9)  AC Wiring

 

 

9.1  Wiring Diagrams

 

 

 
 
 
 
 
 
 
 
 
 

 

 

Fig 5a. D1xS1AC Simplified Block Diagram 

 
 

 
 
 
 
 
 
 
 
 
 
 

 

Fig 5b. D1xS2AC Simplified Block Diagram 

 
9.2 Units First Stage Tones 

Stage one (S1) operation: Simply connect the supply voltage to 
the L and N supply terminals, (see fig. 6). 

 
9.3  AC  Units  Second,  Third  and  Fourth  Stage  Tone 
Selection 

To select the second, third and fourth stage tones on the D1x 
AC alarm horns. 
Stage two (S2) operation: Power L and N, link the Common-C 
(D1xS2) or the Live-L (D1xS1) and S2 terminal. 
Stage three (S3) operation: Power L and N, link the  Common-
C (D1xS2) or the Live-L (D1xS1) and S3 terminals. 
Stage four (S4) operation: Power L and N, link the Common-C 
(D1xS2)  or  the  Live-L  (D1xS1)  and  both  the  S2  and  S3 
terminals.  
 
 
 
 
 
 
 
 
 
 
 

 

 
 
 

 

D1xS1AC Terminals 

 

D1xS2AC Terminals

 

 

Fig. 6 AC Terminals 

 
 
 
 
 
 
 
 

10)  DC Wiring 

 

10.1 Wiring Diagrams

 

 

 

 
 
 
 
 
 
 
 

 
 
 
Fig. 7a DC Simplified Block Diagram (negative 
switching) 
 

 
 
 
 
 
 
 
 
 
 
 

 

Fig.  7b  DC  Simplified  Block  Diagram  (positive 
switching

 

 
10.2  Units First Stage Tones 

Stage one (S1) operation: Simply connect the supply voltage to 
the + and - supply terminals, (see fig. 8). 

 
10.3  DC  Units  Second,  Third  and  Fourth  Stage  Tone 
Selection 

For units set up for 

–ve switching (default setting): 

 

Stage two (S2) operation: Power +ve and 

–ve, link a -ve supply 

line to the S2 terminal. Dip switch 2 alters stage 2 tone. 
Stage  three  (S3)  operation:  Power  +ve  and 

–ve,  link  a  -ve 

supply line to the S3 terminal. Dip switch 1 alters stage 3 tone. 
Stage  four  (S4)  operation:  Power  +ve  and 

–ve,  link  a  -ve 

supply  line  to  both  the  S2  &  S3  terminals.  Dip  switch  1  alters 
stage 4 tone. 
 
For units set up for +ve switching (refer to 9.1): 

 

Stage  two  (S2)  operation:  Power  +ve  and 

–ve,  link  a  +ve 

supply line to the S2 terminal. Dip switch 2 alters stage 2 tone. 
Stage  three  (S3)  operation:  Power  +ve  and 

–ve,  link  a  +ve 

supply line to the S3 terminal. Dip switch 1 alters stage 3 tone. 
Stage  four  (S4)  operation:  Power  +ve  and 

–ve,  link  a  +ve 

supply  line  to  both  the  S2  &  S3  terminals.  Dip  switch  1  alters 
stage 4 tone. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Fig. 8 DC Terminals 

 

 

STAGE 4 = S2 + S3 
(Customer Supplied switches)

 

L L N N E E S2 S3

 

L L N N E C S2 S3

 

STAGE 4 = S2 + S3 
(Customer Supplied switches)

 

STAGE 4 = S2 + S3 
(Customer Supplied switches) 

STAGE 4 = S2 + S3 
(Customer Supplied switches)

 

+ + - - 

S2 S3 

Summary of Contents for D1xS1 Series

Page 1: ...ENTIEL CHARGE LECTROSTATIQUE NETTOYER UNIQUEMENT AVEC UN CHIFFON HUMIDE 3 Ratings and Markings The D1xS1 and D1xS2 Alarm Horns comply with the following standards for hazardous locations UL 1203 CSA C...

Page 2: ...rical installations design selection and erection EN60079 10 1 IEC60079 10 1 Explosive atmospheres Classification of areas Explosive gas atmospheres 4 Installation 4 1 Safe Installation Requirements T...

Page 3: ...y to remove the explosionproof cover to gain access to the explosionproof chamber This can be achieved by unscrewing the explosionproof cover counter clockwise taking extreme care not to damage the ex...

Page 4: ...Simplified Block Diagram negative switching Fig 7b DC Simplified Block Diagram positive switching 10 2 Units First Stage Tones Stage one S1 operation Simply connect the supply voltage to the and suppl...

Page 5: ...f 0 82mm2 18AWG in size 12 End Of Line Monitoring DC Units Only On D1xS1DC D1xS2DC units dc reverse line monitoring can be used if required All DC alarm horns have a blocking diode fitted in their sup...

Page 6: ...9 34 1 10 1000Hz 1s on 1s off x7 7s on 1s off IMO Code 1a 1 0 0 1 0 0 10 34 1 11 420Hz 0 5s on 0 5s off x3 1s gap ISO 8201 Temporal Pattern 0 1 0 1 0 0 11 1 8 12 1000Hz 0 5s on 0 5s off x3 1s gap ISO...

Page 7: ...0 1 48 24 12 49 560 1055Hz 0 18Hz Sweeping 0 0 0 0 1 1 49 24 12 50 560 1055Hz 3 3Hz Sweeping 1 0 0 0 1 1 50 24 12 51 600 1250Hz 0 125Hz Sweeping 0 1 0 0 1 1 51 24 12 52 660 1200Hz 1Hz Sweeping 1 1 0 0...