 4 / 4X / 3R / 13

 

 

Installation must be carried out in compliance with the 
latest issue of the following standards: 

 
EN60079-14 / IEC60079-14: Explosive atmospheres - 
Electrical installations design, selection and erection 
EN60079-10-1 / IEC60079-10-1: Explosive atmospheres - 
Classification of areas. Explosive gas atmospheres 
EN60079-10-2 / IEC60079-10-2: Explosive atmospheres –  
Classification of areas. Explosive dust atmospheres 

 
 
 
 
 
 
 

Summary of Contents for E2xBL2

Page 1: ...5 MINUTES APRES AVOIR DEBRANCHE L ALIMENTATION AVANT D OUVRIR LA BOITIER 3 Rating Marking Information 3 1 ATEX IECEx UKEx certification The E2xBL2 LED beacon complies with the following standards Stan...

Page 2: ...to 55 C Installation must be carried out in compliance with the Canadian Electric Code 4 Zones Gas Groups Category and Temperature Classification When connected to an approved system the E2XBL2 LED be...

Page 3: ...wo large bracket screws in the side of the unit which allow adjustment of the beacon in steps of 18 On completion of the installation the two large bracket adjustment screws on the side of the unit mu...

Page 4: ...when the cover is inserted into the chamber the wires do not exert excess pressure on the terminal blocks This is particularly important when using cables with large cross sectional areas such as 2 5...

Page 5: ...nt should only be carried out by suitably qualified personnel in accordance with the current relevant standards EN60079 19 IEC60079 19 Explosive atmospheres Equipment repair overhaul and reclamation E...

Page 6: ...IGHT Kg SURFACE FINISH MATERIAL ALTERNATIVE MATERIAL SHEET SCALE TITLE A3 IF IN DOUBT ASK DO NOT SCALE ALL DIMENSIONS IN MM DRAWING NUMBER A B C D E F G 10 9 G F E 7 8 6 5 D C 1 3 4 2 A B D209 06 401...

Page 7: ...Assurance Notification Module D SIRA 05 ATEX M342 Provisions fulfilled by the equipment II 3G Ex ec IIC T4 T3 T2 Gc II 3D Ex tc IIIC 85 C 120 C Dc IP6X Dust Protection to EN60079 0 EN60079 31 Standar...

Page 8: ...e and Place of Issue London 22 08 2022 EU Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the m...

Page 9: ...on Module D CSAE 22UKQAN0046 Provisions fulfilled by the equipment II 3G Ex ec IIC T4 T3 T2 Gc II 3D Ex tc IIIC 85 C 120 C Dc IP6X Dust Protection to EN60079 0 EN60079 31 Standards applied EN IEC 6007...

Page 10: ...Place of Issue London 22 08 2022 UKCA Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the marke...

Reviews: