Document No. D211-00-651-IS

 

Issue 1

 

20-08-22

 

 

Sheet 1 of 8

 

 

INSTRUCTION MANUAL 

D2XC2XH1 & D2XC2XH2 UL1971 Alarm Horn and Xenon 
Beacon for use in Hazardous Locations 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

1) 

Product Table 

 
 
 
 
 
 
 
 

 

2) 

Warnings 
 

 DO NOT OPEN WHEN AN EXPLOSIVE 

ATMOSPHERE IS PRESENT 

 DO NOT OPEN WHEN ENERGISED 

 POTENTIAL ELECTROSTATIC CHARGING 

HAZARD - CLEAN ONLY WITH A DAMP 
CLOTH 

 HIGH VOLTAGE SHOCK HAZARD. WAIT 5 

MINUTES AFTER REMOVING POWER 
BEFORE OPENING THE ENCLOSURE 
 

Avertissement: 

 NE PAS OUVRIR UN PRESENCE 

D’ATMOSPHERE EXPLOSIVE 

 NE PAS OUVRIR ENERGIE 

 DANGER POTENTIEL CHARGE 

ÉLECTROSTATIQUE - NETTOYER 
UNIQUEMENT AVEC UN CHIFFON HUMIDE 

 HAUT TENSION, RISK DE CHOC. ATTENDEZ 

5 MINUTES APRES AVOIR DEBRANCHE 
L’ALIMENTATION AVANT D’OUVRIR LA 
BOITIER 

 

3) 

Rating & Marking Information 

 

3.1. Public Mode Fire Alarm Ratings 

 
The D2xC2XH1 and D2xC2XH2 are certified for use as public 
mode  audible  and  visual  alarm  devices  in  accordance  with 
UL1971 / UL1638 & UL464. 
 
See fire instructions D211-00-651-IS-SC-UL 
 
 
 

3.2. ATEX / IECEx / UKEx certification 

 

Standards 

EN IEC 60079-0:2018 / IEC60079-0:2017 (Ed 7): 

Explosive Atmospheres - Equipment. General Requirements 

EN IEC 60079-7:2015 +A1:2018 / IEC 60079-7:2018 (Ed. 5.1): 

Explosive Atmospheres - Equipment Protection by Increased 

Safety "e" 

EN 60079-31:2014 / IEC 60079-31:2013 (Ed 2): 

Explosive Atmospheres - Equipment Dust Ignition Protection by 
Enclosure "t" 

Ratings 

D2xC2XH1 

Ex ec IIC T3 Gc Ta -40°C to +50°C 
Ex tc IIIC T75°C Dc Ta -40°C to +50°C 

D2xC2XH2 

Ex ec IIC T2 Gc Ta -40°C to +50°C 
Ex tc IIIC T85°C Dc Ta -40°C to +50°C 

 

Certificate No. 

DEMKO 14 ATEX 4786493904X 
IECEx ULD 14.0004X 
UL21UKEX2131X 

ATEX Mark, Equipment 
Group and Category: 

 

II 3G 
II 3D

 

CE Marking 
 

 

 

UKCA Marking 

 

 

 
 
 

 

D2XC2XH1 
D2XC2XH2 

Model 

Nominal Voltage 

Beacon 
Current 

Sounder 

Current

 

D2xC2XH1DC024 

20-28Vdc 

296mA 

313mA 

D2xC2XH2DC048 

48Vdc 

145mA 

181mA 

For detailed max and surge current ratings of the device please see Section 14. 

Table 1: Electrical Ratings 

Summary of Contents for D2XC2XH1

Page 1: ...and D2xC2XH2 are certified for use as public mode audible and visual alarm devices in accordance with UL1971 UL1638 UL464 See fire instructions D211 00 651 IS SC UL 3 2 ATEX IECEx UKEx certification S...

Page 2: ...y Enclosure t Rating D2xC2XH1 Ex ec IIC T3 Gc X Ta 40 C to 50 C Ex tc IIIC T75 C Dc Ta 40 C to 50 C D2xC2XH2 Ex ec IIC T2 Gc X Ta 40 C to 50 C Ex tc IIIC T85 C Dc Ta 40 C to 50 C Installation must be...

Page 3: ...ent is not to be mounted with the horn facing upwards Fig 1 Fixing locations 6 2 Access to the Enclosure Warning High voltage may be present risk of electric shock DO NOT open when energised disconnec...

Page 4: ...user wishes to power the strobe separately For further wiring schematics refer to document D211 06 651 10 Earthing The unit has both internal and external earth points please see fig 2 fig 4 Internal...

Page 5: ...the PCB The alarm horns can also be switched to sound the second third and fourth stage alarm tones The tone table shows the switch positions for the 64 tone and which tones are available for the seco...

Page 6: ...22 Sheet 6 of 8 14 Electrical Ratings 14 1 Operating current Consumption Table 6 Electrical Ratings Model Nom Voltage Voltage Range Flash Rate Setting Max operating current D2xC2XH1DC024 24Vdc 20 28Vd...

Page 7: ...s on 0 5s off x3 1s gap ISO 8201 Temporal Pattern 1 1 0 1 0 0 44 1 8 13 422 775Hz 0 85 on 0 5 off x3 1s gap NFPA Temporal Coded 0 0 1 1 0 0 44 1 8 14 1000 2000Hz 1Hz Singapore 1 0 1 1 0 0 23 3 35 15 3...

Page 8: ...Hz Sweeping 1 0 0 0 1 1 44 24 12 51 600 1250Hz 0 125Hz Sweeping 0 1 0 0 1 1 44 24 12 52 660 1200Hz 1Hz Sweeping 1 1 0 0 1 1 64 24 12 53 800 1000Hz 1Hz Sweeping 0 0 1 0 1 1 56 24 12 54 800 1000Hz 7Hz S...

Page 9: ...alarm use the temporal pattern tone No 12 as per the tone table provided in these instructions must be selected This tone produces a minimum sound pressure level of CAN ULC S525 100 4dB A at 10 feet...

Page 10: ...Dispersion for wall mounting public mode 75 60 45 30 15 0 90 Fig 1 Vertical dispersion angles for wall mounting 55 45 8 18 60 40 7 27 65 35 6 36 70 35 6 36 75 30 5 45 80 30 5 45 85 25 4 55 90 25 4 55...

Page 11: ...ght Output Dispersion for Wall Mounting Viewing Angle Of Rating Intensity cd at 1Hz flash rate 0 100 18 18 5 30 90 16 36 35 65 11 82 40 46 8 36 45 34 6 18 50 27 4 91 55 22 4 00 60 18 3 27 65 16 2 91 7...

Page 12: ...fpm 2 28A 1 19A D2xC2XH2DC024 24Vdc 20 28Vdc 1Hz 60fpm 2 76A 1 35A 4 Sound Directional Characteristics for Canadian Fire CAN ULC S525 Horizontal Axis Angle OSPL Angle OSPL Reference 90 101 2 dB A Refe...

Page 13: ...o Sounder ve ve Stage 2 Apply power to Sounder ve ve Connect Stage 2 to ve Stage 3 Apply power to Sounder ve ve Connect Stage 3 to ve Stage 4 Apply power to Sounder ve ve Connect Stage 2 and Stage 3 t...

Page 14: ...herlands B V Utrechtseweg 310 6812 AR Arnhem Netherlands Quality Assurance Notification Module D SIRA 05 ATEX M342 Provisions fulfilled by the equipment II 3G Ex ec IIC T6 T4 T3 T2 T1 Gc II 3D Ex tc I...

Page 15: ...e and Place of Issue London 22 08 2022 EU Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the m...

Page 16: ...Lane Eccleston Chester CH4 9JN UK Quality Assurance Notification Module D CSAE 22UKQAN0046 Provisions fulfilled by the equipment II 3G Ex ec IIC T6 T4 T3 T2 T1 Gc II 3D Ex tc IIIC Ex tc IIIC T55 75 80...