background image

 Sheet 1 of 6 

INSTRUCTION MANUAL 

E2xS2R & E2xS2F Sounder

 

For use in Hazardous Locations

 

1) Warnings

DO NOT OPEN WHEN AN EXPLOSIVE
ATMOSPHERE IS PRESENT

DO NOT OPEN WHEN ENERGISED

POTENTIAL ELECTROSTATIC CHARGING

HAZARD - CLEAN ONLY WITH A DAMP
CLOTH

HIGH VOLTAGE SHOCK HAZARD. WAIT 5

MINUTES AFTER REMOVING POWER

BEFORE OPENING THE ENCLOSURE

Avertissement: 

NE PAS OUVRIR UN PRESENCE
D’ATMOSPHERE EXPLOSIVE

NE PAS OUVRIR ENERGIE

DANGER POTENTIEL CHARGE

ÉLECTROSTATIQUE - NETTOYER
UNIQUEMENT AVEC UN CHIFFON HUMIDE

HAUT TENSION, RISK DE CHOC.

ATTENDEZ 5 MINUTES APRES AVOIR

DEBRANCHE L’ALIMENTATION AVANT
D’OUVRIR LA BOITIER

2) Rating & Marking Information

2.1 ATEX / IECEx certification 

The E2xS2 alarm horn complies with the following standards: 

EN60079-0:2012+A11:2013 / IEC60079-0: ed. 6.0 (2011-06) 

EN60079-15:2010 / IEC60079-15: ed. 4.0 (2010-01) 

EN60079-31:2014 / IEC60079-31:2013 ed. 2.0 (2013-11) 

Certificate No.

    DEMKO 06ATEX 0421554X 

IECEx ULD 14.0012X 

The E2XS2 Alarm horn is rated as follows: 

CE Marking 

Zones, Gas / Dust Groups and Temperature 
Classification 

When connected to an approved system the E2XS2 alarm 

horn may be installed in: 

Zone 2  explosive gas air mixture not likely to occur 
in normal operation, and if it does, it will only exist 

for a short time. 

Zone 22 explosive dust air mixture not likely to occur 
in normal operation, and if it does, it will only exist 

for a short time. 

May be used with gases in groups: 

Group IIA 

propane 

Group IIB 

ethylene 

Group IIC 

hydrogen / acetylene 

Having a temperature classification 
(for Gas applications) of: 

T1 

450ºC 

T2 

300ºC 

T3 

200ºC 

T4 

135ºC 

May be used with Dust types: 

Group IIIA 

combustible flyings 

Group IIIB 

non-conductive dust 

Group IIIC 

conductive dust 

Maximum Surface Temperature for Dust Applications: 

85ºC 

Installation must be carried out in compliance with the latest 

issue of the following standards: 

EN60079-14 / IEC60079-14: Explosive atmospheres - 

Electrical installations design, selection and erection 

EN60079-10-1 / IEC60079-10-1: Explosive atmospheres - 
Classification of areas. Explosive gas atmospheres 

EN60079-10-2 / IEC60079-10-2: Explosive atmospheres – 

Classification of areas. Explosive dust atmospheres 

E2xS2R 

 E2xS2F 

0518 

II 3G Ex nA IIC T4 Gc Ta -20°C to +55°C 

II 3D Ex tc IIIC T85°C Dc Ta -20°C to +55°C 

Reviews: