Stage three (S3) Operation 

Power +ve and –ve, link a -

ve  supply  line  to  the  S3 

terminal.  

Dip  switch  alters  stage  3 
tone. 

Fig. 6 DC Terminals 

9.3 

Line Monitoring 

On E2xS2 DC units, DC reverse line monitoring can be used 
if  required.  All  DC  sounders  have  a  blocking  diode  fitted  in 

their supply input lines. An end of line monitoring resistor can 

be connected across the +ve and –ve terminals. If an end of 

line resistor is used it must have the following values: 

24V DC Sounders 

Minimum resistance 3K9 Ohms 

Minimum Power 0.5W 

Minimum resistance 1K Ohms 

Minimum Power 2.0W 

48V DC Sounders 

Minimum resistance 15K Ohms 

Minimum Power 0.5W 

Minimum resistance 3K9 Ohms 

Minimum Power 2.0W 

The resistor must be connected directly across the +ve and 
-ve terminals as shown in the following drawing. Whilst

keeping its leads as short as possible, a spacing of at least

1/16” (1.58mm) must be provided through air and over

surfaces between uninsulated live parts.

Fig. 8 End of Line Resistor Placement 

10) Settings

10.1

Tone Selection 

The sounders have 45 different tones that can be selected for 

the first stage alarm. The sounders can then be switched to 
sound  second  and  third  stage  alarm  tones.  The  tones  are 

selected by operation of a DIP switch on the PCB for both DC 

and  AC  units.  The  tone  table  on  page  six  shows  the  switch 

positions  for the  45  tones  and  which  tones  are  available  for 
the  second  and  third  stages.  To  operate  the  sounder  on 

stage  1  simply  connect  the  supply  voltage  to  the  normal 

supply terminals (+ve and –ve for DC units, L and N for AC 

units). 

10.2 

Volume Control 

The output level of the E2x sounder can be set by adjusting 

the volume control potentiometer (see Fig 4 for AC & Fig 6 for 
DC).  For  maximum  output,  set  the  potentiometer  fully 

clockwise. 

11) Maintenance, Overhaul & Repair

Maintenance,  repair  and  overhaul  of  the  equipment  should 

only  be  carried  out  by  suitably  qualified  personnel  in 

accordance with the current relevant standards: 

EN60079-19 

IEC60079-19 

Explosive atmospheres - Equipment repair, 

overhaul and reclamation 

EN 60079-17 
IEC60079-17 

Explosive atmospheres - Electrical 
installations inspection and maintenance 

To  avoid  a  possible  ELECTROSTACTIC  CHARGE  the  unit 

must only be cleaned with a damp cloth. 

Units must not be opened while an explosive atmosphere is 

present. 

If  opening  the  unit  during  maintenance  operations  a  clean 

environment must be maintained and any dust layer removed 

prior to opening the unit. 

Warning - High noise levels above 85dB(A) 

during  operation.  High  levels  of  noise  may 
cause  hearing  loss,  wear  suitable  ear 

protection when equipment is in operation.

 

End of Line Resistor 

48V DC 

Volume 

Control 

DIP Switch 

S3

S2

E

 

24V DC 

Volume 

Control 