3.4. NEC & CEC Ratings 

 
NEC & CEC Class / Division Ratings for US / Canada 

 

Standards 

UL1971 Ed. 3 2018 
UL1638 Ed. 5 2017 / CAN/ULC-S526 Ed. 4 
CSA C22.2 No. 205-17 
UL 121201-2021 Edition 9 
CAN/CSA C22.2 No. 213-17 Edition 3 

Ratings 

D2xB1LD3: 
 

Class I Div 2 ABCD T4 Ta -40°C to 50°C 
Class II Div 2 FG T6 Ta -40°C to +50°C 
Class III Div 1&2 Ta -40°C to +50°C 

The certification approval has validated continuous use up to 
38°C and are for transient use up to 50°C ambient. 
 
Installation must be carried out in compliance with the National 
Electric Code / Canadian Electric Code 

 

NEC Class / Zone ratings US 

 

Standards 

UL 60079-0 (Ed. 7): 

Explosive Atmospheres - part 0: Equipment - General 
Requirements  

UL 60079-7 (Ed. 5): 

Explosive Atmospheres - Equipment Protection by Increased 

Safety "e" 

UL 60079-31 (Ed. 2) 

Explosive Atmospheres - Equipment Dust Ignition Protection by 

Enclosure "t"

 

Ratings 

D2xB1LD3: 
 

Class I Zone 2 AEx ec IIC Gc T4 Ta -40°C to 
+50°C 
AEx tc IIIC T75°C Dc Ta -40°C to +50°C 

Installation must be carried out in compliance with the National 
Electric Code. 

 

CEC Class / Zone ratings Canada 
 

Standards 

CAN/CSA C22.2 No. 60079-0 (Ed. 4) 02/2019 

Explosive Atmospheres - Part 0: Equipment - General 
Requirements  

CAN/CSA C22.2 No. 60079-7 (Ed. 2) 

Explosive Atmospheres - Equipment Protection by Increased 

Safety "e" 

CAN/CSA C22.2 No. 60079-31 (Ed. 2) 

Explosive Atmospheres - Equipment Dust Ignition Protection by 

Enclosure "t"

 

Rating 

D2xB2LD3: 

 

Ex ec IIC Gc X T4 Ta -40°C to +50°C 
Ex tc IIIC T75°C Dc X Ta -40°C to +50°C 
 

Installation must be carried out in compliance with the Canadian 
Electric Code 

 

4)  Zones, Gas / Dust Groups and 

Temperature Classification 

 

When connected to an approved system the D2XB1LD3 LED 
beacon may be installed in: 
 

Area Classification 

Zone 2 

Explosive gas air mixture not likely to occur in 
normal operation, and if it does, it will only 
exist for a short time. 

Zone 22 

Explosive dust air mixture not likely to occur in 
normal operation, and if it does, it will only 
exist for a short time. 

Gas Groupings 

Group IIA 

Propane 

Group IIB 

Ethylene 

Group IIC 

Hydrogen and Acetylene 

Temperature Classification for Gas Applications 

T1 

450ºC  

T2 

300ºC 

T3 

200ºC 

T4 

135°C 

Dust Groupings 

(ATEX / IECEx / UKEX only) 

Group IIIA 

Combustible Flyings 

Group IIIB 

Non-conductive Dust 

Group IIIC 

Conductive Dust 

Maximum Surface Temperature for Dust Applications 

(ATEX / IECEx / UKEX only) 

D2xB1LD3: 

75°C 

Equipment Category 

3G / 3D  

Equipment Level Protection 

Gc, Dc 

Ambient Temperature Range 

-40°C to +50°C 

IP Rating 

IP6X to EN/IEC60079-0 

IP66 to EN60529 
To maintain the ingress protection rating, the two off cable entries 
must be fitted with suitably rated, certified cable entry and/or 
blanking devices during installation. 

Type Rating 

Per UL50E / NEMA250: 4 / 4X / 3R / 13

 

 

 
 
 
 
 
 
 

Summary of Contents for D2xB1LD3

Page 1: ...dels are approved for use as a Visual Appliance for use in Private Mode Fire Alarm Systems in accordance with UL1638 Fifth Edition CAN ULC S526 Fourth Edition See fire instruction manual D211 00 471 IS SC UL 3 3 ATEX IECEx UKEx Ratings Standards EN IEC 60079 0 2018 IEC60079 0 2017 Ed 7 Explosive Atmospheres Equipment General Requirements EN IEC 60079 7 2015 A1 2018 IEC 60079 7 2018 Ed 5 1 Explosiv...

Page 2: ...ments CAN CSA C22 2 No 60079 7 Ed 2 Explosive Atmospheres Equipment Protection by Increased Safety e CAN CSA C22 2 No 60079 31 Ed 2 Explosive Atmospheres Equipment Dust Ignition Protection by Enclosure t Rating D2xB2LD3 Ex ec IIC Gc X T4 Ta 40 C to 50 C Ex tc IIIC T75 C Dc X Ta 40 C to 50 C Installation must be carried out in compliance with the Canadian Electric Code 4 Zones Gas Dust Groups and T...

Page 3: ...e using the 2 off M5 X 8mm countersunk screws provided Additional feet are available as spare parts if required The unit can also be pole mounted using the NPT Entry in the centre of the base See Fig 1 116 0mm 4 52in 116 0mm 4 52in 168 0mm 6 55in 130 1mm 5 07in 132 4mm 5 17in Ø6 92mm Ø0 270in 3 4 NPT For pole mount M5 X 8mm Countersunk screw customer to fix Fig 1 Fixing Locations 6 2 Access to the...

Page 4: ...nal blocks are provided on the beacon for power There are 2 off ve 2 off ve terminals in total For further wiring schematics refer to document D211 06 451 9 1 PCBA Terminals Fig 4 D2xB1LD3 Terminals 9 2 Line Monitoring DC reverse line monitoring can be used if required All beacons have a blocking diode fitted in their supply input lines An end of line monitoring resistor can be connected across th...

Page 5: ...e repair and overhaul of the equipment should only be carried out by suitably qualified personnel in accordance with the current relevant standards IEC EN60079 19 Explosive atmospheres Equipment repair overhaul and reclamation IEC EN60079 17 Explosive atmospheres Electrical installations inspection and maintenance To avoid a possible ELECTROSTACTIC CHARGE the unit must only be cleaned with a damp ...

Page 6: ...t Consumption Table 4 Electrical Ratings Model Nom Voltage Voltage Range Flash Rate Setting Nom operating current Max operating current D2xB1LD3DC024 24Vdc Regulated 16 33Vdc 1Hz 60fpm 153mA 465mA 1 33Hz 80fpm 189mA 488mA 1 5 Hz 90fpm 203mA 456mA 2Hz 120fpm 248mA 528mA For Public Mode or private mode Fire Alarm use nominal rms current at nominal voltage max rms current at worst case voltage in vol...

Page 7: ...onducted by UL using a total of 6 units connected to the same wire run Auto synchronization does not require the use of any external sync modules or protocols Providing the correct cable has been selected an unlimited number of units will remain synchronized when powered from the same source 2 2 Private Mode Fire Alarm Ratings D2xB1LD3 is approved for use as Visual Appliance for use in Fire Alarm ...

Page 8: ...3Hz flash rate Intensity cd at 1 5Hz flash rate Intensity cd at 2Hz flash rate 0º 100 80 1 77 1 77 3 82 1 5º 90 72 1 69 4 69 5 73 9 10º 90 72 1 69 4 69 5 73 9 15º 90 72 1 69 4 69 5 73 9 20º 90 72 1 69 4 69 5 73 9 25º 90 72 1 69 4 69 5 73 9 30º 75 60 1 57 8 58 0 61 6 35º 75 60 1 57 8 58 0 61 6 40º 75 60 1 57 8 58 0 61 6 45º 75 60 1 57 8 58 0 61 6 50º 55 44 1 42 4 42 5 45 2 55º 45 36 0 34 7 34 8 37 ...

Page 9: ...º 75 60 1 57 8 58 0 61 6 35º 75 60 1 57 8 58 0 61 6 40º 75 60 1 57 8 58 0 61 6 45º 75 60 1 57 8 58 0 61 6 50º 55 44 1 42 4 42 5 45 2 55º 45 36 0 34 7 34 8 37 0 60º 40 32 0 30 8 30 9 32 9 65º 35 28 0 27 0 27 0 28 8 70º 35 28 0 27 0 27 0 28 8 75º 30 24 0 23 1 23 2 24 6 80º 30 24 0 23 1 23 2 24 6 85º 25 20 0 19 3 19 3 20 5 90º 25 20 0 19 3 19 3 20 5 45º Compound 24 19 2 18 5 18 5 19 7 All light outpu...

Page 10: ...N POTTS R S RAIT B ISARD 17 05 2022 MOD No REASON INITIAL DATE ISSUE 1 INTRODUCTION DH 17 05 2022 D2x DC LED D2XB1LD3 UNITS Line Monitoring Power ve and ve R1 ve IN ve OUT ve IN ve OUT OPTIONAL LINE MONITORING RESISTOR CUSTOMER SUPPLIED REQUIRED MINIMUM VALUES R1 24VDC 1KΩ MIN 2W MIN OR 3K9Ω MIN 0 5W MIN 17 05 2022 17 05 2022 ...

Page 11: ...therlands B V Utrechtseweg 310 6812 AR Arnhem Netherlands Quality Assurance Notification Module D SIRA 05 ATEX M342 Provisions fulfilled by the equipment II 3G Ex ec IIC T6 T4 T3 T2 T1 Gc II 3D Ex tc IIIC Ex tc IIIC T55 75 80 85 90 95 105 110 C Dc IP66 Ingress Dust Protection to EN60079 0 EN60079 31 Standards applied EN IEC 60079 0 2018 EN IEC 60079 7 2015 A1 2018 EN 60079 31 2014 Directive 2014 3...

Page 12: ...te and Place of Issue London 22 08 2022 EU Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the market the equipment conforms with all technical and regulatory requirements of the above listed directives regulations and standards This Declaration is issued under the sole responsibility of the ma...

Page 13: ... Lane Eccleston Chester CH4 9JN UK Quality Assurance Notification Module D CSAE 22UKQAN0046 Provisions fulfilled by the equipment II 3G Ex ec IIC T6 T4 T3 T2 T1 Gc II 3D Ex tc IIIC Ex tc IIIC T55 75 80 85 90 95 105 110 C Dc IP66 Ingress Dust Protection to EN60079 0 EN60079 31 Standards applied EN IEC 60079 0 2018 EN IEC 60079 7 2015 A1 2018 EN 60079 31 2014 Directive 2014 30 EU Electromagnetic Com...

Page 14: ... Place of Issue London 22 08 2022 UKCA Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the market the equipment conforms with all technical and regulatory requirements of the above listed directives regulations and standards This Declaration is issued under the sole responsibility of the manufa...

Reviews: