__________________________________________________________________________________________________________________
European Safety Systems Ltd.
Impress House, Mansell Road, Acton, London W3 7QH [email protected] Tel: +44 (0)208 743 8880
www.e2s.com Fax: +44 (0)208 740 4200
Document No. D190-00-011-IS-SC Issue: 5 24-04-19 Sheet 2 of 7
1) 18-30Vdc for Fire Alarm Use
2) Nom. rms current draw at nom. voltage and worst case tone
3) Max. rms current draw at worst case voltage and tone
3.7 Surge Current for Fire Alarm use per UL Listing
Part No.
Voltage
Peak Surge
Current
RMS surge
Current
D1xS1-DC024
30Vdc
8.36A @
1.44ms
966mA
D1xS2-DC024
30Vdc
9.92A @
1.02ms
1.09A
Surge current given at worst case voltage and tone
3.8
ATEX / IECEx certification
The D1xS1 Alarm Horns comply with the following standards
for hazardous locations:
EN60079-0:2018/ IEC60079-0: ed. 7.0 (2017)
EN60079-1:2014 / IEC60079-1: ed. 7.0 (2014-06)
The D1xS1 Alarm Horns are rated as follows:
Ex db IIC T5 Gb Ta -40°C to +75°C
Ex db IIC T6 Gb Ta -40°C to +70°C
Model No.:
D1xS1
Input Voltage: DC Units 24V
AC Units 115V or 230V
Certificate No.
DEMKO 19 ATEX 2141X
IECEx ULD 19.0008X
The units can be installed in locations with the following
conditions:
Area Classification Gas:
Zone 1
Explosive gas air mixture likely to occur in
normal operation.
Zone 2
Explosive gas air mixture not likely to occur
in normal operation, and if it does, it will
only exist for a short time.
Gas Groupings:
Group IIA
Propane
Group IIB
Ethylene
Group IIC
Hydrogen and Acetylene
Temperature Classification:
T1
450ºC
T2
300ºC
T3
200ºC
T4
135ºC
T5
100ºC
T6
85ºC
Equipment Category:
2G
Equipment Protection Level:
Gb, Gc
Ambient Temperature Range:
-40
°
C to +75
°
C
Installation must be carried out in compliance with the latest
issue of the following standards:
EN60079-14 / IEC60079-14: Explosive atmospheres -
Electrical installations design, selection and erection
EN60079-10-1 / IEC60079-10-1: Explosive atmospheres -
Classification of areas. Explosive gas atmospheres
4)
Installation
4.1 Safe Installation Requirements
The product must only be installed by suitably qualified
personnel in accordance with the latest issues of the relevant
standards.
The installation of the units must also be in accordance with
the NEC / CEC and any local regulations and should only be
carried out by a competent electrical engineer who has the
necessary training.
4.2 Specific Conditions of Use
To maintain the ingress protection rating and mode of
protection, the cable entries must be fitted with suitably rated
cable entry and/or blanking devices during installation. If
conduit is used for installation, seal conduit within 18 inches
from the enclosure.
If entries are fitted with adaptors they must be suitably rated for
the application. Fitting of blanking elements into adaptors is not
permitted.
If a high IP (Ingress Protection) rating is required then a
suitable sealing washer or O-ring must be fitted under any
cable gland or blanking device with metric threads.
Only the explosionproof cover is to be used for access to the
enclosure for installation, service and maintenance.
Connections are to be made into the terminal blocks using
solid or stranded wire, sizes 0.5-2.5mm
2
/ AWG 20-14. Wire
insulation needs to be stripped 6-7mm. Wires may be fitted
securely with crimped ferrules. Terminal screws need to be
tightened down with a tightening torque of 0.4 Nm / 3.5 Lb-in.
Earthing connections should be made to the Internal Earth
terminal in the explosionproof chamber or the external earth
stud.
Check that the ‘O’ ring seal is in place before replacing the
explosionproof cover.
If temperature exceeds 70°C at entry or 80°C at branching
point use suitable rated cable and cable glands
:
Max. ambient temperature
75ºC
Req. Cable / Cable Gland
Rating: (D1xS1DC024 Only)
85ºC
0518
II 2G
Epsilon x
Equipment Group and
Category:
CE Marking
Notified Body No.