14) Tone Table 

45

Tone 34

Tone 38

0  0  1  1  0  1

1KHz 1s on, 1s off Intermittent

PFEER Gen. Alarm

Tone 5

Tone 2

1  1  0  1  0  1

Motor Siren - slow rise to 2400Hz

44

Tone 5

Tone 2

0  1  0  1  0  1

1200Hz Continuous

43

Tone 5

Tone 2

1  0  0  1  0  1

Motor Siren - slow rise to 800Hz

42

Tone 5

Tone 2

0  0  0  1  0  1

Motor Siren - slow rise to 1200Hz

41

Tone 27

Tone 31

1  1  1  0  0  1

544Hz (100mS)/440Hz (400mS)
- NF S 32-001

40

Tone 17

Tone 23

0  1  1  0  0  1

800Hz 0.25 sec on, 1 sec off Intermittent

39

Tone 45

Tone 34

1  0  1  0  0  1

2000Hz Continuous

38

Tone 45

Tone 9

0  0  1  0  0  1

1000Hz Continuous - 

PFEER Toxic Gas

37

Tone 5

Tone 35

1  1  0  0  0  1

500-1200Hz 3.75 sec /0.25 sec 

Australian Evac.

36

Tone 5

Tone 36

0  1  0  0  0  1

420Hz @ 0.625 Sec Australian Alert

35

Tone 45

Tone 38

1  0  0  0  0  1

1000 & 2000Hz @ 0.5 sec 

Aletrnating - Signapore

34

Tone 5

Tone 2

0  0  0  0  0  1

745Hz @ 1Hz Intermittent

33

Tone 15

Tone 26

1  1  1  1  1  0

Two tone chime

32

Tone 5

Tone 26

0  1  1  1  1  0

660/1200Hz @ 1Hz Sweeping

31

Tone 5

Tone 2

1  0  1  1  1  0

300Hz Continuous

30

Tone 5

Tone 7

0  0  1  1  1  0

800/1000Hz @ 7Hz Sweeping

29

Tone 5

Tone 2

1  1  0  1  1  0

440Hz Continuous

28

Tone 5

Tone 26

0  1  0  1  1  0

554Hz Continuous

27

Tone 15

Tone 2

1  0  0  1  1  0

Bell

26

Tone 5

Tone 29

0  0  0  1  1  0

2400/2900Hz @ 50Hz Sweeping

25

Tone 5

Tone 29

1  1  1  0  1  0

800/1000Hz @ 50Hz Sweeping

24

Tone 5

Tone 6

0  1  1  0  1  0

800Hz @ 2Hz Intermittent

23

Tone 5

Tone 2

1  0  1  0  1  0

544Hz @ 0.875 sec Intermittent

22

Tone 5

Tone 2

0  0  1  0  1  0

554Hz/440Hz @ 1Hz Alternating

21

Tone 5

Tone 2

1  1  0  0  1  0

660Hz Continuous

20

Tone 5

Tone 2

0  1  0  0  1  0

1.4KHz - 1.6KHz 1s, 1.6KHz - 1.4 
KHz 0.5s - NFC48-265

19

Tone 5

Tone 2

1  0  0  0  1  0

660Hz 1.8 sec on, 1.8 sec off Intermittent

18

Tone 27

Tone 2

0  0  0  0  1  0

544Hz (100mS)/440 Hz (400m/S)
- NF S 32-001

17

Tone 5

Tone 18

1  1  1  1  0  0

660Hz 150mS on, 150mS off Intermittent

16

Tone 5

Tone 2

0  1  1  1  0  0

800Hz Continuous

15

Tone 5

Tone 4

1  0  1  1  0  0

800Hz 0.25 sec on, 1 sec off Intermittent

14

Tone 5

Tone 15

0  0  1  1  0  0

2400Hz @ 1Hz Intermittent

13

Tone 5

Tone 4

1  1  0  1  0  0

800/1000Hz @ 0.875Hz Alternating

12

Tone 5

Tone 2

0  1  0  1  0  0

1000Hz @ 1Hz Intermittent

11

Tone 5

Tone 7

1  0  0  1  0  0

2400/2900Hz @ 2Hz Alternating

10

Tone 2

Tone 15

0  0  0  1  0  0

1200/500Hz @ 1Hz - DIN 

PFEER P.T.A.P.

9

Tone 5

Tone 2

1  1  1  0  0  0

500/1200/500Hz @ 0.3Hz Sweeping

8

Tone 5

Tone 10

0  1  1  0  0  0

2400/2900Hz @ 1Hz Sweeping

7

Tone 5

Tone 7

1  0  1  0  0  0

2400/2900Hz @ 7Hz Sweeping

6

Tone 20

Tone 3

0  0  1  0  0  0

2400Hz Continuous

5

Tone 5

Tone 6

1  1  0  0  0  0

800/1000Hz @ 1Hz Sweeping

4

Tone 5

Tone 2

0  1  0  0  0  0

500/1200Hz @ 0.3Hz sec
Slow Whoop

3

Tone 5

Tone 17

1  0  0  0  0  0

800/1000Hz @ 0.25 sec Alternating

2

1  2  3  4  5  6

Tone 5

Tone 2

0  0  0  0  0  0

340Hz Continuous

1

Stage 3

Stage 2

Switch

Frequency Description

Stage 1

 

Fig. 9 Dip Switch 

 

1=ON; 0=OFF 
Example shown: 100000 = Tone 2 (Default setting) 

 

Summary of Contents for E2 C1LD2F Series

Page 1: ...rtificate No DEMKO 06ATEX 0421554X IECEx ULD 14 0012X The E2xC1LD2 combined alarm horn and LED beacon is rated as follows CE Marking Zones Gas Dust Groups and Temperature Classification When connected...

Page 2: ...24 18 30Vdc 346mA 284mA E2xC1LD2FDC048 E2xC1LD2RDC048 42 54Vdc 115mA 146mA E2xC1LD2FAC115 E2xC1LD2RAC115 115 120Vac 50 60Hz 102 4mA 104mA E2xC1LD2FAC230 E2xC1LD2RAC230 220 230Vac 50 60Hz 49 4mA 54mA I...

Page 3: ...s and cable glands must be used as per table below Ambient Temp 40 C 45 C 50 C 55 C Min Rating of cables and cable glands 90 C 95 C 100 C 105 C If a high IP Ingress Protection rating is required then...

Page 4: ...d be removed from both sets of terminal blocks refer to fig 3b 5b 9 AC Wiring A 6 way terminal block is provided on the AC Sounder for power There are 2 off Live 2 off Neutral and 2 off Earth terminal...

Page 5: ...here are 2 off ve 2 off ve 1 off stage2 and 1 off stage 3 terminals in total 10 1 Wiring Diagrams Fig 5a E2xC1LD2 DC Simplified Block Diagram for Simultaneous Beacon Sounder Operation Pre wired Connec...

Page 6: ...e resistor legs as shown in Fig 9a remove the ve and ve terminal plugs and fit the resistor across the two terminal plugs before refitting them to the PCBA as shown in Fig 9b A spacing of at least 1 1...

Page 7: ...and overhaul of the equipment should only be carried out by suitably qualified personnel in accordance with the current relevant standards EN60079 19 IEC60079 19 Explosive atmospheres Equipment repai...

Page 8: ...1 1 0 554Hz Continuous 27 Tone 15 Tone 2 1 0 0 1 1 0 Bell 26 Tone 5 Tone 29 0 0 0 1 1 0 2400 2900Hz 50Hz Sweeping 25 Tone 5 Tone 29 1 1 1 0 1 0 800 1000Hz 50Hz Sweeping 24 Tone 5 Tone 6 0 1 1 0 1 0 8...