background image

 

 

European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH

 

www.e2s.com

 

Tel: +44 (0)208 743 8880

 

Document No. D190-00-101-IS

 

Issue 2

 

17-03-2022

 

 

Sheet 2 of 8

 

 

3)  Marking & Rating Information 

 

The  D1xS2  Alarm  Horns  comply  with  the  following  standards  for 
hazardous locations:  

 

3.1 

Class/Division Ratings for US & Canada 

 

Standards 

Class I UL 1203 & CSA C22.2 No 30-M1986

 

Class Division Ratings for US (NEC) 

Model No: 

Rating 

D1xS2-DC024-A  / 
D1xS2-AC230-A 

 

Class I Div 1 ABCD T4A Ta -55°C to +85°C 
Class I Div 1 ABCD T5 Ta -55°C to +80°C 
Class I Div 1 ABCD T6 Ta -55°C to +65°C 

Class Division Ratings for Canada (CEC)

 

Model No:

 

Rating

 

D1xS2-DC024-A  

Class I Div 1 ABCD T4A Ta -55°C to +85°C 
Class I Div 1 ABCD T5 Ta -55°C to +80°C 
Class I Div 1 ABCD T6 Ta -55°C to +65°C 

D1xS2-AC230-A 

Class I Div 1 ABCD T6 Ta -55°C to +40°C 

Class Zone Ratings for US (NEC)

 

Model No:

 

Rating

 

D1xS2-DC024-A  / 
D1xS2-AC230-A 

Class I Zone 1 IIC T4A Ta -55°C to +85°C 
Class I Zone 1 IIC T5 Ta -55°C to +80°C 
Class I Zone 1 IIC T6 Ta -55°C to +65°C 

Class Zone Ratings for Canada (CEC)

 

Model No:

 

Rating

 

D1xS2-DC024-A  

Class I Zone 1 IIC T4A Ta -55°C to +85°C 
Class I Zone 1 IIC T5 Ta -55°C to +80°C 
Class I Zone 1 IIC T6 Ta -55°C to +65°C 

D1xS2-AC230-A 

Class I Zone 1 IIC T6 Ta -55°C to +40°C 

Installation must be carried out in compliance with the National 
Electric Code / Canadian Electric Code 

3.2 

ATEX / IECEx & UKEx Ratings 

 

Standards 

EN60079-0:2018/IEC60079-0:2017  (ed.7):  Explosive  Atmospheres  - 
Equipment General Requirements. 
EN60079-1:2014/IEC60079-1:2014  (ed.7):  Explosive  Atmospheres  - 
Equipment Protection by Flameproof Enclosures “d”.  
EN60079-31:2014/IEC60079-31:2013  (ed.2):  Explosive  Atmospheres  - 
Equipment Dust Ignition Protection by enclosure “t”.

 

Model No: 

Rating 

D1xS2-DC024-A 

Ex db IIC T5 Gb Ta 

–55°C to +75°C 

Ex db IIC T6 Gb Ta 

–55°C to +60°C 

Ex tb IIIC T95°C Db Ta 

–55°C to +75°C 

D1xS2-AC230-A 

Ex db IIC T5 Gb Ta 

–55°C to +75°C 

Ex db IIC T6 Gb Ta 

–55°C to +60°C 

Ex tb IIIC T93°C Db Ta 

–55°C to +75°C 

See Product table for electrical ratings of each unit model

 

Certificate No.    

DEMKO  19ATEX2141X  
IECEx ULD 19.0008X 

 

UKEx UL UL21UKEX2132X          

Epsilon x 
Equipment Group 
and Category: 

 

II 2G 
II 2D

 

CE Marking and 
Notified Body No.

 

 

2813

 

UKCA Marking and 
Notified Body No. 

 

 

0518 

4)  Zones, Gas Group, Category and 

Temperature Classification 

 

The units can be installed in locations with the following conditions: 

 

Area Classification Gas 

Zone 1 

Explosive gas air mixture likely to occur in normal 
operation. 

Zone 2 

Explosive gas air mixture not likely to occur in 
normal operation, and if it does, it will only exist for 
a short time. 

Gas Groupings 

Group IIA 

Propane 

Group IIB 

Ethylene 

Group IIC 

Hydrogen and Acetylene 

Temperature Classification for Gas Applications 

T1 

450

o

 C  

T2 

300

o

 C 

T3 

200

o

 C 

T4 

135

o

 C 

T5 

100ºC 

T6 

85ºC (D1xS2 up to 60°C ambient) 

Area Classification Dust 

Zone 21 

Explosive dust air mixture likely to occur in normal 
operation. 

Zone 22 

Explosive dust air mixture not likely to occur in 
normal operation, and if it does, it will only exist for 
a short time. 

Dust Groupings 

Group IIIA 

Combustible Dusts 

Group IIIB 

Non-Conductive Dusts 

Group IIIC 

Conductive Dusts 

Equipment Category 

2G, 2D

 

Equipment Protection Level 

Gb, Gc, Db, Dc

 

Maximum Surface Temperature for Dust Applications 

95°C (D1xS2-DC024-A) 
93°C (D1xS2-AC230-A)  

Ambient Temperature Range 

-55°C to +75°C (-67°F to +167°F) 

IP Rating 

IP66 to EN60529 
4 / 4X / 3R / 13 to UL50E / NEMA250 

Installation must be carried out in compliance with the latest issue 
of the following standards: 
  
EN60079-14  /  IEC60079-14:  Explosive  atmospheres  -  Electrical 
installations design, selection and erection 
EN60079-10-1  /  IEC60079-10-1:  Explosive  atmospheres  - 
Classification of areas. Explosive gas atmospheres 
EN60079-10-2  /  IEC60079-10-2:  Explosive  atmospheres  - 
Classification of areas. Explosive dust atmospheres 

 
 

 

Summary of Contents for D1xS2FAC230-A

Page 1: ...S ATMOSPHERES DISCONNECT FROM SUPPLY BEFORE OPENING KEEP TIGHTLY CLOSED WHEN IN OPERATION WARNING FIT SEALING FITTING IN CONDUIT RUNS WITHIN 18 INCHES FROM ENCLOSURE EQUIPMENT MUST NOT BE INSTALLED WI...

Page 2: ...C Ex tb IIIC T95 C Db Ta 55 C to 75 C D1xS2 AC230 A Ex db IIC T5 Gb Ta 55 C to 75 C Ex db IIC T6 Gb Ta 55 C to 60 C Ex tb IIIC T93 C Db Ta 55 C to 75 C See Product table for electrical ratings of eac...

Page 3: ...arges on non conducting surfaces Only the explosionproof cover is to be used for access to the enclosure for installation service and maintenance 6 Specific Conditions for Safe Use Flameproof threaded...

Page 4: ...nd the length of the cable runs The cable size selected must have the necessary capacity to provide the input current to all the sounders connected to the line AC 1 0 2 5mm2 AWG18 AWG12 DC 0 2 2 5mm2...

Page 5: ...ders See schematic diagram D190 06 001 for details 9 1 Configuration See Table 1 for product power supply and Sound Pressure Levels SPL Configuration for DC Units Fig 5 DC PCBA Configuration for AC Un...

Page 6: ...iring options Config Voltage Configuration Description Features Product Option Identifier 1a DC Single Stage Configuration Line monitoring Positive Switching 1 1b DC Two Stage Configuration Common Neg...

Page 7: ...f Line Monitoring An optional 12 way terminal module is available to enable up to four alarm stages to be activated from three DC voltage output channels The three alarm stage activation inputs can be...

Page 8: ...ces may be fitted between the ve ve terminals of the PCBA Please ensure that the device legs meet the wire size range stated for the connection terminals and are fitted correctly in order to avoid a s...

Page 9: ...0 0 0 1 0 1 0 0 0 0 1 1 0 0 0 1 1 1 0 0 0 0 0 0 1 0 0 1 0 0 1 0 0 0 1 0 1 0 0 1 1 0 1 0 0 0 0 1 1 0 0 1 0 1 1 0 0 0 1 1 1 0 0 1 1 1 1 0 0 0 0 0 0 1 0 1 0 0 0 1 0 0 1 0 0 1 0 1 1 0 0 1 0 0 0 1 0 1 0 1...

Page 10: ...US 100 2dB A CA 108 5dB A P3 US 103 5dB A CA 111 6dB A at 10 feet 24Vdc For Fire Alarm applications the Sounder Volume must be at the highest setting see volume control section For fire alarm use Ton...

Page 11: ...al Axis 3dB A 39 41 38 41 6dB A 45 47 64 69 D1xS2FDC024 A D1xS2FDC024 S Sounder Directional Characteristics for Canadian Fire CAN ULC S525 P3 OSPL Horizontal Axis Vertical Axis 3dB A 46 48 46 47 6dB A...

Page 12: ...INE MONITORING RESISTOR CUSTOMER SUPPLIED 14V MAX SYSTEM 120 MIN 2W MIN OR 1K MIN 0 5W MIN 28V MAX SYSTEM 470 MIN 2W MIN OR 2 4K MIN 0 5W MIN RECOMMENDED MINIMUM VALUES R1 Stage 1 ve IN Stage 1 ve OUT...

Page 13: ...n ve OUT Stage 1 ve OUT Stage 3 ve Stage 1 ve IN H2 H1 Stage 1 ve Stage 1 ve Stage 2 ve Stage 2 ve OF 2 3 R1 S2 S3 R1 S2 R2 OPTIONAL LINE MONITORING RESISTOR CUSTOMER SUPPLIED 14V MAX SYSTEM 120 MIN 2...

Page 14: ...er to Stage 2 ve Stage 2 ve Two Three Stage Voltage Free Activation Configuration Config 5 Customer Set H1 H2 to Negative Switching See Below Power ve ve Stage 1 Connect Stage 1 ve to Common ve Stage...

Page 15: ...5 R S RAIT B ISARD R N POTTS OF NTS 1 SWITCHES FOR STAGE OPERATION CUSTOMER SUPPLIED 1 Earth Earth Stage 2 Stage 3 Common Live IN Live OUT Neutral IN Neutral OUT Earth Stage 1 Stage 2 Common N N L L E...

Page 16: ...warden Industrial Park Hawarden Deeside CH5 3US UK Quality Assurance Notification Module D SIRA 05 ATEX M342 Provisions fulfilled by the equipment II 2G Ex db IIC T6 T3 GB II 2D Ex tb IIIC T82 C 145 C...

Page 17: ...e and Place of Issue London 10 02 2022 EU Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the m...

Page 18: ...CH4 9JN UK Quality Assurance Notification Module D CSAE 22UKQAN0046 Provisions fulfilled by the equipment II 2G Ex db IIC T6 T3 GB II 2D Ex tb IIIC T82 C 145 C Db Standards applied EN 60079 0 2018 EN...

Page 19: ...ate and Place of Issue London 24 02 2022 EU Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the...

Page 20: ...Page left Intentionally blank...

Reviews: